7.5  Setting the Temperature

Set the required (maximum) domestic hot water temperature on the controller under "Para". To ensure that

scalding cannot occur at the water valve, the maximum hot water temperature must not exceed 60 °C.

Primary side

The temperature required in the buffer tank on the primary side depends on the desired hot water tempera-

ture and the required dispensing quantity. The temperature in the buffer tank must be at least 5 K above the

required hot water temperature.

Secondary side

The possible dispensing medium flow rate [l/min] on the water valve depends on the hot water temperature

that is set in the controller and the temperature that is available in the storage tank. The recommended max-

imum domestic water medium flow rate through the fresh water module is 25 l/min. The following table

shows the relationship between the storage tank temperature and the maximum dispensing medium flow

rate that is connected when the temperature on the valve is 45 °C (e.g. single-lever mixer). If the hot water

temperature that is set on the Controller is higher than 45 °C, the dispensing medium flow rate consists of a

mixture of hot and cold water. The transmission capacity that is specified for this is required to warm the

water quantity of the dispensing medium flow rate [l/min] from 10 °C to 45 °C.

EFS 35 Single and Duo

Tempera-

ture in

buffer

tank

probe

S08

[°C]

HW tem-

perature

set on

the con-

troller

[°C]

Maximum medium

flow rate from the

fresh water station

with the set. HW

temperature

[l/min]

Maximum dis-

pensing medium

flow rate at the

water valve for an

HW Temperature

of 45 °C

[l/min]

Transmission

capacity of the fresh

water station

[kW]

Return

tempera-

ture to

the

storage

tank

[°C]

 

 

Single

Duo

Single

Duo

Single

Duo

 

45

40

34

68

---

---

71

142

20

50

40

44

88

---

---

92

184

18

45

32

64

---

---

79

158

22

55

40

53

106

---

---

111

222

16

45

42

84

---

---

102

204

19

50

31

62

35

70

87

174

24

60

40

61

122

---

---

128

256

15

45

50

100

---

---

121

242

17

50

40

80

45

90

111

222

21

55

30

60

39

78

95

190

27

65

40

65

130

---

---

135

270

14

45

57

114

---

---

138

276

16

50

47

94

53

106

131

262

19

55

39

78

49

98

120

240

23

60

15

30

42

84

103

206

29

70

40

65

130 

*)

---

---

135

270

13

45

64

128

---

---

155

310

14

50

54

108

61

122

149

298

17

 

 

 

REMKO fresh water station

 

 

22

Содержание EFS 35

Страница 1: ...Assembly and operating instructions Read the instructions prior to performing any task REMKO fresh water station EFS 35 EFS 50 Instructions for users and specialists 0062 2017 09 Edition 2 en_GB...

Страница 2: ...g inal Read these operating instructions carefully before commis sioning using this device These instructions are an integral part of the system and must always be kept near or on the device Subject t...

Страница 3: ...ironmental protection and recycling 6 2 Technical data 7 2 1 Unit data 7 2 2 Pressure loss characteristic curves 9 3 Unit description 10 4 Design and planning 11 4 1 General notes 11 4 2 Design of the...

Страница 4: ...tal or cause serious injury WARNING This combination of symbol and signal word warns of a potentially hazardous situation which if not avoided may be fatal or cause serious injury CAUTION This combina...

Страница 5: ...lst at a standstill as a matter of prin ciple n Appropriate hazard prevention measures must be taken to prevent risks to people when per forming installation repair maintenance or cleaning work on the...

Страница 6: ...ivery conditions Further more only the parties to a contract can conclude special agreements beyond these conditions In this case contact your contractual partner in the first instance 1 12 Transporta...

Страница 7: ...rol W 4 70 6 140 Circulation pump optional HE pump with PWM control 5 63 watts Heat exchanger 40 Plates 60 Plates Medium flow rate probe for technical data see extra table FlowSonic measurement range...

Страница 8: ...e medium Water potable Cvs value 8 Flow measurement Accuracy 10 of measured value Reaction time sec 1 Equipment Medium flow rate probe Ultrasonic sensors Electrical specifications Supply voltage V 5 V...

Страница 9: ...25 75 1 2 EFS 35 Fig 1 Pressure loss characteristic curve EFS 35 A Pressure mWS B Medium flow rate m3 h C Pressure kPa 1 Secondary 2 Primary A B C EFS 50 1 2 Fig 2 Pressure loss characteristic curve E...

Страница 10: ...ul installation must always be per formed before commissioning REMKO GmbH Co KG herewith confirms that the supplied product corresponds to the UBA German Environment Agency positive list A B C E 1 2 3...

Страница 11: ...are permitted to be installed between the fresh water module and the buffer tank The fresh water module is not permitted to be connected to a heating cycle distributor Installation example The operat...

Страница 12: ...place without reheating 20 l min x 20 min 400 l 400 l x 1 3 520 l The heated part of the buffer tank must be 520 litres in size The required buffer volume for 1 litre of water is calculated using the...

Страница 13: ...normal conditions 0 Corrosion can occur especially if other factors are rated as 0 Use not recommended Plate material Soldering mate rial Water content Concentra tion mg l or ppm Time limits for anal...

Страница 14: ...by chlorides in pH neutral environ ments 2 Generally a low pH below 6 increases the risk of corrosion and a high pH over 7 5 reduces the risk of corrosion 3 Fe3 and Mn4 are strong oxidisers and can i...

Страница 15: ...Outside this time window the circulation pump can be activated via a dispensing pulse if pulse controlled operation is also activated NOTICE In the delivered state circulation is not acti vated see t...

Страница 16: ...gth 2 m 2 Secondary side Hot water circulation return flow 1 connection OT flat sealing 3 Secondary side Cold water inlet 1 connection OT flat sealing 4 Secondary side Hot water outlet 1 connection OT...

Страница 17: ...ndary 167 mm Integration in a domestic connection group safety assembly Please note A domestic connection group safety assembly is required despite an integrated safety valve DIN 1988 Installation exa...

Страница 18: ...ball valve for filling drainage which may cause bodily injury Open the ball valve for filling drainage slowly and from a safe distance 1 Open the ball valve F by turning it to the 0 position 2 Fill t...

Страница 19: ...ny air noises switch the pump off To do this select manual oper ation H1 in the selection menu of the con troller 6 Set the pump to automatic operation A 7 Slowly open the piston valves on the secon d...

Страница 20: ...pressure loss on the domestic water side of the fresh water station 1000 mbar The following examples explain the relationships between the individual variables of the hot water temperature the dispen...

Страница 21: ...14 Maximum dispensing medium flow rate A Dispensing medium flow rate l min B Power kW 1 Hot water temperature 45 C after heating to 60 C and mixing in cold water 10 C 2 Buffer storage temperature Bou...

Страница 22: ...lever mixer If the hot water temperature that is set on the Controller is higher than 45 C the dispensing medium flow rate consists of a mixture of hot and cold water The transmission capacity that is...

Страница 23: ...is 1000 mbar in this case higher values are possible in a limited way hydraulically The maximum flow rate depends on the pressure loss on the primary side The maximum dispensing quantity depends on t...

Страница 24: ...400 24 75 40 88 176 183 366 13 45 88 176 214 428 14 50 88 176 100 200 244 488 16 55 87 174 111 222 264 492 18 60 67 134 95 190 233 466 21 80 40 88 176 183 366 12 45 88 176 214 428 14 50 88 176 100 200...

Страница 25: ...t on the primary side q Checked Is pressure of at least 2 5 bar present on the secondary side q Checked Is an error message shown on the display q No message Installation operation Date Signature 8 Ma...

Страница 26: ...alist Depiction of spare parts EFS 35 50 1 2 7 3 4 7 4 5 6 3 3 8 Fig 15 Spare parts EFS 35 50 We reserve the right to modify the dimensions and design as part of the ongoing technical development proc...

Страница 27: ...rmo ball valve DN 32 260156 4 8 Plate heat exchanger 260156 8 When ordering spare parts please always state the EDP number unit number and unit type see name plate Depiction of circulation pump spare...

Страница 28: ...aging disposal 6 Pipe connections 8 Piping of the fresh water station EFS 35 16 EFS 50 16 Pressure loss characteristic curve EFS 35 9 EFS 50 9 R Recycling 6 S Safety Dangers of failure to observe the...

Страница 29: ...29...

Страница 30: ...REMKO fresh water station 30...

Страница 31: ......

Страница 32: ...t as advisers to our customers in air conditioning and heating technology SFlbCustomer Service Our equipment operates precisely and reliably However in the event of a fault REMKO customer service is q...

Отзывы: