Bulletin 044
December 2022

Page 7 of 9

www.reliablesprinkler.com

6 in. [150 mm]

MAXIMUM

OBSTRUCTION

CEILING

NONCOMBUSTIBLE INSULATION, SECURED ABOVE
SPRINKLERS WITH WIRE NETTING OR EQUIVALENT

UPPER
DECK

SEE NOTE 2

PIPE SHALL BE LOCATED A MAXIMUM OF 6 in. (150 mm)

ABOVE THE TOP OF THE CEILING (OR INSULATION), OR
A MAXIMUM OF ONE-THIRD (1/3) THE DEPTH OF THE
CONCEALED SPACE ABOVE THE TOP OF THE CEILING,
WHICHEVER IS SMALLER.

SEE NOTE 1

WHEN OFFSETTING CPVC PIPE OVER
OBSTRUCTION, A CCS SPRINKLER MUST BE

INSTALLED DIRECTLY ON THE PIPE OVER THE
OBSTRUCTION.

INSTALLATION NOTES:

1.

DISTANCE EVALUATED AS PART OF THE cULus LISTING: 12 in. TO 36 in. (300 mm TO 900 mm). NFPA 13 PERMITS INSTALLATION OF

THE SPRINKLER WHERE THIS DISTANCE IS LESS THAN 12 in. (300 mm).

2.

DEFLECTOR DISTANCE BELOW BOTTOM OF JOIST TO 1-1/2 in. TO 4 in. (38 mm TO 100 mm) BELOW BOTTOM OF TOP CHORD. IN NO
CASE SHALL DEFLECTOR BE ABOVE THE BOTTOM OF THE SOLID OR COMPOSITE WOOD JOIST.

3.

INSTALL SPRINKLER WITH FRAME ARMS PARALLEL TO PIPE.

NOTE 3

HYDRAULIC DESIGN AREA REQUIREMENTS

1.

WET SYSTEM:  DRAFT CURTAINS (OR FULL HEIGHT WALLS) MUST BE PROVIDED AT 1000 ft

2

 (93 m

2

) MAXIMUM AREAS. CALCULATE

ALL SPRINKLERS WITHIN THE COMPARTMENTED AREA.

2.

ADDITIONAL SPRINKLERS THAT ARE REQUIRED FOR PROTECTION OF CPVC PIPING THAT IS OFFSET OVER AN OBSTRUCTION DO

NOT NEED TO BE INCLUDED IN THE DESIGN AREA.

SPRINKLER SPACING AND COVERAGE AREA

A. 16  ft (4.9 m) MAXIMUM BETWEEN SPRINKLERS

B.

6 ft (1.8 m) MINIMUM BETWEEN SPRINKLERS

C.

256 ft

2

 (23.4 m

2

) MAXIMUM COVERAGE AREA PER SPRINKLER

Figure 5

Solid Wood or Composite Wood Joist Filled with Non-Combustible Insulation, CPVC Pipe

Draft Curtains: Required at 1000 Ft

2

 (93 m

2

)

Содержание KFR-CCS

Страница 1: ...damage the sprinkler and will void the manufacturer s warranty Damaged sprinklers must be immediately replaced A leak tight NPT R1 2 sprinkler joint can be obtained with an installation torque of appr...

Страница 2: ...onal sprinklers that are required for protection of CPVC piping that is offset over an obstruction Maximum Distance Spacing Between Sprinklers Refer to Figures 2 through 7 Maximum Coverage Area Per Sp...

Страница 3: ...whichever is smaller Where the members at the bottom of the concealed space are greater than 6 in 150 mm tall installing CPVC piping directly on top of those members shall be permitted When using 1 i...

Страница 4: ...NCEALED SPACE ABOVE THE TOP OF THE CEILING WHICHEVER IS SMALLER SEE NOTE 1 HYDRAULIC DESIGN AREA REQUIREMENTS A WET SYSTEM WHERE DRAFT CURTAINS OR FULL HEIGHT WALLS ARE PROVIDED AT MAXIMUM AREAS OF 10...

Страница 5: ...E PROVIDED AT MAXIMUM AREAS OF 1000 ft2 93 m2 OR LESS CALCULATE ALL SPRINKLERS WITHIN THE COMPARTMENTED AREA 2 WET SYSTEM WHERE DRAFT CURTAINS OR FULL HEIGHT WALLS ARE NOT PROVIDED OR PROVIDED AT AREA...

Страница 6: ...R WHERE THIS DISTANCE IS LESS THAN 12 in 300 mm 1A WHERE CEILING IS NOT SUPPORTED BY JOISTS EXAMPLE SUSPENDED A C T MEASUREMENT POINT IS TOP OF CEILING 2 DEFLECTOR DISTANCE BELOW BOTTOM OF JOIST TO 1...

Страница 7: ...S THAN 12 in 300 mm 2 DEFLECTOR DISTANCE BELOW BOTTOM OF JOIST TO 1 1 2 in TO 4 in 38 mm TO 100 mm BELOW BOTTOM OF TOP CHORD IN NO CASE SHALL DEFLECTOR BE ABOVE THE BOTTOM OF THE SOLID OR COMPOSITE WO...

Страница 8: ...NOT SUPPORTED BY JOISTS EXAMPLE SUSPENDED A C T MEASUREMENT POINT IS TOP OF CEILING 2 DEFLECTOR DISTANCE BELOW BOTTOM OF JOIST TO 1 1 2 in TO 4 in 38 mm TO 100 mm BELOW BOTTOM OF TOP CHORD IN NO CASE...

Страница 9: ...C T MEASUREMENT POINT IS TOP OF CEILING 2 DEFLECTOR DISTANCE BELOW BOTTOM OF JOIST TO 1 1 2 in TO 4 in 38 mm TO 100 mm BELOW BOTTOM OF TOP CHORD IN NO CASE SHALL DEFLECTOR BE ABOVE THE BOTTOM OF THE S...

Отзывы: