2
Technical data
2.1 Unit data
Series
MVV 1200 DC
MVV 1600 DC
MVV 2000 DC
Operating mode
Inverter outdoor units for cooling and heating
Number of outdoor units
1
1
1
Nominal cooling output
1)
kW
12.0
5)
(5.76-12.43)
15.5
5)
(7.75-16.33)
20.0
7)
(9.23-21.53)
Nominal heat capacity
2)
kW
13.5
5)
(6.60-15.53)
18.6
5)
(8.30-20.13)
23.3
7)
(10.52-25.43)
Operating range - outdoor unit - cooling
°C
-15 to +48
Operating range - outdoor unit - heating
°C
-15 to +27
Refrigerant
R410A
4)
Energy efficiency ratio, cooling
1)
A
5)
A
5)
B
7)
Energy efficiency rating EER
1)
3.21
5)
3.29
5)
3.03
7)
Energy efficiency ratio, heating
2)
A
5)
A
5)
A
7)
Energy efficiency rating COP
2)
3.71
5)
3.75
5)
3.77
7)
Power consumption, annual, (500h) C/H
1870/1820
2355/2480
3295/3090
Operating pressure, max.
kPa
4200
Air flow rate, max.
m³/h
6000
10800
Sound power level
3)
dB (A)
66/63
65/62
70/67
Sound pressure level, max.
3)
dB (A)
58/55
57/52
59/56
Power supply
V/Hz
400V / 3~ / N / Pe
Enclosure class
IP
24
Electrical rated power consumption, cooling
1)
kW
3.74
4.71
6.59
Electrical rated current consumpt., cooling
1)
A
5.51
6.94
13.80
Electrical rated power consumpt., heating
2)
kW
3.64
4.96
6.18
Electrical rated current consumpt., heating
2)
A
5.36
7.03
10.90
El. starting current, max.
A
10
12
15
El. power consumption, max.
kW
6.4
7.3
8.7
Compressor model
Rotary piston
Scroll
Scroll
Flow regulator
Electronic expansion valves
Refrigerant, basic quantity
kg
3.30
3.90
4.80
Refrigerant, additional quantity
g/m
Max. number of indoor units
7
8
10
Refrigerant connection, liquid pipe OU
Inches
(mm)
3/8" (9.52)
3/8" (9.52)
3/8" (9.52)
REMKO MVV...DC
8
Содержание MVV 1200 Dc