Troubleshooting and customer service 

 

 

The equipment and components are manufactured using state-of-the-art production methods and tested sev-

eral times to verify their correct function. If malfunctions should occur, please check the functions as detailed

in the list below. For installations with an indoor unit and outdoor unit, refer to the chapter "Troubleshooting

and customer service" in both manuals. Please inform your dealer if the unit is still not working correctly after

all the functional checks have been performed!

Malfunctions

Fault

Possible cause

Checks

Remedy

The unit does not start or

switches it self off

Power outage, under-

voltage, defective mains

fuse / main switch in off

position

Are all other electrical

installations functioning

correctly?

Check voltage if neces-

sary wait until turned on

again.

Damaged mains cable

Are all other electrical

installations functioning

correctly?

Repair by a specialist

Wait time after switching

on is too short

Have approx. 5 minutes

elapsed since the

restart?

Schedule longer waiting

periods

Temperature outside

operating range.

Are the fans in the indoor

unit and outdoor compo-

nent working correctly?

Take into account the

temperature range for

the indoor unit and out-

door component

Electrical surges caused

by thunderstorms

Have there been light-

ning strikes in the area

recently?

Switch off the mains

breaker and switch it

back on. Have it checked

by a specialist

Fault in external conden-

sation pump

Did the pump shut down

due to a fault?

Check and if necessary

clean the pump

The unit does not

respond to the remote

control

Transmission distance

too far / receiver affected

by interference

Does the indoor unit

beep when pressing a

button?

Reduce the distance to

less than 6 m or change

position

Defective remote control

Is the unit running in

manual mode?

Replace the remote con-

trol

Receiver or transmitter

unit exposed to exces-

sive solar radiation

Does it function correctly

in the shade?

Place the receiver &

transmitter unit in the

shade

Electromagnetic fields

are interfering with trans-

mission

Does it function when

switching off possible

sources of interference?

Signal is not transmitted

when interference

sources are operational

Button in remote control

jammed / two buttons

pressed at same time

Does the “Send” symbol

appear on the display?

Release the button /

press only one button

Batteries in remote con-

trol are flat

Have new batteries been

inserted? Is the display

incomplete?

Insert new batteries

The unit is running with

reduced or without

cooling / heating output

Filter is unclean / air

inlet / outlet blocked by

foreign objects

Have the filters been

cleaned?

Clean the filters

 

 

 

REMKO MXD

 

 

36

Содержание MXD202

Страница 1: ...and operating instructions Read the instructions prior to performing any task REMKO MXD 202 MXD 262 MXD 352 MXD 522 Ceiling cassette for inverter multi split designed outdoor units 0047 2013 05 Editio...

Страница 2: ...g inal Read these operating instructions carefully before commis sioning using this device These instructions are an integral part of the system and must always be kept near or on the device Subject t...

Страница 3: ...d recycling 6 2 Technical data 7 2 1 Technical data 7 2 2 Unit dimensions 8 3 Design and function 9 3 1 Equipment description 9 3 2 Combinations 10 4 Operation 12 5 Installation instructions for quali...

Страница 4: ...ay be fatal or cause serious injury WARNING This combination of symbol and signal word warns of a potentially hazardous situation which if not avoided may be fatal or cause serious injury CAUTION This...

Страница 5: ...ctures walls or floors n Mobile units must be set up securely on suit able surfaces and in an upright position Sta tionary units must be permanently installed for operation n The units and components...

Страница 6: ...ion and recycling Disposal of packaging All products are packed for transport in environ mentally friendly materials Make a valuable contri bution to reducing waste and sustaining raw mate rials Only...

Страница 7: ...m h 380 445 580 380 445 580 500 570 720 635 690 800 Sound press level per speed setting 3 dB A 40 44 48 40 44 48 40 43 48 40 43 46 Sound power Turbo mode dB A 52 53 54 54 Power supply V Hz 230 1 50 P...

Страница 8: ...intake temperature TK 20 C outdoor temperature TK 7 C FK 6 C max air volume 5m pipe length 3 Distance 1 m free field 4 Contains greenhouse gas according to Kyoto protocol For details of the energy ef...

Страница 9: ...of a fin vaporiser vapor iser fan controller and condensation pan The indoor unit can be combined with REMKO out door units of series MVT 601DC 901DC und 1051DC with sufficient combinations The outdo...

Страница 10: ...10 l l 11 l l Outdoor unit MVT 901 DC Combina tion MXD 202 MXD 262 MXD 352 MXD 522 One indoor unit 1 l 2 l 3 l 4 l Two indoor units 5 ll 6 ll 7 ll 8 l l 9 l l 10 l l Combina tion MXD 202 MXD 262 MXD 3...

Страница 11: ...ll 24 l ll 25 ll l 26 l l l 27 l l l 28 ll l 29 l l l 30 l ll 31 l ll 32 ll l Four indoor units 33 llll 34 llll 35 llll 36 lll l 37 lll l 38 ll ll 39 ll l l 40 l lll 41 l ll l 42 lll l 43 ll ll 44 l...

Страница 12: ...emote control The infrared remote control sends the programmed settings over a distance of up to 6 m from the receiver of the indoor unit Data will only be received correctly if the remote control is...

Страница 13: ...peration 5 Fan Defrost 6 Alarm indicator Keys on the remote control 4 1 7 8 10 11 3 2 13 9 5 6 12 14 15 Fig 6 Keys of the remote control 1 Key ON OFF Press this key to operate the unit 2 Key With this...

Страница 14: ...10 Key TIMER ON This button initiates the automatic switch on time for the unit Each time the key is pressed the auto matic time setting increases in increments of 30 minutes Once the time setting sho...

Страница 15: ...er 8 Timer activated deactivated 9 Display of fan speed 10 Sleep mode aktivated 11 Follow Me function aktivated 12 Remote control locked 13 Display on off Key functions A symbol is shown on the displa...

Страница 16: ...mperature range lies between 17 C and 30 C Fig 10 and keys MODE key Use the MODE key to select between individual operating modes A total of 5 modes are available 1 Automatic 2 Cooling 3 Dehumidifying...

Страница 17: ...tch off the other indoor units from which are in cooling mode the cooling During heating operation can not be cooled Dehumidification mode It is recommended that the target temperature be set to 24 C...

Страница 18: ...protect the compressor the controller will wait 3 minutes before switching on the heating mode again The fan operation starts only at a temperature of 32 C at the heat exchanger Fig 15 Heating mode Th...

Страница 19: ...intervals to the indoor unit LED FOLLOW ME 2 sec Fig 17 Follow Me function SLEEP key A programming function is activated using this key which increases the target temperature in cooling mode by 1 C af...

Страница 20: ...erval of 30 minutes 0 5 h to switch on the unit 3 sec TIMER ON TIMER ON Fig 19 TIMER ON key TIMER OFF key This key allows the unit is switched on in an adjustable interval of 30 minutes 0 5 h to switc...

Страница 21: ...stment of the set values LOCK Fig 22 LOCK key RESET key With this recessed key the remote control can be reset RESET Fig 23 RESET key Cable remote control Connection of an optional cable remote contro...

Страница 22: ...prevent the infiltra tion of moisture and never kink or compress the refrigerant piping n Only use the union nuts supplied with the refrigerant piping These should only be removed shortly before conn...

Страница 23: ...nded ceiling Fig 26 2 Fit the indoor unit onto the threaded rods and use the lower nuts to level the unit Fig 27 3 Ensure a clearance of 35 mm from the ceiling Connect the refrigerant pipes elec trica...

Страница 24: ...ndependently of this to suction in fresh air 2 1 2 Fig 29 Adjacent room and fresh air connection 1 Fresh air connection 2 Adjacent room connection NOTICE Only one adjacent room connection and one fres...

Страница 25: ...m pipe length of 7 m may not be exceeded Fig 34 n To ensure that air is transported to the adja cent room 1 or 2 of the 4 air outlets are to be sealed on the indoor unit To do this use a black strip w...

Страница 26: ...y n To prevent rainwater from entering the unit the air may only be suctioned in by the fresh air intake at a maximum speed of 2 5 m s n To connect the fan it is necessary for the cus tomer to install...

Страница 27: ...ight Condensate draining If the temperature falls below the dew point con densation will form on the cooling fins during cooling mode A collection tray together with a con densation pump and float swi...

Страница 28: ...blocks for making the connections are located inside of the unit After opening the cover they are reachable n If a condensate pump is available as an acces sory when using a turn off switch of the pu...

Страница 29: ...2 1 3 Fig 40 Unit connection 1 Entrance power supply 2 Dismantle the cover of the switch box 3 Connection control line from the outdoor unit 29...

Страница 30: ...DC 230V 1 50 Hz L A N A S A L N L B N B S B L C N C S C L D N D S D L N S L N S L N S L N S A 1 B1 B2 B3 B4 2 2 Fig 41 Electrical connection diagram A Outdoor unit MVT 601 DC 1051 DC B Indoor units M...

Страница 31: ...th DIP switch 1 DIP switch 1 SW6 2 DIP switch 2 SW7 DIP switch 1 SW6 DIP switch 2 SW7 Choice of temperature Choice of unit Unit ON 1 2 6 K ON 1 2 MXD 202 ON 1 2 4 K ON 1 2 MXD 262 ON 1 2 2 K ON 1 2 MX...

Страница 32: ...NEWFAN N P1 N P6 CN15 2 1 4 3 5 6 7 8 9 A 10 11 SW2 12 Fig 43 Electrical circuit diagram A Power supply control board 1 Swing motor 2 Connectivity cable remote control 3 MCC bus 4 Connection display b...

Страница 33: ...SW3 CN4 H M L 2 1 4 3 5 6 7 8 9 A 10 11 12 Fig 44 Electrical circuit diagram A Power supply control board 1 Swing motor 2 Connectivity cable remote control 3 MCC bus 4 Connection display board 5 Liqui...

Страница 34: ...ect function of the condensa tion line by pouring distilled water into the condensation tray A bottle with a spout is recommended for pouring the water into the condensation tray Functional test for h...

Страница 35: ...Switch off the voltage supply to the unit 4 Check the unit for visible signs of damage and clean it as described in the chapter Care and maintenance Permanent shut down Ensure that equipment and comp...

Страница 36: ...component Electrical surges caused by thunderstorms Have there been light ning strikes in the area recently Switch off the mains breaker and switch it back on Have it checked by a specialist Fault in...

Страница 37: ...tion discharge on unit Drainage pipe on collec tion container clogged damaged Can the condensation drain off without any obstruction Clean the drainage pipe and collection container Faulty external co...

Страница 38: ...connec tion leads flashes flashes E0 EEPROM error Check EEPROM flashes on Shutdown inverter module flashes Liquid level switch con densate pump defective actuated Contact specialist dealer flashes on...

Страница 39: ...plant at all times Cleaning the cover of the indoor unit 1 Disconnect the supply voltage to the equip ment 2 Open and fold down the air inlet guard on the cover The filter is held in place by the fla...

Страница 40: ...ownward Fig 47 6 When using water allow the filter dry out properly in air before replacing it in the unit 7 Carefully insert the filter Make sure it is seated correctly 8 Close the cover as described...

Страница 41: ...iew of the unit and spare parts list 13 1 Exploded view Fig 48 Exploded view MXD 202 522 We reserve the right to modify the dimensions and structural design as part of the ongoing technical devel opme...

Страница 42: ...062 1111062 1111062 1111062 7 Condensation float switch 1112502 1112502 1112502 1112502 8 Display board 1111064 1111064 1111064 1111064 9 Cover cpl 1112503 1112503 1112503 1112503 10 Air filter 111250...

Страница 43: ...ling mode 34 Heating mode 34 G Greenhouse gas according to Kyoto protocol 8 I Infrared remote control 12 Installation instructions 24 Installation location selection 22 Installation materials 22 Inten...

Страница 44: ...REMKO MXD 44...

Страница 45: ...45...

Страница 46: ...REMKO MXD 46...

Страница 47: ......

Страница 48: ...t as advisers to our customers in air conditioning and heating technology SFlbCustomer Service Our equipment operates precisely and reliably However in the event of a fault REMKO customer service is q...

Отзывы: