background image

2

136FG02

Technical data:

Models

Response

Deflector 

Orientation

Nominal 

K-factor

Thread Size

Max. 

Working 

Pressure

Min. 

Working 

Pressure

Temperature 

Rating

Finish

F1FR LO

Quick 

Response

Upright 

Pendent

Conventional

K 8.0

(115 metric)

3

/

4

" NPT

or

ISO7-1R 

3

/

4

175 psi 

(1)

7 psi

See “Temperature 

Ratings” Table

See  

“Finish Table”

Material Data:

Frame

Deflector

Load Screw

Cup

Washer

Bulb

DZR Brass

QM Brass

CDA Alloy 510

CDA Alloy 210, 220, 314, 316, 360

or

CDA Alloy 544

CDA Alloy 314

or

CDA Alloy 353 

Nickel Alloy 440 or Alloy 360 coated 

with PTFE Adhesive Tape

Glass

See “Installation Data” table from page 3 for more details.

(1)

  Model F1FR LO Pendent, Recessed Pendent, and Upright sprinklers (SIN R3612 and R3622) are cULus Listed for 250 psi (17 bar).

DEFLECTOR

LOAD SCREW

BULB 

WASHER

FRAME

CUP

Отзывы: