background image

35

Example: 

Quinta 45, total length 10 m, 2 bends 90°. 

80 mm: 10 m + 2 x 2 = 14 m < 16 m: 

flue OK

.

Note: If the design parameters are outside the values shown in the above table or 
there is any doubt over the flue system, please contact our technical department for 
calculation to be undertaken.

7.3.6  Different pressure zones 

Fig. 09 

Different pressure zones 

04W4H7900004

Bird guard

Flue outlet
Air inlet

The Remeha Quinta boilers (twin connection only) are capable of operating with the air 
inlet and flue outlet in different pressure zones (CLV System).
There are some restrictions to the flue/air inlet lengths and max height differences 
which have been detailed in 

Fig. 09.

Maximum total length of air inlet and flue gas outlet pipework (L) as detailed in table 
below (calculation based on using 1 x 90 bend).

Quinta 45

80 mm

Quinta 65

100 mm

max eq. Length

m

28

18

eq. Length bend 45°

m

1.2

1.4

eq. Length bend 90°

m

4

4.9

Table 15 

Calculation data different pressure zones

Содержание Quinta Pro 45

Страница 1: ...1 R e m e h a Q u i n t a 4 5 6 5 High efficiency con densing boiler for wall mounted installation Output Quinta 45 9 43 kW Quinta 65 13 65 kW Technical information Remeha Quinta 45 and 65...

Страница 2: ...trol panel 14 6 1 3 Combined key functions in operating mode only 15 6 1 4 Display of values with more than two digits 16 6 2 Flow diagram control system 17 6 3 Operating mode x 19 6 4 Shut off mode b...

Страница 3: ...pply 31 7 3 1 General 31 7 3 2 Classification due to discharging flue gases 31 7 3 3 Material and installation 32 7 3 4 Single boiler conventional flue 33 7 3 5 Single boiler room sealed flue 34 7 3 6...

Страница 4: ...Broag priority 48 8 5 1 Temperature control 48 8 5 2 Primary flow control 48 8 6 System pump 48 8 7 Frost protection 48 8 8 Remote alarm and boiler run indication 49 8 9 Safety interlock 49 9 Commissi...

Страница 5: ...ied out by a competent Engineer with the relevant certification ie CORGI ACOPS IEE regs etc On completion a copy of the commissioning sheet should be returned to Broag Ltd for record purposes If you h...

Страница 6: ...ith its gas air ratio control system ensures clean trouble free operation with higher than average efficiencies of 110 NCV in the condensing mode combined with ultra low NOx and minimum CO emissi ons...

Страница 7: ...ombi block with governor 4 Gas injector venturi 5 Cast aluminium heat exchanger 6 Temperature sensor return 7 Air inlet tube 8 Pressure gauge 9 Control panel 10 Facility for incorporating a rematic we...

Страница 8: ...lay will also indicate a flashing fault code confirming the reason for the failure The products of combustion in the form of hot flue gases are forced through the heat exchanger transfering their heat...

Страница 9: ...onnection 1 BSP m 1 BSP f Gas connection BSP m Condensate connection 25 mm o d plastic Combustion air supply connection 125 mm i d Quinta 45 and 150 i d Quinta 65 Combustion air supply connection 80 m...

Страница 10: ...ssure natural gas mbar 17 30 17 30 Min Max Inlet pressure propane mbar 37 50 37 50 Gas consumption natural gas m 3 h 1 0 5 0 1 5 7 5 Gas consumption propane m 3 h 0 3 1 7 0 5 2 5 NOx emission mg kWh 4...

Страница 11: ...ratio control for maxi mum efficiency Intelligent advanced boiler control abc c w a comprehensive operating service and fault diagnostic facility Available for conventional flue or room sealed operat...

Страница 12: ...to communicate directly with the boiler controls two wire to make full use of it s fully modulating fea ture ensuring that the boiler closely matches the system demand at all times External control s...

Страница 13: ...flashing digits shut off codes flashing dots c reset key to reset after a lockout condition d m key Program function key to select the required mode e s key Program function key to select the require...

Страница 14: ...override symbol not illuminated HTG under normal control NOTE In the Switch function in order to protect the boiler and the installation the flow temperature cannot exceed it s pre set maximum It is...

Страница 15: ...displayed as follows negative values will be indicated by a dot behind the last digit e g 1 10 values from 00 to 99 will be indicated without any punctuation marks values from 100 to 199 will be indi...

Страница 16: ...u n a High limit temperature set point Fan speed at full load HTG Fan speed at part load HTG and DHW Modulation start point t F R Interface selection control option B DHW cut in t C Fan speed at full...

Страница 17: ...sor n a Flow temperature set point Actual heat demand status Calculated HTG cut in temperature Actual flow temperature rise A n a Failure mode see Par 6 9 Speed mode see Par 6 8 Fan speed Read out mod...

Страница 18: ...temperature set point 5 C 7 HTG pump run on 8 DHW pump run on or for three way valve option HTG pump run on with valve open to DHW max 5 minutes 9 Normal control stop during DHW flow temperature set...

Страница 19: ...er correct boiler parameter Quinta 45 P 44 Quinta 65 P 64 Press e key to confirm settings Table 05 Shut off codes NOTE Shut off mode is a normal boiler operating function and does not represent a boil...

Страница 20: ...until the digit with dot appears in the code display Press the s key until the digit with dot appears in the code display Set the required value using the and keys Press the e key to store the new va...

Страница 21: ...option 11 HTG modulating or on off with DHW on To change the control option Press the m key until the digit with dot appears in the code display Press the s key until the digit A with dot appears in t...

Страница 22: ...by non qualified persons the control sys tem requires an input code to gain access to the second level of boiler control Press the m and s keys simultaneously and hold The code display now shows a le...

Страница 23: ...B DHW cut in T 10 05 read 1 5 C 06 read 10 C 07 read 15 C 08 read 20 C 05 C Fan speed at full load DHW 10 60 hundreds 52 D Intern May not be changed 00 E N a 0 100 F N a 25 G Forced part load time af...

Страница 24: ...3 Fan speed at full load HTG Adjustable from 18 to 100 output 1100 Quinta 45 1200 Quinta 65 to 5200 rpm factory default 52 100 This value sets the maximum output of the boiler 6 6 4 Fan speed at part...

Страница 25: ...l modulate when the flow temp equals the DHW set point DHW con trol stop set point parameter I i e 55 20 75 The boiler carries out a control stop at a flow temp of 80 C modulation point 5 C the displa...

Страница 26: ...al return temp at the moment of control stop during HTG demand A control stop occurs when the flow temp equals the flow temp set point 5 C HTG cut in temperature actual return temperature at the momen...

Страница 27: ...boiler set points and values Using the m key press repeatedly until flashing dot appears in the code display Then select the required code or etc using the s key Code Description Read out example Actu...

Страница 28: ...t the required code 2 3 or 4 etc using the s key and read off the relevant value Code t Description 1 37 Display of failure code see Par 10 2 2 03 Operating mode during failure 3 53 Flow temperature d...

Страница 29: ...tenance Instructions These manufactures Instructions must NOT be taken as overriding statutory obligati ons Failure to install this appliance correctly could result in an unsafe condition which can le...

Страница 30: ...stem should slope towards the supply ope ning Room sealed terminals should comply with the Gastec QA requirements for both hori zontal and vertical outlet constructions Care should be taken when sitin...

Страница 31: ...cordance with BS 6644 and BS 5440 compartment ventilation For maximum flue air inlet length see table in Par 7 3 5 For installations where supply and discharge points are in two different pressure zon...

Страница 32: ...supply Material Single walled rigid or flexible aluminium stainless steel and plastic to comply with building regulations 7 3 4 Single boiler conventional flue Fig 07 Flue gas discharge duct without b...

Страница 33: ...ver the flue system please contact our technical department for calculation to be undertaken 7 3 5 Single boiler room sealed flue Fig 08 Flue gas discharge duct without bends single boiler room sealed...

Страница 34: ...utlet Air inlet The Remeha Quinta boilers twin connection only are capable of operating with the air inlet and flue outlet in different pressure zones CLV System There are some restrictions to the flu...

Страница 35: ...d be filled with mains cold water for the UK this will usually have a pH of between 7 and 8 Pressurised installations with a boiler system content ratio of 1 10 or less should not require water treatm...

Страница 36: ...e flushing takes place especially if cleansing chemicals are used to assist the process IMPORTANT Under no circumstances is the boiler to be operated with cleaning che micals in the system To Summaris...

Страница 37: ...TE The boiler is suitable for both natural gas and propane firing It is supplied as standard set for natural gas therefore an adjustment to the gas valve and the fan speed setting must be carried out...

Страница 38: ...nd turns off the HTG or boiler pump Fig 10 DHW three way valve resistance graph The boiler flow temperature is boosted to the DHW set point DHW control stop set point see Par 6 6 7 and 6 6 10 When the...

Страница 39: ...Remeha Quinta 45 65 40 Fig 11 Remeha Quinta with calorifier and three way valve 04W4HHS00001 Fig 12 Remeha Quinta with calorifier and DHW pump 04W4HHS00002...

Страница 40: ...seconds Safety time 3 seconds Anti hunting time 150 seconds Pump run on HTG 1 15 minutes Pump run on DHW 5 minutes 8 2 3 Fuse specification The boiler is protected by fuses on the main power supply l...

Страница 41: ...ntrol panel 8 2 6 Low water protection flow and content The Remeha Quinta 45 and 65 is supplied with a low water protection on the basis of temperature measurement see Fig 22 Boiler sensor resistance...

Страница 42: ...43 Fig 14 Terminal strip Remeha Quinta 45 and 65 04W4H7900001 remove fitted wire link to use see Par 8 9...

Страница 43: ...n the minimum and maximum value on the basis of the boiler flow temperature sensor This applies to both single and multiple boiler installations up to a max of 8 under the dictates of a room and or ou...

Страница 44: ...o core cable to terminals 1 and 2 Set the x value of the boiler control operation parameter A to 1 2945 C3 K Optimising weather compensated boiler control for multiple boilers These controls are suppl...

Страница 45: ...0 to 90 C set the x value of the boiler control operation parameter A to 4 To set the ratio between voltage and the desired flow temperature see Par 6 6 15 and the graph below Output based fixed param...

Страница 46: ...ture Desired flow temperature o C Off On Input voltage V 10 20 30 40 50 60 70 80 90 100 0 1 2 3 4 5 6 7 8 9 10 10 20 30 40 50 60 70 80 90 100 Desired output 0 1 2 3 4 5 6 7 8 9 10 Off On Input voltage...

Страница 47: ...the sensor option 8 5 2 Primary flow control With a three way diverting valve Set the DHW control option parameter J to 00 02 connected to terminals 17 230 V power open spring returned and 18 With a...

Страница 48: ...the interlock control making sure that the terminal numbers are not mixed 9 COMMISSIONING 9 1 Initial lighting 1 Isolate main power supply 2 Remove the front panel 3 Check that the gas supply is avai...

Страница 49: ...surement of CO2 can lead to inaccuracies due to varying CO2 levels in the natural gas Proceed as follows Fig 20 Flue gas measure point 05W4H7900004 Correct gas air setup 16 1 Connect the flue gas anal...

Страница 50: ...allel axis each adjustment therefore alters the previous setting slightly Repeat the process 16 2 to 16 7 and re check the values as many times as necessary until they are correct at both loads 17 Rem...

Страница 51: ...at circuit it was protecting and rectify if faulty The fuse in the euro con nector The control box fuses 2 Boiler display shows a fault code For flashing digits If yes follow instruc tions in the tabl...

Страница 52: ...box Check the wiring on the boiler terminal strip and to the Gasmodul control box Table 17 Fault finding 10 2 Fault codes In the event of an error message both the code display and the t display will...

Страница 53: ...and also opens electrode is fitted properly is clean and set the gas air ratio is correct see Par 9 1 the gas pipe is not clogged or incorrectly sized the air supply and flue outlet is free of obstruc...

Страница 54: ...wrong direction or flow and return connections crossed 2 Fan not run ning Fan or motor failed Supply and or signal control cable poor connections or failed 2 Fan runs con tinuously or speed signal not...

Страница 55: ...rature in C resistance in Other Codes Control box failure Fault codes 3 6 7 10 13 14 15 16 17 41 42 44 and 60 Press the reset key When fault returns check wiring for short circuits When faults still r...

Страница 56: ...both part and full flame is flame core visible is flame geometry stable ignition probe earthing temperature sensors for loss current humidty on sensors Visual check of ignition ionisation probes if w...

Страница 57: ...ollowing cleaning the boiler should be re assembled in the reverse order re pla cing gaskets and joints where found necessary 4 All general cleaning should be carried out with a soft brush or damp clo...

Страница 58: ...ting Subject to alteration 55979 0602 R e m e h a Q u i n t a 4 5 6 5 Broag Ltd Head office Remeha House Molly Millars Lane Wokingham Berkshire RG 41 2QP Tel 0118 976977 Fax 0118 9783434 Email boilers...

Отзывы: