  The units must be installed away 

from traffic zones and installed 
by crane, for example

  The units may only be operated 

in completely assembled 
condition

  Safety components (e.g. 

protection grids) must not 
be removed or rendered 
inoperative 

  The units may only be used as 

intended within the specified 
output limits and with the 
approved conveying media 

  The intake protection grid must 

always be free of dirt and loose 
objects; the unit outtake may 
not be covered or closed 

  Never insert foreign objects into 

the unit

  The units may not be exposed 

to direct jets of water

  Do not operate the units in wet 

areas with high humidity (e.g. 
automatic car washes, etc.)

  All electrical cables for the 

units must be protected against 
damage (e.g. by animals etc.)

Unit description

The units are stationary, indirectly 
fuelled recirculation cooling/
heating units with Cu/Al finned 
heat exchangers for connection 
to a pumped cold / hot water 
network up to max. 90 °C. 
 
The units have an exclusive 
and low design, have universal 
applications, and are easy to install 
and service.

NOTE

Fault-free function of the units 
is only guaranteed if the inlet 
temperature at the unit inlet 
and the pump performance are 
appropriate for the selected 
unit classification.

The tube heat exchangers are 
made of copper tubes with 
aluminium fins on top. 
A condensate pump is installed 
ready for connection to remove 
the condensate that occurs in 
cooling mode.

For optimised air guidance, 
individually adjustable fins are 
installed in the top of the housing 
and fins that can be adjusted 
completely are installed in the 
bottom.

The air discharge direction 
(horizontal or vertical) can be 
adjusted individually to the on-site 
requirements my changing the 
fan’s direction of rotation.

The plastic housing can be 
removed from the bearing housing 
parts by removing the locking bar. 
The integrated securing straps 
prevent the hood falling down.

The plastic housing on the 
units consists of materials that 
extinguish themselves in the event 
of fire (corresponding to fire class 
V-0).

The units conform to the 
fundamental health and safety 
requirements of the appropriate 
EU regulations, and are simple to 
operate.

The units are used wherever high 
and low-ceilinged rooms have to 
be heated or cooled and wherever 
great value is placed on exclusivity. 

Examples of large rooms include: 

   Exhibition halls

   Salesrooms

   Malls

   Business premises

   Warehouses

   Production halls

   Design offices

   Large entrance areas

The units must be installed on 
the ceiling or roof structure in 
a horizontal position. 

The units are equipped with 
an aerodynamically designed, 
2-speed, high-performance axial 
fan with a 400V/50 Hz external 
motor. 
The inner, load-bearing unit 
structure is made of galvanised 
steel sheet.

Help by reducing energy 
usage in stand-by operation! 
If the unit, the system or 
the components are not 
being used, we recommend 
disconnecting the power 
supply.  
Our recommendation does 
not apply to safety relevant 
components.

      TIP

Содержание PWL 101-H

Страница 1: ...tions prior to performing any task PWL 101 H PWL 102 H PWL 103 H PWL 201 H PWL 202 H PWL 203 H PWL 301 H PWL 302 H PWL 303 H PWL 101 HK PWL 102 HK PWL 103 HK PWL 201 HK PWL 202 HK PWL 203 HK PWL 301 HK PWL 302 HK PWL 303 HK REMKO PWL series Ceiling mounted ventilation unit ...

Страница 2: ......

Страница 3: ...cal data PWL 201 203 16 Performance tables technical data PWL 301 303 18 Intended use 20 Customer service and guarantee 20 Environmental protection and recycling 20 View of the unit 21 Spare parts list 21 Legend usable limits 22 Technical data 23 Carefully read this original operating manual prior to commissioning using the units This manual is an integral part of the unit and must always be kept ...

Страница 4: ...re Required heating medium temperatures for supply and return flow The air outlet temperature of the units should not fall below 34 C or exceed 42 C If the outlet temperature is below 34 there is the risk of unpleasant cool drafts in the work area If the outlet temperature is higher than 42 C an increased temperature in the ceiling area occurs The casting distance of the warm air flow is reduced a...

Страница 5: ... condensate that occurs in cooling mode For optimised air guidance individually adjustable fins are installed in the top of the housing and fins that can be adjusted completely are installed in the bottom The air discharge direction horizontal or vertical can be adjusted individually to the on site requirements my changing the fan s direction of rotation The plastic housing can be removed from the...

Страница 6: ...s of the primary air flow Maximum installation heights and application limitations The maximum installation heights depend on the maximum casting distance and direction PWL Installation height and casting distance in m with vertical discharge Installation height and casting distance in m with horizontal discharge 101 3 3 8 casting distance 2 3 2 5 casting distance 3 4 201 3 5 5 casting distance 4 ...

Страница 7: ... that are in the top part of the housing This prevents people being exposed to direct airflow Low ceilinged rooms horizontal discharge Low ceilinged rooms horizontal discharge High ceilinged rooms vertical discharge High ceilinged rooms vertical discharge Combined options for heating and cooling mode Due to the triangular shape of the units there are numerous installation arrangements so that even...

Страница 8: ... and return flow We recommend using compensators and automatic bleeders The connection side is on top and the supply and return flow can be connected as required The thread sizes of the pipe connections are R 1 inside thread The finned heat exchangers must be bled carefully after installation is complete Air pockets in the heat exchanger cause a reduction in the heating or cooling capacity Hydraul...

Страница 9: ...regarding anti freeze protection In order to prevent frost damage a frost protection device must be used at temperatures below 0 C In systems that are decommissioned in rooms at risk of freezing the heat exchanger may never contain only water The heating medium water must then be supplemented with a suitable antifreeze with a sufficient mixture ratio for the environment In the process the hydrauli...

Страница 10: ...it and safeguard it to prevent it being opened inadvertently Allow the finned heat exchanger to cool Cleaning the units Only dry clean the unit surfaces or clean with a moistened cloth and some soap solution if necessary Never use high pressure cleaners or steam cleaners on the installed unit Never use abrasive or solvent based cleaners Only suitable cleaners may be used even for heavy contaminati...

Страница 11: ...rical connection 3 Disconnect the hydraulic unit connection 4 Remove the bottom bearing plate 6 screws 5 Remove the bearing plate along with the finned heat exchanger in a downwards direction 6 Install the replacement heat exchanger and all other components carefully in reverse order Replacing the fan 1 Remove the unit housing see Care and maintenance 2 Disconnect the fan s electrical connection 3...

Страница 12: ...g mode The pump is a self priming rotation diaphragm pump The condensate is pumped out via a flexible PVC condensate hose with an inner diameter of 6 mm Safety notes Ensure that the power supply has been disconnected before connecting removing or replacing the condensate pump Do not use the condensate pump to pump flammable and explosive fluids such as petrol heating oil solvents etc The condensat...

Страница 13: ...any way Unit dimensions Dimen sions PWL 101 103 HK PWL 201 203 HK PWL 301 303 HK A 985 mm 1084 mm 1178 mm B 632 mm 963 mm 1043 mm C 229 mm 229 mm 229 mm D 989 mm 1073 mm 1160 mm H 465 mm 485 mm 504 mm Condensate pump The distance between the unit and ceiling must be at least 80 mm 217 80 44 H 16 90 D A C 90 B B B M 8 View A A Condensate hose Hydraulic connection R 1 ...

Страница 14: ... 34 15 5 7 23 5 1 24 9 4 29 8 5 30 12 3 34 10 6 35 20 4 7 27 4 2 27 7 7 32 7 0 33 10 1 36 8 7 37 55 45 C 0 9 9 14 8 8 15 16 1 24 14 5 26 21 1 33 18 1 35 5 8 9 18 7 9 19 14 5 27 13 0 29 18 9 34 16 3 36 10 7 8 21 7 0 22 12 8 29 11 5 31 16 7 36 14 4 38 15 6 8 25 6 1 26 11 1 32 10 0 33 14 6 38 12 5 39 20 5 8 28 5 2 29 9 5 34 8 5 36 12 4 39 10 7 40 60 45 C 0 10 2 15 9 1 16 16 7 25 15 0 27 21 9 34 18 8 ...

Страница 15: ...7 4 0 17 6 7 15 5 8 15 15 25 3 2 21 2 9 21 5 2 18 4 7 18 7 7 16 6 6 15 15 26 3 0 22 2 7 21 4 8 19 4 3 18 7 1 16 6 1 16 16 27 3 4 22 3 0 22 5 6 19 4 9 19 8 1 17 7 0 16 16 32 4 7 26 4 2 25 7 7 22 6 8 21 10 8 18 9 4 18 18 9 14 C 23 2 0 20 1 8 20 3 3 18 2 9 18 5 1 16 4 4 16 16 25 2 4 22 2 2 21 4 0 19 3 6 19 6 1 17 5 2 17 17 26 2 7 22 2 4 22 4 4 20 3 9 19 6 2 17 5 3 17 17 27 2 7 23 2 4 23 4 4 20 3 9 20...

Страница 16: ... 15 6 8 21 6 2 22 12 8 28 11 3 29 16 6 32 14 5 33 20 5 4 25 4 9 26 10 5 31 9 3 31 13 6 34 11 9 35 55 45 C 0 12 7 12 11 4 13 21 9 22 19 3 24 28 3 29 24 7 31 5 11 2 16 10 1 16 19 7 25 17 3 26 25 4 31 22 1 33 10 9 8 19 8 8 20 17 4 28 15 3 29 22 5 33 19 6 35 15 8 4 23 7 5 24 15 1 30 13 4 31 19 6 35 17 1 36 20 6 9 27 6 2 27 12 9 33 11 4 34 16 6 37 14 5 38 60 45 C 0 12 6 12 11 4 13 22 7 23 20 1 25 29 4 ...

Страница 17: ...18 10 0 17 8 9 16 26 3 3 23 3 0 23 6 9 19 6 2 19 9 3 17 8 3 17 27 3 6 24 3 2 23 7 8 20 7 0 19 10 6 18 9 4 17 32 5 0 27 4 5 27 10 7 22 9 6 22 14 5 20 12 8 19 9 14 C 23 2 0 21 1 8 21 4 7 18 4 3 18 6 5 17 5 7 17 25 2 6 23 2 3 22 5 7 20 5 2 19 7 8 18 7 0 17 26 2 9 23 2 6 23 6 4 20 5 7 19 8 2 18 7 2 18 27 3 1 24 2 8 24 6 2 21 5 6 20 8 5 19 7 5 18 32 4 4 28 4 0 27 9 0 23 8 1 23 12 3 21 10 9 20 11 16 C 2...

Страница 18: ... 9 0 21 6 8 23 14 7 25 10 5 28 21 5 31 12 3 36 20 7 2 25 5 4 26 11 7 28 8 4 30 17 7 33 10 2 38 55 45 C 0 16 5 11 12 3 14 26 7 19 19 0 23 36 7 28 20 7 35 5 14 7 15 10 9 17 23 7 22 16 9 26 32 9 30 18 6 37 10 12 8 19 9 6 21 20 7 25 14 8 28 29 2 32 16 5 38 15 11 0 22 8 2 24 17 8 28 12 7 31 25 4 34 14 4 40 20 9 1 26 6 8 28 14 8 30 10 6 33 21 6 36 12 3 41 60 45 C 0 16 5 11 12 3 14 26 8 19 19 1 23 38 1 2...

Страница 19: ... 1 17 7 7 15 26 4 4 23 3 3 22 7 1 21 5 1 20 12 2 18 7 1 15 27 4 7 24 3 5 23 7 7 21 5 5 20 13 8 18 8 1 16 32 6 5 27 5 1 26 10 6 24 8 0 23 18 8 20 10 9 17 9 14 C 23 2 7 21 2 1 21 4 4 20 3 2 19 8 4 17 5 0 16 25 3 4 23 2 6 22 5 5 21 4 0 20 10 2 18 6 0 16 26 3 8 23 2 9 23 6 3 21 4 5 20 10 7 18 6 1 16 27 4 1 24 3 1 23 6 6 22 4 7 21 11 1 19 6 5 17 32 5 8 28 4 3 27 9 4 25 6 6 23 16 0 21 9 3 18 11 16 C 23 ...

Страница 20: ...units are carefully packed and delivered in stable transport packaging and if applicable on a wooden pallet The packaging materials are environmentally friendly and can be recycled By recycling packaging materials you make a valuable contribution to the reduction of waste and conservation of raw materials Therefore only dispose of packaging material at appropriate collection points Disposal of the...

Страница 21: ...711 1110722 1b Heat exchanger assy 2 1110701 1110712 1110723 1c Heat exchanger assy 3 1110702 1110713 1110724 2 Electr terminal box 1110703 1110714 1110725 3 Unit housing 1110704 1110715 1110726 4 Protective fan grate 1110705 1110716 1110727 5 400V 2 speed fan 1110706 1110717 1110728 6 Support plate top 1110707 1110718 1110729 7 Support plate bottom 1110708 1110719 1110730 8 Air grate side 1110709...

Страница 22: ...ub at the same time On the external motor the impeller and its drive motor are combined in one unit that is optimised for ventilation and in its design The axial fan is balanced statically and dynamically The rotor housing is made of cast aluminium 3 phase drive 400 V 50 Hz Heat class F Enclosure class IP 54 Motor protection Thermal contact TC The winding circuit in the star Y is the low speed The...

Страница 23: ...pacity for assembly 1 m3 h 2030 1685 3110 2580 4300 2650 Ventilation capacity for assembly 2 m3 h 1960 1610 2900 2400 4150 2400 Ventilation capacity for assembly 3 m3 h 1885 1530 2580 2350 3900 1710 Sound pressure level LpA 1m 1 dB A 56 47 61 56 66 59 Hydraulic connection Inches R 1 IT R 1 IT R 1 IT Water volume 2 ltr 1 0 1 6 2 5 1 0 1 8 2 9 1 1 2 0 3 3 Cooling heating medium C Pumped cold hot wat...

Страница 24: ...0 5232 606 260 E mail info remko de URL www remko de REMKO GmbH Co KG Klima und Wärmetechnik Im Seelenkamp 12 32791 Lage Hotline within Germany 49 0 5232 606 0 Hotline International 49 0 5232 606 130 We reserve the right to make technical changes and provide no guarantee as to the accuracy of this data ...

Отзывы: