![REMKO PWW 100 Series Скачать руководство пользователя страница 15](http://html1.mh-extra.com/html/remko/pww-100-series/pww-100-series_operation_1439015015.webp)
15
Technical data:
Servomotor type KSP
overload-proof
Rating 3.5 W, 230V, 50Hz
Degree of protection IP 54
Operating time about 150 seconds
Maximum ambient temperature
50°C.
Servomotor KSP
(variable speed)
The servomotor type KSP is sup-
plied with 230V.
A transformer converts the system
voltage into a low voltage of 24V.
The motor is controlled depending
on the input voltage and position
of the feedback potentiometer.
The direction of rotation of the
motor can be reversed with the
rotary control switch.
The connection of an electrical
indicator for the flap position and
further servomotors is possible.
Servomotor KSH
(open/closed)
The servomotor is mounted direct-
ly on the flap shaft. It is provided
with a universal terminal block and
is fixed with the supplied locking
element.
The drive is overload-proof and
requires no limit switch.
For manual actuation, the gear can
be disengaged with a self-resetting
pushbutton.
Technical data:
Servomotor Type KSH
overload-proof
Rating 2.5 W, 230V, 50Hz
Degree of protection IP 54
Operating time about 150 seconds
Maximum ambient temperature
50°C.
Typ KSH
N
L1
230V/1~
1 2 3
Aderbezeichnung
Wiring diagram
Stellungsgeber 0-10V
Aderbezeichnung
1 2
3
5
N L1
y
N L1
230V/1~
1
2
3
U
vcc
4
Typ KSP
Wiring diagram
AttENtiON
Installation and repairs to the
electrical installation must
only be carried out by autho-
rised electrical specialists for
safety reasons.
NOtE
All electrical wiring terminals
must be checked for tightness
and retightened if necessary.
injection shutter iJ
The injection shutter is a useful ex-
tension for the REMKO PWW unit
and is designed for direct moun-
ting on the units.
The supply air is optimally blown in
via the injection shutter. The posi-
tion of the air directing fins influ-
ences the air velocity and air outlet
temperature of the total air flow.
This technology provides for a hig-
her blowing range and more rapid
heating of the rooms.
Intake of the already heated room
air prevents the occurrence of
varying air temperatures. The heat
is distributed evenly throughout
the room.
Installation
Unclip the existing fins and fix the
injection shutter with four screws.
The position of the fins can also be
electrically regulated via an optio-
nal control.
Содержание PWW 100 Series
Страница 1: ...Edition GB T08 REMKO PWW Warm water heaters Operation Technology Spare Parts...
Страница 2: ......