Revision lines indicate updated or new data.

The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association, Factory 

Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable. Products 

manufactured and distributed by Reliable have been protecting life and property for over 90 years, and are installed and serviced by the most highly qualified 

and reputable sprinkler contractors located throughout the United States, Canada and foreign countries.

When installing Model F1FR LO Sprinklers, use the Model D 

Sprinkler Wrench. When installing Model F1FR LO Recessed 
Pendent or Sidewall Sprinklers, use the Model GFR1 Sprinkler 
Wrench. Any other type of wrench may damage these sprinklers. 

Note:

 A leak tight 

1

/

2

" NPT (R 

1

/

2

) sprinkler joint can be obtained 

with a torque of 8 - 18 ft-lb (11 - 24 N-m). Do not tighten sprinklers 
over maximum recommended torque. It may cause leakage or 
impairment of the sprinklers.

Glass bulb sprinklers have orange bulb protectors to minimize 

bulb damage during shipping, handling and installation. 
REMOVE THIS PROTECTION AT THE TIME THE SPRINKLER 
SYSTEM IS PLACED IN SERVICE FOR FIRE PROTECTION. 
Removal of the protectors before this time may leave the bulb 
vulnerable to damage. RASCO wrenches are designed to install 
sprinklers when covers are in place. REMOVE PROTECTORS 
BY UNDOING THE CLASP BY HAND. DO NOT USE TOOLS 
TO REMOVE THE PROTECTORS.

Temperature Ratings

Classification

Sprinkler 

Temperature

Maximum 

Ambient 

Temperature

Bulb 

Color

°F

°C

°F

°C

Ordinary

135

57

100

38

Orange

Ordinary

155

68

100

38

Red

Intermediate

175

79

150

66

Yellow

Intermediate

200

93

150

66

Green

High 

(1)

286

141

225

107

Blue

(1)

  Not Available for recessed sprinklers.

Maintenance

The Models F1FR LO and F1FR LO Recessed Sprinklers 

should be inspected and the sprinkler system maintained in 
accordance with NFPA 25. Do not clean sprinklers with soap 
and water, ammonia or any other cleaning fluids. Remove 
dust by using a soft brush or gentle vacuuming. Remove any 
sprinkler which has been painted (other than factory applied) 
or damaged in any way. A stock of spare sprinklers should be 
maintained to allow quick replacement of damaged or operated 
sprinklers. Prior to installation, sprinklers should be maintained 
in the original cartons and packaging until used to minimize the 
potential for damage to sprinklers that would cause improper 
operation or non-operation.

Sprinkler Types 

Standard Upright 
Standard Pendent 

Conventional 
Recessed Pendent 

Finishes 

(1)(2)

Standard Finishes

Sprinkler

Escutcheon

Bronze

Chrome Plated

White Polyester Coated 

(4)(5)

Brass

Chrome Plated 

(3)

White Painted 

(3)

Special Application Finishes

Sprinkler

Escutcheon

Electroless Nickel PTFE 

(6)

Bright Brass

Black Plated

Black Paint

Off White 

Satin Chrome

Electroless Nickel PTFE

Bright Brass

Black Plated

Black Paint

Off White

Chrome Dull

(1)

 Other finishes and colors are available on special order. Consult the 

factory for details.

(2)

 FM Approvals is limited to bronze and brass, chrome or black plated 

finishes only.

(3)

  FP Push-on/Thread-off escutcheon.

(4)

  cULus listed corrosion resistance. SIN R3622.

(5)

  FM Approved for SIN R3622, R3612

(6)

  cULus listed corrosion resistant SIN R3622 & R3612

Note:

 For 

1

/

2

" orifice pendent FM approved white polyester 

coated, cULus listed white and black polyester and Electroless 
Nickel PTFE Plated corrosion resistant sprinklers refer to 
bulletin 014.

Maximum Working Pressure

175 psi (12 bar)
SIN R3612 & R3622 cULus listed for 250 psi (17 bar)
100% Factory tested hydrostatically to 500 psi (34.5 bar)

Ordering Information

Specify:

1.  Sprinkler Model
2.  Sprinkler Type
3.  Orifice Size
4.  Deflector Type
5.  Temperature Rating
6.  Sprinkler Finish
7.  Escutcheon Type
8.  Escutcheon Finish (where applicable)

Note:

 When Model F1FR LO Recessed sprinklers are ordered, 

the sprinklers and escutcheons are packaged separately

.

EG. Printed in U.S.A. 12 / 15 