20
-
Manuale d’uso
Register
Name
Comment
Register Type R/W Default
Value
Range
Modbus
Address
I MAX 100
Max RMS Current (mA/100) in
hundredths
Signed long
(LSW first)
R/W
40223
40224
I min 100
Min RMS Current (mA/100) in
hundredths
Signed long
(LSW first)
R/W
40225
40226
P MAX 100 Max RMS Power (W/100) in
hundredths
Signed long
(LSW first)
R/W
40227
40228
P min 100
Min RMS Power (W/100) in
hundredths
Signed long
(LSW first)
R/W
40229
40230
Q MAX 100 Max Reactive Power (VAR/100) in
hundredths
Signed long
(LSW first)
R/W
40231
40232
Q min 100
Min Reactive Power (VAR/100) in
hundredths
Signed long
(LSW first)
R/W
40233
40234
S MAX 100
Max Apparent Power (VA/100) in
hundredths
Signed long
(LSW first)
R/W
40235
40236
S min 100
Min Apparent Power (VA/100) in
hundredths
Signed long
(LSW first)
R/W
40237
40238
Cosφ MAX 100 Max Cosφ in hundredths
Signed long
(LSW first)
R/W
40239
40240
Cosφ min 100 Min Cosφ in hundredths
Signed long
(LSW first)
R/W
40241
40242
Frequency MAX
100
Max Frequency (Hz/100) in
hundredths
Signed long
(LSW first)
R/W
40243
40244
Frequency min
100
Min Frequency (Hz/100) in
hundredths
Signed long
(LSW first)
R/W
40245
40246
THD MAX 100 Max THD in hundredths
Signed long
(LSW first)
R/W
40247
40248
THD min 100 min THD in hundredths
Signed long
(LSW first)
R/W
40249
40250
Command
Flash settings save command =
0xC1C0;
Reset command = 0xC1A0;
Load Energy command = 0xBABA
(energy to load must be written in
Command_aux);
Load Positive Energy command =
0xBABB (positive energy to load must
be written in Command_aux);
Load Negative Energy command =
0xBABC (negative energy to load
must be written in Command_aux);
Unsigned short R/W
0
40252
Command aux Auxiliary Register for Energy
Command (see command register)
Float
(LSW first)
R/W
0
40253
40254