8
Systemübersicht Verdrahtung / System overview wiring / Présentation du système Câblage / Systemöversikt kabeldragning / Systeemoverzicht bedrading / Panoramica del sistema cablaggio / Vista
general del sistema del cableado / Přehled systému zapojení kabelů / Bekötés rendszeráttekintése / Vedere de ansamblu cablare sistem / Kablolama sistem genel bakış / Przegląd okablowania systemu
/ Обзор системы, кабельная разводка
R-Module
24 V
R-Module
24 V
R-Module
24 V
R-Module
24 V
R-Module
24 V
Base 24 V - Slave 4
230 V AC
24 V AC
230 V AC
24 V AC
Base 24 V - Slave 3
230 V AC
24 V AC
230 V AC
24 V AC
Base 24 V - Slave 2
230 V AC
24 V AC
Base 24 V - Slave 1
Base 24 V - Master
230 V AC
24 V AC
230 V AC
24 V AC
ZOBUS
ZOBUS
ZOBUS
ZOBUS
ZOBUS
SYSBUS
SYSBUS
1
ON DIP
2 3 4
1
ON DIP
2 3 4
1
ON DIP
2 3 4
1
ON DIP
2 3 4
1
ON DIP
2 3 4
Module Address
Module Address 1
Module Address 2
Module Address 3
Module Address 4
1
ON DIP
2 3 4
Module Address 0
1
ON DIP
2 3 4
Module Address 1
1
ON DIP
2 3 4
Module Address 2
230 V AC
24 V AC
230 V AC
24 V AC
230 V AC
24 V AC
U-Module
24 V
(
*
)
230 V AC
24 V AC
U-Module
24 V
(
*
)
230 V AC
24 V AC
U-Module
24 V
(
*
)
230 V AC
24 V AC
U-Module
24 V
(
**
)
U-Module
24 V
(
**
)
1
ON DIP
2 3 4
1
ON DIP
2 3 4
Module Address 3
Module Address 4
Trans-
former
Trans-
former
Trans-
former
Trans-
former
Trans-
former
Trans-
former
Trans-
former
Trans-
former
Trans-
former
Trans-
former
Trans-
former
Trans-
former
Trans-
former
SYSBUS
U-Module
24 V
(
**
)
U-Module
24 V
(
**
)
1
ON DIP
2 3 4
1
ON DIP
2 3 4
Module Address 5
Module Address 6
SYSBUS
U-Module
24 V
(
**
)
U-Module
24 V
(
**
)
1
ON DIP
2 3 4
1
ON DIP
2 3 4
Module Address 7
Module Address 8
(
*
)
Mixed circuit configuration
(
**
)
Fan coil or dehumidifier configuration
max. 12 Room Units radio controlled/bus
on each Base 24 V and R-Module 24 V
Cable Types:
▪
ZOBUS: I (Y) St Y 2 x 2 x 0.8 mm /
existing 2-core wire (max. 100 m length)
▪
SYSBUS: I (Y) St Y 2 x 2 x 0.8 mm (max. 500 m length)
▪
max. length between 2 Base 24 V: 250 m