background image

6

REMKO ETF 320

Safety notes

Condensation heat

The Energy transferred to the air 
from the condenser consists of:
1.  The amount of heat derived 

beforehand in the evaporator.

2. The electrical drive energy.
3.  The condensation heat released 

by liquefying the water vapour. 

Energy must be supplied when 
liquid is converted into a gas. 
This energy is designated as 
evaporation heat. It does not 
cause any increase in temperature, 
but is required to convert a liquid 
into a gas. Conversely, energy is 
released when gas is liquefied, 
this is designated as condensation 
heat. 

The amount of energy from 
evaporation heat and condensation 
heat is the same.   

For water, this is:  
2250 kJ/kg (4.18 kJ = 1kcal)

From this it is evident that the 
condensation of water vapour 
causes a large quantity of energy 
to be released.
If the moisture that it is to be 
condensed is not introduced by 
evaporation in the room itself, 
but from outside, e.g. through 
ventilation, the condensation 
heat released contributes to 
the heating of the room. With 
drying operations, a heat cycle 
is created, whereby heat is 
consumed for evaporation 

and released for condensation. 
When dehumidifying fed air, 
a larger contribution of heat is 
created, which manifests itself as 
a temperature increase. 

Generally speaking, the time 
required for the drying process is 
not only dependent on the output 
of the unit, but is determined to 
a greater extent by the speed at 
which the material or building 
section loses its moisture.

 

The units have been subjected to 
extensive material, functional and 
quality inspections prior to delivery.

However, dangers can result 
from the units if they are used 
improperly or not as intended by 
untrained personnel.

The following notes 
must be observed in full:

■ 

The units may not be installed 
or operated in explosive 
environments

■ 

The units must not be installed 
or operated in atmospheres 
containing oil, sulphur, chlorine 
or salt

■ 

The units must be installed 
upright and in a stable position

■ 

The units must not be exposed 
to direct jets of water

■ 

An unobstructed air inlet and 
air outlet must be guaranteed 
at all times

■ 

The air-inlet grille must always 
be kept free of dirt and loose 
objects

■ 

The units must not be covered 
during operation

■ 

Never stick foreign objects into 
the units

■ 

The units must not be 
transported while they are 
running

■ 

The units may only be 
transported upright

■ 

All electrical cables on the 
outside of the units must be 
protected against damage 
(e.g. by animals etc.)

■ 

Before each change of location, 
the condensate container must 
be emptied

Extensions to the connection 
cable must only be conducted 
by authorised specialist 
electricians, taking into 
consideration the unit power 
consumption, cable length and 
local use.

Work on the refrigerant 
system and on the electrical 
equipment must only be 
conducted by a specially-
authorised specialist! 

 

!

   CAUTION

 

!

   CAUTION

Содержание ETF 320

Страница 1: ...Edition GB I03 REMKO ETF 320 Mobile dehumidifiers Operation Technology Spare parts...

Страница 2: ......

Страница 3: ...or on the unit itself Subject to modifications no liability accepted for errors or misprints Air dehumidification 4 Safety notes 6 Unit description 7 Set up 8 Commissioning 9 Shutdown 11 Unit transpo...

Страница 4: ...r vapour released from parts of a building or materials is absorbed by the surrounding air As a result the moisture content increases which ultimately gives rise to corrosion mould rot peeling of pain...

Страница 5: ...emperature to fall below it Building materials and structures are capable of absorbing considerable volumes of water such as brick 90 190 l m heavy concrete 140 190 l m and limestone 180 270 l m The d...

Страница 6: ...t on the output of the unit but is determined to a greater extent by the speed at which the material or building section loses its moisture The units have been subjected to extensive material function...

Страница 7: ...xtinguishes again when the empty condensate container is re inserted The units then restart after a switch on delay of around 3 minutes In unattended continuous operation with an external condensate c...

Страница 8: ...if the unit is set up approx 1 m above the ground The room being dried or dehumidified must be closed to the surrounding atmosphere Avoid having opened windows and doors etc and avoid frequent entry...

Страница 9: ...a waiting time of 3 minutes has elapsed Restart protection NOTE The devices can be switched ON and OFF via an external time accessory if required Before commissioning the unit or if local requirements...

Страница 10: ...rly fast and effective and guarantees high dehumidification performance Dehumidification mode is only paused for a short time during the defrost phase The Defrost mode indicator light indicates that t...

Страница 11: ...the connection nozzle that is now exposed In unattended permanent operating mode the condensate should preferably be drained into a lower level drain If using an external collection container pan buck...

Страница 12: ...utlet grille for contamination on a regular basis Clean or replace if required Care and maintenance NOTE Regular care and maintenance is fundamental to a long service life and fault free operation of...

Страница 13: ...ax 40 C soap solution Finally always rinse the filter carefully with clear water and allow to dry 7 Also check the intake grill for contamination and clean if necessary 8 Before refitting grill and fi...

Страница 14: ...tutory or locally applicable regulations The unit is loud or condensate runs out Check whether the unit is on a stable and even base Check whether the unit is standing upright and stably Have the cond...

Страница 15: ...are environmentally friendly and can be recycled By recycling packaging materials you make a valuable contribution to the reduction of waste and conservation of raw materials Therefore only dispose o...

Страница 16: ...it We reserve the right to modify the dimensions and design as part of the ongoing technical development process 1 3 6 5 10 29 27 34 24 19 16 15 40 41 43 17 18 26 28 39 9 25 7 35 36 32 23 30 33 21 31...

Страница 17: ...1103673 20 Fan motor 1103661 21 Fan housing 1111133 22 Fan wheel 1103636 23 Protection grid 1103637 24 Condenser fan motor 1103668 25 Distribution block 1111134 26 Mains cable with plug 1103660 27 Boa...

Страница 18: ...Fan function checked Air inlet grid with filter cleaned Unit checked for damage Safety devices checked All fastening screws checked Electrical safety check Test run 1 Date Signature 2 Date Signature 3...

Страница 19: ...15 2 At 15 C 60 RH l day 8 4 Max airflow volume m3 h 190 Condensate container capacity Litres 5 5 4 5 Refrigerant 1 R 410A Refrigerant quantity g 180 Power supply V 230 1 Frequency Hz 50 Max rated cur...

Страница 20: ...dvisers to our customers in air conditioning and heating technology Customer service Our units operate precisely and reliably However in the event of a malfunction REMKO customer service is quickly on...

Отзывы: