Heat exchanger cleaning

 

1.   Remove revision cover (1). 

2.   Pull waste gas suppressors (3) out of unit 

3.   Clean waste gas passes (4). 

A special cleaning brush can be obtained as acces-
sories.

 

4.  Clean waste gas suppressors or replace them, if 

necessary. 

5.  Check gasket (2) of revision cover and replace, if 

necessary. 

5. Disassemble tightening bolts at supports of combus-
     tion chamber and pull out combustion chamber side-
     ways.  

     Look  out:

 Supports of combustion chamber (

1

) may 

     neither be bent nor damaged! 

Combustion chamber cleaning 

 

à

Clean combustion chamber (5) through its opening 
(6) by means of a vacuum cleaner. 

Special cleaning sets can be obtained as accesso-
ries to the REMKO industrial vacuum cleaner. 

Important Hint! 

 
An operation/use other than that indicated in these in-
structions is prohibited! In the case of non-observation 
we will not be held responsible and our guarantee will 
become void. 

Any claims under guarantee regarding materials can be ac-
cepted only when the orderer or his customer has filled in 
completely the 

“guarantee certificate”

 which is enclosed 

with every REMKO-heater and has returned it to REMKO 
GmbH & Co. KG in due time after the unit’s sale and com-
missioning.  

Burner maintenance

 

à

Make sure that the burner is exclusively maintained 
by authorized experts. 

à

Make sure to observe the limit values for waste gas 
losses according to the relevant regulations. 

à

For safety reasons we recommend that you con-
clude a maintenance contract! 

Assembly of combustion chamber

 

1.    Assembly is to be carried out in reverse order. 

2.    Make sure that the gasket and the revision cover (

1

are correctly seated. 

3.   Insert combustion chamber carefully into unit and 

adjust it. 

Tightening bolts of supports just should be screwed 
in loose. 

4.    Install burner with burner-flange. 

5.   Pay attention to the correct distance of burner to 

flange. 

Approx. 30 mm, see opposite draft. 

6.    Check flange gasket and replace, if necessary. 

7.    Tighten the tightening screws of combustion chamber 

supports. 

8.    Remount all trim panels.  

9.    Remount waste gas connection duly. 

While doing so, check gasket (7) and replace, if 
necessary. 

10. Re-establish all connections and joints and check 

them thoroughly. 

11. Put unit into service and check proper function of all 

operating modes.  

12. Make sure to observe the limit values for waste gas 

losses according to the relevant regulations. 

Important hint to the revision cover! 

à

During assembling take care of uniform tightening of 
the fixing nuts the revision cover. 

à

Uneven tightening may result in leakages of waste 
gas passes!

 

Содержание HTL 150-FB

Страница 1: ...REMKO as strong as an ox REMKO HTL 150 250 FB 2 step Automatic Oil Heater Edition GB M02 Operation Technology Spare Parts...

Страница 2: ......

Страница 3: ...rams 12 Wiring Diagram 13 Oil Burner 14 Operating instructions Make sure to read these instructions carefully before starting using the unit Our guarantee will become void when the unit supplied by us...

Страница 4: ...ld resistant down to 20 C below 20 C the de vice switches off when the temperature rises above this temperature it switches on again When the sensor or the capillary tube is damaged or when an overtem...

Страница 5: ...d Please use exclusively those hot air hoses accessories which have been approved by our company The inside overlappings on the seams of the hot air hoses must run with the air current direction Make...

Страница 6: ...STB If the STB has been released make sure to find the reasons why e g unit could not cool down as the electric power has been cut off temperature of blown out air is too high because of inadequate ai...

Страница 7: ...Have the waste gas values of the burner checked regularly by authorised experts For safety reasons we recommend that you con clude a maintenance contract Make sure to store the unit in a dust free an...

Страница 8: ...s sale and com missioning Burner maintenance Make sure that the burner is exclusively maintained by authorized experts Make sure to observe the limit values for waste gas losses according to the relev...

Страница 9: ...0 3N 50 400 3N 50 power take up max entirely unit W 2 640 4 580 4 810 rated current max entirely unit A 6 1 9 3 9 8 power take up min max fan W 960 1 950 2 700 3 900 2 850 4 100 rated current max fan...

Страница 10: ...6 17 18 20 19 21 22 23 11 9 8 46 7 30 29 28 27 26 31 32 33 34 35 36 39 38 40 41 42 43 44 45 25 24 Unit design comb chamber heat exchanger We reserve the right to make modifications in dimensions and c...

Страница 11: ...ttom rear 1105389 1105389 1105389 26 bracket fan 1105390 1105391 1105391 27 fan 1105375 1105377 1105380 28 inlet nozzle 1105376 1105378 1105378 29 suction plate 1105392 1105393 1105393 30 plate rear w...

Страница 12: ...tactor phase sequence relay K7 Auxiliary relay KX5 6 phase sequence relay KB combined regulator M1 fan motor P1 hour counter RT room thermostat socket S1 operating switch S2 burner reset S3 change ove...

Страница 13: ...double socket close to burner S2 burner reset S3 change over switch 1 2 Step SK switch box TW burner temperature monitor WS4 4 pole plug to burner WS7 7 pole plug to burner X3 terminal strip close to...

Страница 14: ...ng cross section Loosen socket screw and turn air inlet device into desired posi tion pay attention to the arrows Turn to min reduced burner pressure Turn to max increased burner pressure Secondary ai...

Страница 15: ...he setting of the control cam air vol ume 1 Less air stage 1 Set the blue adjustment lever by moving it anticlockwise to decrease the opening angle If the burner is operating the servomotor turns auto...

Страница 16: ...REMKO GmbH Co KG Klima und W rmetechnik D 32791 Lage Im Seelenkamp 12 D 32777 Lage PO Box 1827 Phone 49 5232 606 0 Fax 49 5232 606260...

Отзывы: