Air curtains

Application, Operating Conditions and Construction

Information from the manufacturer

DoorMaster door curtains are manufactured in compli-

ance with the valid Czech and European technical regu-

lations and technical standards.

Doormaster air curtains form an unobtrusive aerodyna-

mic barrier in order to suppress the free flow of air be-

tween an inside and outside environment, at the entran-

ce to a building for example, and an environment with 

various conditions (different temperatures, dustiness, 

insects etc).  A second integral function of the curtain is 

the mixing of the air that remains after entering with the 

air that has been heated in the room where the curtain 

is installed, which reduces the negative feeling evoked 

by the flow of cool air.  The manufacturer recommends 

the use of a curtain without heating (version N) only in 

particular cases where there is a reason for it (to se-

parate an air-conditioned room for example) when the 

use of built-in heating is unsuitable. The curtains are 

to be installed and used only in compliance with this 

documentation.  Any other usage does not comply with 

their designated purpose.Neither the manufacturer nor 

the supplier can assume responsibility for damages 

that arise from such misusage, and the user carries 

the whole risk. The operating and service personnel 

must have access to the mounting and operating docu-

mentation, and it is expedient to place it in the vicinity 

of the curtain. The valid safety instructions, norms and 

generally recognized technical regulations are to be re-

spected when handling, assembling, connecting to the 

mains, putting into operation, as well as during repair 

and maintenance work on the equipment.  All conne-

ctions of the device must comply with the appropriate 

safety standards. Any changes and modifications of the 

units that might influence safety may not be done wit-

hout the agreement of the manufacturer/supplier.  The 

same applies to the installing and setting of protection  

equipment and valves. Before installing and using, it is 

necessary to familiarize yourself with the following in-

structions and to respect them.

Usage and operating conditions

  DoorMaster air curtains are designed for inside in-

stallation in a dry environment in a horizontal position 

above the door opening.  The curtains are not intended 

for vertical application and cannot be installed next to 

the door opening.  The maximum height recommended 

for the installation is 2.5 m for curtains of the C1 series 

and 3.0 m for those of the D2 series.

  The curtain can operate in air void of coarse dust 

particles, lubricants, chemical vapors and other con-

taminants.  The curtain is intended for an environment 

with a normal influence classification (ČSN 33 2000-1 

ed.2). Its usage is prohibited in an aggressive environ-

ment, outdoors, in a moist environment with dangerous 

condensation or in an environment with a dangerous 

explosion!  The version with electric heating and the 

version without heating can be operated at temperatu-

res as low as -5 °C (provided there is no condensation 

in the environment).  The version with a water exchan-

ger (W) is not safeguarded against freezing and must 

be installed in a non-freezing area, i.e. +5 °C to +40 °C.  

Otherwise, a sufficient supply of heated water must be 

provided so that the medium in the water exchanger 

does not freeze.

  Door curtains are intended for connecting to the po-

wer-supply system N+PE /50Hz or -

N+PE /50 Hz (according to the type or heating of the 

curtain).  The main lead-in must be properly protected 

with the possibility of a safety disconnection in order to 

ensure a non-voltage state.  The fuse of the main lead-

-in must be equipped with a shut-off release, which is 

an indispensable component of the protection system 

for an air curtain against over-heating.  The electrical 

connection must comply with the diagram. A curtain in 

the standard version is prepared for connecting external 

drivers. The external drivers (shut-off switches) must 

be dimensioned at least to the value for inductive load, 

which is listed in the corresponding tables of this docu-

mentation.

  As standard equipment, the door curtains are fur-

nished with fan motors that have thermal contacts led 

out to the cable that ensures disconnection of the power 

supply to the motor or to the electric heating when there 

is an over-load.  Fuses provide for short-circuit protecti-

on of the motor and of the control circuits.  The fans are 

furnished with motors that have thermal insulation for 

the winding of the F class. 

  Curtains with water heat exchanger are intended 

with no limitations for higher medium temperatures (up 

to 70 °C). For even higher flow temperature is it nece-

ssary to fit thermostatically controlled inlet valve TVW 

TVW-P or-R and the valve head has to limit the heat 

transfer rate to a maximum temperature of 40 ° C (tem-

perature of the outlet air from the air curtain).

The maximum permissible operating pressure of the he-

ating water in the exchanger is 1.5 MPa.  When conne-

cting pipes are used to connect the exchangers, their 

maximum permissible operating pressure (1.0 MPa) 

must be respected.

  The level of acoustic output that is emanated with 

the air from the device is listed below in the correspon-

ding tables for the appropriate types.

Construction of the air curtain

C1 curtains

The curtain's construction is frameless with covering 

panels made of varnished sheet metal in the shade 

RAL 9002 and with plastic sidewalls.  The components 

used are from leading European manufacturers: special 

tangential fans from the company Punker and energy-

-saving EBM motors (with an input power of only 130W 

for a length of 1 m), a two-row  CU/Al water exchanger 

(version W) in all lengths with one connection for the 

media, an electric exchanger with stainless coiled hea-

ting rods (two outputs - version E1 and E2). The over-all 

electric protection of the covered curtains is IP 20.

D2 curtains

The internal chassis with covering panels is made of 

varnished sheet metal in the shade RAL 9002.  

Содержание DoorMaster C1

Страница 1: ...INSTALLATION AND OPERATING INSTRUCTIONS Air curtains C1 D2 04 2013...

Страница 2: ...exchangers 10 Mounting 11 Electrical connection 12 Putting into operation 13 Mounting of accessories 14 Controllers and room thermostats 16 Connection diagrams 17 Chaining of curtains 22 Operating an...

Страница 3: ...xplosion The version with electric heating and the version without heating can be operated at temperatu res as low as 5 C provided there is no condensation in the environment The version with a water...

Страница 4: ...er electric heater heating output Information and safety plates Plates with the warning sign Attention electric device on the safety covers of the wiring Inlet and outlet for heating water version W P...

Страница 5: ...erve the safety instructions listed in the appropriate sections of the documentation When designing the fastenings for the device and also when carrying out the actual installation respect the weight...

Страница 6: ...the curtains in the C1 series Figure 7 basic dimensions of the curtains in the D2 series Size A ZAV Hanging on hanging profile NKC Hanging on wall console Size A W curtain with water heating E1 E2 cu...

Страница 7: ...c sidewall cover for the wiring Figure 9 basic description of D2 series curtain adjustable outlet screen service panel that can be opened plastic sidewall internal aluminum sidewall removable intake p...

Страница 8: ...7 68 II Step Airflow m h 950 1 400 1 850 850 1 250 1 700 Acoustic pressure dB A 53 55 56 51 53 54 Acoustic output dB A 65 67 68 63 65 66 I Step Airflow m h 800 1 200 1 600 700 1 050 1 450 Acoustic pre...

Страница 9: ...74 76 77 78 73 75 76 77 I Step Airflow m h 1 600 2 400 3 250 4 000 1 600 2 400 3 250 4 000 Acoustic pressure dB A 55 56 58 59 53 55 56 57 Acoustic output dB A 70 72 73 74 69 71 72 73 DoorMaster D2 D2...

Страница 10: ...electric power page 12 Dismounting of the C1 service panels Dismounting procedure Loosen the fast closures located in the openings in the intake panel Do the loosening with a screwdriver by turning th...

Страница 11: ...n are intended for the thermostatic valve connection and are closed with brass plugs refer to the section Accessory Installation on page 14 Wiring It is necessary to ensure safety during this activity...

Страница 12: ...50 Hz power supply system Connect the electric heater to the LE Q1E Q2E Q3E terminals c Door Contact Connection If the door contact is used connect it to the DK1 DK2 terminals These terminals are inte...

Страница 13: ...from the power supply When connecting the valve observe the instructions included in these Installation and Ope rating Instructions Connect the valve Remove the laminated side wall on the header side...

Страница 14: ...tic valve 3 4 with thermostatic regulator and separa te sensor thermo valve accessory Extension 3 4 65mm internal external thread thermo valve accessory Elbow 90 3 4 L 40mm double ended thread thermo...

Страница 15: ...heater to be switched on off Attention To ensure their proper functioning the heater thermo static controllers and room thermostats must be situa ted within the area below the air curtain so they can...

Страница 16: ...r curtain chaining assembly according to the type refer to the Air Curtain Chai ning section page 21 Figure 23 C1 E1 TR air curtains connection X1 Main power connection supply L1 L2 L3 N PE Input volt...

Страница 17: ...at single stage terminals LE Q3E XS Terminals for air curtain chaining assembly according to t the type refer to the Air Curtain Chaining section page 21 Figure 24 C1 E2 air curtains connection Wiring...

Страница 18: ...ion terminals STA21 VVI 46 20 TVW E thermo electric valve Figure 27 W and C1 N TR air curtains connection X1 Main power connection supply L N PE Input voltage terminals DK1 DK2 Door contact connection...

Страница 19: ...ion terminals DK DK Door contact connection terminals XV Fan controller connection terminals Q1 1 Speed stage Q2 2 Speed stage Q3 3 Speed stage the highest speed or two pole switch breaker connection...

Страница 20: ...ng control Possibility for connection of door contact 1 Number of speed steps Three step speed controller 0 1 2 3 Number of heating steps Three step heating controller 0 1 2 3 Room thermostat on off w...

Страница 21: ...e side wall bulging will be left be tween them The electrical interconnection of the connected air curtains is only possible by external cabling Wiring a Fan Control The maximum number of air curtains...

Страница 22: ...of its type designation This version enables direct connection of the subse quent air curtain s electric heater control to the installed terminals XS allowing the switching of chained electric heater...

Страница 23: ...ervice life the user is ob liged to perform regular inspections of the electrical equipment at intervals in accordance with the applicable legal regulations For a list and frequency of regular inspect...

Страница 24: ...ge inspection by an expert Expert Check Expert checking of the device can only be performed by professionally trained persons who have been informed of possible dangers arising from the assignments wh...