Air curtains

Installation, mounting

Rules for location - correct installation

Install the curtains above the entrance door with the 

outlet slot near the side of the door and with the intake 

side in the direction of the room.

Observe the instructions listed in the chapter "Usage 

and operating conditions".

Place the curtain with the outlet slot as close as possi-

ble to the wall and as close as possible to the upper 

edge of the door opening so that air is prevented from 

penetrating through an unwanted gap.  The width of the 

curtain must correspond at least to the width of the door 

opening.  A partial overlapping on the sides increases 

the efficiency.  When designing the hanging, a minimum 

of space must be maintained for connecting the media 

above the curtain (we recommend at least 150 mm); 

easy access to all the service parts of the curtain must 

also be ensured - see below and make sure that the 

space for intake and exhaust is not restricted by ob-

stacles or other screening.  The device must be located 

at a safe distance from inflammable materials according 

to the appropriate laws.

The curtains are designed for hanging on M8 threaded 

bars with the help of hanging profiles (standard equip-

ment of the curtain); as a variation, C1 curtains can be 

hung on wall hanging consoles (optional accessory).

Safety instructions

  Only professionally trained personnel, who have 

been instructed as to the possible dangers regarding 

the tasks entrusted to them, may mount the device, put 

it into operation and perform maintenance work on it.

  When handling, mounting and doing repair and 

maintenance work, observe the safety instructions listed 

in the appropriate sections of the documentation.

  When designing the fastenings for the device and 

also when carrying out the actual installation, respect 

the weight listed for the product!

  The connection of the device must comply with the 

appropriate safety norms (before putting into operation, 

for example, it is necessary to carry out a final electrical 

inspection).

Figure 3 

- installation above entrance door

Service procedures

For the location of the curtain, it is important that enou-

gh space is provided for maintenance and service.  

Such space depends on the type of curtain, see illus. 4.

Check before mounting

Before the actual mounting, it is necessary to carry out 

the following checks: 

  intactness of the delivery 

  (its completeness according to the delivery receipt)

  parameters of the voltage system and of the connec-

ted power. 

The defects ascertained must be eliminated before 

mounting begins.

Procedure for mounting the curtains

Mounting on hanging bars and hanging profile on 

the upper part of the C1 and D2 curtains

  Adjust the length of the threaded bars according  

  to the height of the hanging.

  Affix the M8 hanging bars to the construction  

  (to the ceiling).

  Screw the nuts and washers to the lower end of the 

bars in the following order: 

M8 nut - 8.4 washer - M8 nut - 8.4 washer - rectangu-

lar binding washer - rectangular binding washer - 8.4 

washer - spring washer - M8 nut 

Figure 4 

- service procedures

Service procedures for the 
C1 curtain

  removable intake panel 

(fuses, terminals for the electri-
cal connection)

Service procedures for the D" 
curtain

  removable intake panel 

(fuses, filtration insert)

  service panel  (terminals for 

the electrical connection)

Figure 5 

- hanging profile

hanging bar M8

M8 nut, 8.4 washer

binding washers

M8 nut, 
spring washer

hanging profile

Содержание DoorMaster C1

Страница 1: ...INSTALLATION AND OPERATING INSTRUCTIONS Air curtains C1 D2 04 2013...

Страница 2: ...exchangers 10 Mounting 11 Electrical connection 12 Putting into operation 13 Mounting of accessories 14 Controllers and room thermostats 16 Connection diagrams 17 Chaining of curtains 22 Operating an...

Страница 3: ...xplosion The version with electric heating and the version without heating can be operated at temperatu res as low as 5 C provided there is no condensation in the environment The version with a water...

Страница 4: ...er electric heater heating output Information and safety plates Plates with the warning sign Attention electric device on the safety covers of the wiring Inlet and outlet for heating water version W P...

Страница 5: ...erve the safety instructions listed in the appropriate sections of the documentation When designing the fastenings for the device and also when carrying out the actual installation respect the weight...

Страница 6: ...the curtains in the C1 series Figure 7 basic dimensions of the curtains in the D2 series Size A ZAV Hanging on hanging profile NKC Hanging on wall console Size A W curtain with water heating E1 E2 cu...

Страница 7: ...c sidewall cover for the wiring Figure 9 basic description of D2 series curtain adjustable outlet screen service panel that can be opened plastic sidewall internal aluminum sidewall removable intake p...

Страница 8: ...7 68 II Step Airflow m h 950 1 400 1 850 850 1 250 1 700 Acoustic pressure dB A 53 55 56 51 53 54 Acoustic output dB A 65 67 68 63 65 66 I Step Airflow m h 800 1 200 1 600 700 1 050 1 450 Acoustic pre...

Страница 9: ...74 76 77 78 73 75 76 77 I Step Airflow m h 1 600 2 400 3 250 4 000 1 600 2 400 3 250 4 000 Acoustic pressure dB A 55 56 58 59 53 55 56 57 Acoustic output dB A 70 72 73 74 69 71 72 73 DoorMaster D2 D2...

Страница 10: ...electric power page 12 Dismounting of the C1 service panels Dismounting procedure Loosen the fast closures located in the openings in the intake panel Do the loosening with a screwdriver by turning th...

Страница 11: ...n are intended for the thermostatic valve connection and are closed with brass plugs refer to the section Accessory Installation on page 14 Wiring It is necessary to ensure safety during this activity...

Страница 12: ...50 Hz power supply system Connect the electric heater to the LE Q1E Q2E Q3E terminals c Door Contact Connection If the door contact is used connect it to the DK1 DK2 terminals These terminals are inte...

Страница 13: ...from the power supply When connecting the valve observe the instructions included in these Installation and Ope rating Instructions Connect the valve Remove the laminated side wall on the header side...

Страница 14: ...tic valve 3 4 with thermostatic regulator and separa te sensor thermo valve accessory Extension 3 4 65mm internal external thread thermo valve accessory Elbow 90 3 4 L 40mm double ended thread thermo...

Страница 15: ...heater to be switched on off Attention To ensure their proper functioning the heater thermo static controllers and room thermostats must be situa ted within the area below the air curtain so they can...

Страница 16: ...r curtain chaining assembly according to the type refer to the Air Curtain Chai ning section page 21 Figure 23 C1 E1 TR air curtains connection X1 Main power connection supply L1 L2 L3 N PE Input volt...

Страница 17: ...at single stage terminals LE Q3E XS Terminals for air curtain chaining assembly according to t the type refer to the Air Curtain Chaining section page 21 Figure 24 C1 E2 air curtains connection Wiring...

Страница 18: ...ion terminals STA21 VVI 46 20 TVW E thermo electric valve Figure 27 W and C1 N TR air curtains connection X1 Main power connection supply L N PE Input voltage terminals DK1 DK2 Door contact connection...

Страница 19: ...ion terminals DK DK Door contact connection terminals XV Fan controller connection terminals Q1 1 Speed stage Q2 2 Speed stage Q3 3 Speed stage the highest speed or two pole switch breaker connection...

Страница 20: ...ng control Possibility for connection of door contact 1 Number of speed steps Three step speed controller 0 1 2 3 Number of heating steps Three step heating controller 0 1 2 3 Room thermostat on off w...

Страница 21: ...e side wall bulging will be left be tween them The electrical interconnection of the connected air curtains is only possible by external cabling Wiring a Fan Control The maximum number of air curtains...

Страница 22: ...of its type designation This version enables direct connection of the subse quent air curtain s electric heater control to the installed terminals XS allowing the switching of chained electric heater...

Страница 23: ...ervice life the user is ob liged to perform regular inspections of the electrical equipment at intervals in accordance with the applicable legal regulations For a list and frequency of regular inspect...

Страница 24: ...ge inspection by an expert Expert Check Expert checking of the device can only be performed by professionally trained persons who have been informed of possible dangers arising from the assignments wh...

Страница 25: ...parts and service materials When disposing of materials it is necessary to observe the applicable local environmental protection and waste disposal re gulations In case of final liquidation of the de...

Страница 26: ...or a part must not be printed or copied without prior written permission from REMAK a s Zubersk 2601 Ro nov pod Radho t m These Installation and Operating Instructions are the sole property of REMAK...

Страница 27: ...27 Air curtains...

Страница 28: ...EMAK a s Zubersk 2601 756 61 Ro nov pod Radho t m tel 420 571 877 878 fax 420 571 877 877 email remak remak cz internet www remak cz V robce si vyhrazuje pr vo zm ny bez p edchoz ho upozorn n R0803110...

Отзывы: