If Tc is >50 °C and the compressor runs within 5
minutes, the unit switches off and the error code
"E3" is shown in the segment display [3] and the
CHECK indicator [9] flashes. In this case, the fault
cannot be reset with a key press. The unit power
plug must be removed from the socket so that the
unit is completely de-energised. Then, the dehu-
midifier can be restarted after a restart delay of 70
seconds.
If Tc is > 50 °C and the compressor runs over 5
minutes, the compressor stops but the fan motor
continues to run for a further 30 minutes. The seg-
ment display flashes with fault code E3 during this
time. After 30 minutes the unit is restarted for
normal function with the previous setting.
NOTE:
n
Within this 30 minute protective period, the
"ON / OFF" key can be pressed in order to
switch the unit off. If the "ON / OFF" key is
then pressed, the unit restarts after a delay
time of 1 minute.
10
RT °C INDICATOR:
If the "ROOM TEMP" key is pressed, the RT indi-
cator [10] illuminates for 5 seconds.
11
"FULL TANK" DISPLAY:
If the water tank is full the "FULL TANK" and
"CHECK" indicators illuminate. The compressor
and the fan motor are automatically switched off at
this time.
In order to reset the messages described, the con-
densate water must be removed from the water
tank. Then the water tank must be properly
inserted back into the unit. After that the unit will
start again after a 3 minute delay time.
If the unit is switched off while the "FULL TANK"
and "CHECK" indicators are illuminated, both indi-
cators switch off.
If the unit is switched on, but is in standby mode
(i.e.: room humidity is lower than the target room
humidity set), the compressor and the fan motor
are switched off and the "COMP. ON" indicator illu-
minates. If the water tank is full at this time, the
"FULL TANK" and "CHECK" indicators flash.
12
kWh INDICATOR:
By actuating the "COUNTED" key, the "kWh" indi-
cator illuminates and the electrical power in kW
consumed by the unit is displayed in the segment
display [6].