8
-
User manual
Dip-switch settings
1
2
All setting from EEPROM
0
0
Set Address 1- Baud 9600
1
0
Set Address 1 -Baud 38400
1
1
8
EnergyMeter-Programmer
The free interface program EnergyMeter-Programmer is the fastest way to configure
the device. The changes made to the program act on the register of the
device
.
To restore the default configuration, just press the button FACTORY DEFAULT.
Type of measure
Allows the selection of the measure RMS or DC only to
define the sign (positive or negative) of reading
Save on energy flash
It is possible to activate the saving of the counters
directly on the device’s flash memory
Report of transformation
In case you would use the TA and / or TV, you can define
the transformation ratio for the current input and
voltage input, the default ratio is 1:1
Filter
Allows to insert a filter on reading in order to get more
speed in responding (value 1) or a more stable and
accurate measurement ( value 5 ). By default the value
is set to 2. You can choose between intermediate values
already set or manually enter the desired filter by
choosing the CUSTOM option from the menu.
In this case, you can set the following parameters:
filtering in DC, filtering in AC (default value 5 ), Frequency
measurement on Current channel
CAUTION
: Magnetic fields of high intensity can vary the values measured by the
transformer. Avoid installation near permanent magnets, electromagnets or iron
masses that induce strong changes in the magnetic field. If any irregularity, to reorient
or move the transformer in the area most appropriate.
9
Modbus Register Map
See
paragraph 9, page 15.