Malfunction indicated by display MVV 1200-1600 DC
Display Description
Cause
Details
E0
EEPROM error
EEPROM contact problem
E2
Communication error between IU and OU
Power supply faulty,
communication line faulty
E3
Communication error of board in the OU
Board faulty, connection faulty
E4
Probe outside temperature defective / inter-
rupted,
probe, condenser defective / interrupted
Probes faulty, connection faulty
E5
Voltage monitoring has tripped
Power supply faulty, board faulty
E6
Fan motor defective, connection interrupted Board faulty
E7
Excessive temperature heat exchanger out-
door unit in heating mode
Fan motor faulty,
connection faulty
E8
2x E6 malfunctions in 10 minutes
Fan motor faulty,
connection faulty
P0
Excessive temperature inverter module
Heat build-up in board space
P1
High pressure fault
Connections faulty,
fan motor faulty,
register outdoor unit dirty,
high pressure switch faulty
P2
Low pressure alarm
Connections faulty,
refrigerant piping faulty,
register indoor unit dirty,
low pressure switch faulty
P3
Compressor overcurrent protection has
tripped
Outside temperature too high,
fan motor faulty,
register outdoor unit dirty,
refrigerant piping faulty
P4
Excessive temperature compressor outlet
Connection faulty,
refrigerant low,probe faulty
P5
Excessive temperature in condenser
Register outdoor unit dirty,
refrigerant piping faulty,
probe faulty
P6
Inverter module fault
Condenser faulty,
inverter module faulty
P7
Excessive temperature evaporator
Connection faulty,
board indoor unit faulty,
probe faulty
P8
Fan protection against excessive speed
Strong wind at the outdoor unit
REMKO MVV...DC
46