background image

MKT 240

With low cleaning effort, you 
can guarantee malfunction-free 
operation and a long service 
life.

■ 

Use only mild, environment-
friendly cleaning agents.

■ 

Regularly clean the  
ventilation slots. 

■ 

Clean the device as required, 
but at least once a year, with 
a moist cloth and lukewarm 
water. 

■ 

Do not expose the device to 
direct water spray. 

Maintenance and Care

Cleaning the air fi lter

Clean the air fi lter regularly, 
but at least every 100 operat-
ing hours. In case of strongly 
contaminated air, the period is 
reduced accordingly.

1.

Switch off the device and 
pull the mains plug.

2.

Remove the fi lter from the 
device (Fig. 14).

3.

Clean the fi lter using a 
vacuum cleaner or, in case 
of heavy soiling, carefully 
using lukewarm water (Fig. 
15/16).

4.

Let the fi lter air-dry and then 
reinsert it.

Fig. 14  

Removing the air fi lter 

upwards from the machine

CAUTION

Always turn off the device 
and pull the mains plug before 
cleaning!

Never operate the device 
without the air fi lter.

Fig.15/16 

Cleaning the air fi lter

Fig.17  

Draining the condensate

Draining the condensate

■ 

The condensate evaporates 
during operation and is then 
conducted outside with the 
exhaust air via the air outlet 
hose. 

■ 

In case of extreme humidity, 
the device collects conden-
sate in a reservoir. If the 
permissible level is exceeded, 
the red fault LED lights up 
and the device shuts down. 

■ 

The reservoir must be  
emptied via the condensate 
drain spout (Fig. 17).

Fig. 13  

Functional principle of the cooling process

Functional principle of 
the cooling process

The air conditioner
cools the air by re-
moving heat from it. 
The fan (circulation 
air) conducts cooled 
air into the room. The 
heat that the device 
has removed from the 
air is conducted out-
side via the air outlet 
hose.

Ventilator 

(exhaust air)

(exhaust air)

Evaporator

Evaporator

Condenser

Condenser

Cooling circuit

Cooling circuit

Air inlet (exhaust air)

Air inlet (exhaust air)

Air inlet (circulation air) 

with air fi lter

Humidity is removed 
from the air and drips 
as condensate from the 
evaporator onto the hot 
condenser and evapora-
tes. Excess condensate 
drips from the condenser 
into a collection tray 
and conducted from 
there to the condenser 
again using a rotor, 
evaporated, and then 
conducted away with 
the exhaust air fl ow.

Cooled circulation 

air in the room     

air

air

Fan (circulation air)

Warm exhaust air 

outside

Содержание MKT 240

Страница 1: ...Timer Functional Principle of the Cooling Process Maintenance and Care Cleaning the Filter Draining the Condensate Trouble Shooting Taking the Device Out of Service Warranty Environment and Recycling...

Страница 2: ...lines under carpeting Do not lay lines under carpeting Never operate the device with Never operate the device with out an air lter Never direct the air ow at Never direct the air ow at people Never op...

Страница 3: ...ed Observe the following notices Plug the air outlet hose in cluded in delivery onto the air outlet on the rear panel of the device Lock both catches on the air outlet into both openings of the air ou...

Страница 4: ...D 14 C F toggle button only on the remote control Operation The device is operated comfortably using the control panel on the device or the in frared remote control Keys with the same symbols have the...

Страница 5: ...ed the display switches from the room temperature to the set tempera ture LED 13 lights up and shows the desired temperature for 15 seconds 7 Set the desired room temperature using the Timer Temp Adju...

Страница 6: ...porates during operation and is then conducted outside with the exhaust air via the air outlet hose In case of extreme humidity the device collects conden sate in a reservoir If the permissible level...

Страница 7: ...and pull the mains plug 2 Place a at tray under the condensate drain spout and remove the plug Fig 17 3 After the condensate has drained reinsert the plug rmly The device is not cooling properly Chec...

Страница 8: ...design sub ject to alteration Control panel Evaporator fan Condenser Red Orange Yellow White White W Red Red Red Blue Blue Blue Blue Condenser Condenser Compressor Evaporator fan Reservoir motor Mains...

Страница 9: ...480 mm with a diameter of at least 135 mm Take the minimum distance of 430 mm between the oor mounting surface of the device and the centre of the wall bushing into consideration Insert the telescopi...

Страница 10: ...of the MKT 240 Technical dimensions and design subject to alteration Device Diagram 28 28 35 35 33 33 34 34 18 18 29 29 19 19 21 31 31 18 18 18 18 20 30 27 25 25 8 1 2 3 10 7 7 6 6 11 5 9 4 23 23 13...

Страница 11: ...n wheel right circulation air 1106870 21 Fan motor circulation air 1106871 22 Side wall right 1106872 23 Circuit board 1106873 24 Mains supply line with plug 1106874 25 Front wall 1106875 26 Back wall...

Страница 12: ...setting range C 16 bis 32 Temperature operating limits C 16 bis 35 Refrigerant R 407 C Refrigerant quantity kg 0 770 Circulation air volume ow rate m3 h 230 260 300 Exhaust air volume ow rate Max m3...

Отзывы: