2.

2.  Lower air pressure allows for smaller capacity, lower cost 

dehydration equipment, where required.

3.  Lower air or nitrogen pressure can reduce water delivery 

time when the system actuates, and in some cases, may 
eliminate the need for an accelerator.

4.  For systems supplied with nitrogen, low supervisory pres-

sure reduces the quantity of nitrogen required to maintain  
the system pressure.

The Model DDX-LP PrePaK system is initially pressurized with 

air provided by the factory-installed air compressor.  Superviso-
ry pressure is provided and maintained by the integral nitrogen 
generator and is monitored by a system pressure switch.

Note:

  Compressed air is not to be considered dry air and 

may contribute to internal corrosion of piping, and/or ice plugs 
in system piping.  The factory-installed air compressor should 

be utilized for initial fill only and make-up air only when the nitro

-

gen generator is not active.

When a fire sprinkler operates, there will be a loss of air or Ni

-

trogen pressure in the sprinkler system piping which will cause 
the Model LP-Dry Pilot Actuator to open. The opening of this 
device allows the Model DDX-LP valve to flow water into the 
system piping. 

A Model B Hydraulic Manual Emergency Releasing station 

is standard equipment in the Reliable DDX-LP PrePaK system. 
It consists of an aluminum nameplate mechanically attached 
to a ball valve. The valve handle in its OFF position is guarded 
against accidental turning to the ON position (and system dis-
charge) by a nylon cable tie provided with the DDX-LP PrePaK 
system assembly. The cable tie is designed to allow, in case of 
an emergency, forceful turning of the valve handle to the ON 
position.

Approvals

• 

The Model DDX-LP N2-Blast PrePaK dry-pipe system 
is FM Approved as a factory-assembled Dry-pipe Sys-
tem to Approval Standard 1011/1012/1013, Deluge 
and Preaction Sprinkler Systems.

• 

The Model DDX-LP dry-pipe valve and trim are FM Ap-
proved and cULus Listed.

• 

The South-Tek N2-Blast® Model FPS-900-RS nitrogen 
generator is FM Approved to Approval Standard 1035, 
Nitrogen Generators for Corrosion Mitigation.

     

        

Technical Data

1.  The Reliable Model DDX-LP PrePaK system is rated for 

a minimum water supply pressure of 20 psi (1.4 bar). 
The 2”, 2-1/2”, 3”, and 8” sizes are rated for a maximum 
pressure of 250 psi (17.2 bar), and the 4” and 6” sizes 
are rated for a maximum pressure of 300 psi (20.7 bar). 
Water temperature must be maintained between 40°F 
and 140°F (4°C and 60°C).

2.  Friction loss, expressed in equivalent length of Schedule 

40 pipe and based on Hazen-Williams Formula is:

System Size

Equivalent Length

2” (50 mm)

19.4 ft (1.3 m)  

2½” (65 mm)

24.5 ft (1.8 m)  

3” (80 mm) 

28.9 ft (3.8 m)  

4” (100 mm)

 32.8 ft (17.7 m)  

The equivalent length in the table above includes the Mod-
el DDX-LP valve, supply manifold tee, supply side control 
valve, and the section of pipe above the Model DDX-LP 
valve.
3.  Shipping Weight:

System Size

Weight

2” (50mm)

950 lbs (431 kg)

2-1/2” (65mm)

3” (80mm)

4” (100 mm)

1075 lbs (488 kg)

4.  Refer to Figure 1 for dimensions.

The following is a list of Technical Data Bulletins which de-

scribe the valves and devices which are used in the system:

Device

Reliable Bulletin #

(unless otherwise noted)

Model DDX Deluge Valve 

Reliable Bulletin 519

Model DDX-LP Dry Pipe System

Reliable Bulletin 338

Low Air Pressure Switch

Potter, 5401564

Alarm Pressure switch

Potter, 5400928

Installation Requirements

The automatic sprinklers utilized with the DDX-LP PrePaK 

system  must be UL and/or ULC Listed or FM Approved, as 
applicable.

The steel enclosure and all the interconnecting piping must 

be located indoors in a readily visible and accessible location 
and in an area that can be maintained at a minimum tempera-
ture of 40°F (4°C). 

Note:

 Heat tracing is not permitted.  The 

Model DDX-LP PrePaK system operation is controlled by the 
Model LP Dry Pilot Actuator. The introduction of moisture into 
the system piping exposed to freezing temperatures can cre-
ate ice blockage, which could prevent proper system operation.  
As a minimum, the air supply should be taken from the area 
of lowest temperature within the protected area. The air sup-
ply system must be carefully designed to prevent plugging by 
frost deposits. Special requirements, such as those in FME&R 
“Installation Guidelines for Refrigerated Storage” may need to 
be incorporated.

Optional Seismic Kit

 Reliable part number 6501200041 (25” x 28” cabinet for 2” 
-4” systems without nitrogen generator) and 6501200042 (30” 
x 33” cabinet for 6” and 8” systems, and all units with nitrogen 
generator) are seismic upgrade kits required to make the Re-
liable PrePaK OSHPD compliant. One kit is required for each 
PrePaK (reference Caution Sheet 331).

Содержание N2-Blast DDX-LP PrePaK

Страница 1: ...rePaK system incor porates a South Tek Systems FPS 900 pressure swing adsorp tion N2 Blast nitrogen generator complete with independent air compressor nitrogen storage tank and control system The nitr...

Страница 2: ...ar The 2 2 1 2 3 and 8 sizes are rated for a maximum pressure of 250 psi 17 2 bar and the 4 and 6 sizes are rated for a maximum pressure of 300 psi 20 7 bar Water temperature must be maintained betwee...

Страница 3: ...3 Fig 1...

Страница 4: ...nal box mounted on the inside of the enclosure All field wiring connec tions are made at this terminal box A separate power connection is provided for the optional air compressor Note The air compress...

Страница 5: ...16 Secure the handle of the Model B Manual Emergency Station in the OFF position with a nylon tie supplied with the assembly Inspection And Testing Of The DDX LP PrePaK Systems Refer to Figure 2 1 Wat...

Страница 6: ...6 Fig 2 Model DDX LP Low Pressure Dry Pipe System Valve Legend Note Some items omitted for clarity...

Страница 7: ...7 Fig 3...

Страница 8: ...er has drained then close Note Leaving the condensate drain open for an extended pe riod of time may allow excess air nitrogen to bleed off and result in accidental release of the Model LP Dry Pilot A...

Страница 9: ...r can lead to incorrect gas supply The nitrogen generator produces nitrogen at a low flow rate which quickly dissipates into the air Nitrogen is not poison ous but do not directly inhaled since high c...

Страница 10: ...not adjust the factory preset cut in and out pressure without first consulting with South Tek Systems Patented BlastOff Leak Detection System The BlastOff Leak Detection is a patented feature which se...

Страница 11: ...r further troubleshoot ing Low System Pressure Alarm Mode Lo n2 The low system pressure alarm activates when a sys tem pressure is detected below the normal functioning limits of the nitrogen generato...

Страница 12: ...esponding filter housings Hand tighten only After replacing the filters check the filter bowls for leaks by turn ing on the unit momentarily Turn the unit off to reinstall the front cover and then pow...

Страница 13: ...Fig 5 Nitrogen Generator Filter Locations 13...