4
MACH-Air™ VAV Controller
2002 Reliable Controls™ Corporation
Getting Started
!
Inputs four, five, and six (IN4, IN5, IN6) and outputs four and
five (OUT4, OUT5) are dedicated to air flow and motor
functions (see Inputs and Outputs).
!
Variable one (VAR1) of the MACH-Air™ is reserved for the
‘Flow Calibration Constant’.
!
MACH-Air™ network settings, such as baud rate, network
type, controller address, and last panel must be configured
using the SETUP-Tool™ (see SETUP-Tool).
!
A sample Control BASIC™ program is preloaded on the
MACH-Air™ VAV controller. This program is a template for
basic VAV operation.
!
The MACH-Air™ controller does not have a Real Time Clock.
The controller receives its time from a MACH1™, MACH2™,
or MACH-Global™ controller or an ETHER-Link™ portal that
is addressed as number one on the network.
!
The MACH-Air™ controller does not have an EIA-232 port. In
order to access a MACH-Air™ controller from a workstation,
it is necessary to connect to a MACH1™, MACH2™, or
MACH-Global™ controller, or an ETHER-Link™
portal on the
same network.
!
The X-Port™ converter is available to facilitate EIA-232
communications between the SMART-Net™ port of the
MACH-Air™ controller and any workstation or laptop. The X-
Port™ converter could also be used for remote access by
connecting a modem instead of a workstation.
Содержание MACH-Air
Страница 4: ...MACH AirTM VAV Controller iv 2001 Reliable Controls Corporation...
Страница 14: ...8 MACH Air VAV Controller 2002 Reliable Controls Corporation Installation MACH Air VAV Controller Orientations...
Страница 17: ...11 MACH Air VAV Controller Power Wiring 2002 Reliable Controls Corporation MACH Air VAV Controller Power Wiring...
Страница 43: ...37 MACH Air VAV Controller Notes 2002 Reliable Controls Corporation...