2002 Reliable Controls™ Corporation
Outputs
MA-T™ Dual Stage Triac Outputs
The MA-T™ model has a dual stage triac. The dual stage triac
can be connected to a two stage load.
!
Both triac stages are
OFF
when
the output is commanded to 0
volts.
!
The first stage triac (T1) is
ON
when the output is commanded
to 5 volts.
!
Both triac stages (T1 & T2) are
ON
when the output is
commanded to 10 volts.
Connect the two stages as
shown in the diagram below.
Dual Stage Triac States
Voltage
T1
T2
0
OFF
OFF
5
ON
OFF
10
ON
ON