REMKO AMT 60-E Скачать руководство пользователя страница 6

G

 

Any work regarding the refrigerating plant and its 
electrical equipment is to be carried out exclu-
sively by especially authorized experts!

 

Safety Instructions

 

 
REMKO dehumidifiers will provide you with high utility 
and long life thanks to our extensive material, function 
and quality controls. 

Dangers may arise nevertheless if the unit is used by 
persons not familiar with its operation or if the unit is not 
used for its intended purpose. 

Make sure to install and use the unit only in explo-
sion-proof rooms. 

Make sure not to install and use the unit in an atmos-
phere containing fuel, oil, sulphur and salt. 

Make sure to install the unit on a solid base and in a 
vertical position. 

Make sure not to expose the unit to a direct water 
jet.  

Make sure that the air can be freely sucked in and 
blown off. 

Make sure that the suction side is always free from 
dirt and loose objects. 

Never put objects into the unit. 

Do not cover the unit during operation. 

Make sure not to transport the unit during operation. 

Avoid strong vibrations on the unit as soon as there 
is condensate in the condensate tank. 

Make sure to protect all electric cables outside the 
unit from damage (e.g. by animals). 

Before installing connection cable extensions make 
sure that they are suitable for the connected power, 
cable length and the intended purpose. 

Make sure to empty the condensate tank before in-
stalling the unit in another place. 

Make sure to transport the unit only in a vertical posi-
tion. 

Damage on the compressor will be avoid by a wait-
ing period of at least 1 minutes before starting the 
unit. 

Uses/operations other than that indicated in these 
operating instructions are not allowed! 

In the case of non-observation, any of our responsi-
bilities and guarantees will become void. 

The unit is to be used with the environmentally 
friendly, ozone-neutral refrigerant R407C. 

The refrigerant/oil mixture in the unit is to be dis-
posed of correctly and in accordance with the legal 
or local prescriptions. 

Important Tip Regarding Recycling!

 

Unit Description  

 
These unit have been designed for automatic, universal 
and problem-free air dehumidification. Thanks to their 
compact dimensions they can be easily transported and 
installed. 

The unit work according to the condensation principle 
and are equipped with a hermetically sealed refrigerat-
ing plant, a silent nearly maintenance-free ventilator as 
well as with a connection cable with plug. 

For an operation-control exists a green control-lamp 
“operation” on the control-panel. The correct time of op-
eration will record by a hour counter. 

The fully automatic electronic control, the condensate 
container with integrated overflow safety device, as well 
as the connecting branch for direct condensation drain-
ing ensure trouble-free continuous operation. 

The unit correspond to the fundamental safety and 
health requirements of the relevant EC regulations, they 
operate safely and are easy to handle. 

Function 

When the unit is switched on the electronic control and 
monitoring starts. 
The green control lamp is lit up. 
The compressor and fan are switched on time-delayed. 

The 

fan 

sucks in the ambient air via the air filter, the 

evaporator and the condenser placed behind the latter. 

Heat is extracted from the ambient air at the cold 

evaporator.

 It cools down below the dew point, and the 

water vapour contained in the air is deposited as con-
densate or hair frost on the evaporator lamellas. 

When necessary the evaporator is defrosted with hot 
gas with temperature control. 

The dehumidified cooled down air is reheated at the 

condenser

 (heat exchanger), and then it is blown out 

when it has reached a temperature of approx. 3 - 5 de-
grees above the ambient temperature. 

The treated dry air is mixed with the ambient air. 
Thanks to the continuous circulation of the ambient air 
through the unit, the relative air humidity in the place of 
installation is continuously reduced until it has reached 
the desired value.  

water container 

condensate trap 

ambient air 

fan 

compressor 

dehumidified 
ambient air 

condenser 

evaporator 

fig. AMT 60 

Schematic display of function 

Содержание AMT 60-E

Страница 1: ...Operation Technology Spare Parts Edition GB M02 REMKO powerful like a bear REMKO AMT 60 E 90 E Mobile Dehumidifier...

Страница 2: ......

Страница 3: ...er REMKO AMT 60 E AMT 90 E G Always keep these operating instructions near or on the unit G Contents page Air Dehumidification 4 Safety Instructions 6 Unit Description 6 Working Range 7 Installation 7...

Страница 4: ...kg of dry air absolute water content 1 m of air weighs approx 1 2 kg at 20 C Depending on the temperature each kg of air can only absorb a defined quantity of water vapour When this quantity has been...

Страница 5: ...n the other hand energy is re leased when gas is liquefied and this energy is called condensation heat The energy rate of evaporation and condensation heat is identical For water this is 2250 kJ kg 4...

Страница 6: ...rdance with the legal or local prescriptions Important Tip Regarding Recycling Unit Description These unit have been designed for automatic universal and problem free air dehumidification Thanks to th...

Страница 7: ...ce depends exclusively upon the design of the room the room temperature the relative humidity and the correct observance of the setup instructions The dehumidification performance increases with the r...

Страница 8: ...socket 230V 1 50 Hz fuse 16 A 2 Put main switch into position I Green control lamp operation is lit up 3 Please note the unit is switched on time delayed and then goes into the continuous operation mo...

Страница 9: ...safe transport 1 Switch off the unit prior to changing its place and to remove the mains plug from the plug socket 2 After that empty the condensate container 3 Make sure to transport and store the u...

Страница 10: ...there are any operating troubles check the unit according to the following listing The unit does not start Control or check operating switch The green control lamp must be lit Check connection to the...

Страница 11: ...difying capacity max l day 64 93 Dehumidifying capacity at 30 C 80 r h l day 54 2 79 8 Dehumidifying capacity at 20 C 70 r h l day 34 9 43 1 Dehumidifying capacity at 10 C 60 r h l day 11 3 16 3 Capac...

Страница 12: ...to make modifications in dimensions and construction in the interests of technical progress 1 2 3 4 5 6 7 8 9 10 12 13 14 15 16 20 19 17 18 21 22 23 25 26 27 28 29 30 32 33 31 35 36 37 38 34 39 11 24...

Страница 13: ...mp green 1105514 20 running hour meter 1105515 21 main switch 1102248 22 main fuse 1105561 23 fuse holder 1105560 24 electric cable 1101076 25 cable relief 1101047 26 axle 1105516 27 wheel 1102155 28...

Страница 14: ...1 12 13 14 15 16 18 20 21 22 24 19 25 26 27 29 28 30 31 32 34 33 35 37 38 36 17 7 23 39 We reserve the right to make modifications in dimensions and construction in the interests of technical progress...

Страница 15: ...amp red 1105513 19 control lamp green 1105514 20 running hour meter 1105515 21 main switch 1102248 22 main fuse 1105561 23 fuse holder 1105560 24 electric cable 1101076 25 cable relief 1101047 26 elec...

Страница 16: ...ensor red R2 Temperature sensor blue S1 Main switch S2 Micro switch water container Y1 Solenoid valve MAINS COMPR VALVE FAN COND NTC EVAP NTC FAIL LAMP 1 2 3 4 5 6 7 8 20 21 22 23 24 25 CONTROL BOARD...

Страница 17: ...erature sensor red R2 Temperature sensor blue S1 Main switch Y1 Solenoid valve MAINS COMPR VALVE FAN COND NTC EVAP NTC FAIL LAMP 1 2 3 4 5 6 7 8 20 21 22 23 24 25 H2 green S1 F1 8 2 A 5 2 4 1 C S R h...

Страница 18: ...13 14 15 16 17 18 19 20 Model Model No Device must be maintained according to legal regulations by authorised personnel only Remarks 1 Date 2 Date 3 Date 4 Date 5 Date Signature Signature Signature S...

Страница 19: ......

Страница 20: ...REMKO GmbH Co KG Klima und W rmetechnik D 32791 Lage Im Seelenkamp 12 D 32777 Lage PO Box 1827 Phone 49 5232 606 0 Fax 49 5232 606260...

Отзывы: