REGULUS - TRS 5 Controller - www.regulus.eu
Settings HC
menu 5
F 5.4 - Day correction
menu 5.4
= paralelní posun k
ř
ivky
The day correction means a parallel shift of the heating curve during the daytime operating hours, since
depending on the outdoor temperature it is possible that the building may not be optimally heated with the set
characteristic. If the characteristic is not optimized, the following situation may occur:
in hot weather - the rooms are too cold
in cold weather - the rooms are too hot
In this case, one should gradually reduce the characteristic slope in steps of 0.2, each time raising the day
correction by 2-4
°C.
This procedure can be repeated several times as needed.
Setting range: from -10
°C to 50
°C
Default: 5
°C
F 5.5 - Night correction
menu 5.5
= paralelní posun k
ř
ivky
The night correction produces a parallel shift of the heating curve during the nighttime operating hours. If
a negative value is set for the night correction, the reference
fl
ow temperature is lowered accordingly during
the nighttime operating hours. In this manner, primarily at night, but also during the day when no-one is at
home, energy can be saved.
Example: A day correction of +5
°C and a night correction of -2
°C produces a reference
fl
ow
temperature in nighttime operation that is by 7
°C below that of daytime operation.
Setting range: from -30
°C to 30
°C
Default: -2
°C
F 5.6 - Comfort temperature boost
menu 5.6
= paralelní posun k
ř
ivky
The comfort temperature boost is added to the set day correction. In this manner it is possible to carry out
quick heating and/or a higher temperature in the living spaces at a certain time each day.
Setting range: from 0
°C to 15
°C
Default: 0
°C = vyp.
F 5.8 - Reference / actual -
menu 5.8
= switch-on hysteresis for additional heating
This setting determines the allowed undershoot of the heating circuit temperature under the calculated
reference
fl
ow temperature. If the heating circuit
fl
ow temperature falls below the reference temperature by this
value, the additional heating (R5) is activated after a delay of 5 minutes.
Setting range: -10
°C to 10
°C
Default: -2
°C
The additional heating (relay R5) is started when the
fl
ow temperature (in case of 2 heat circuits:
one of the
fl
ow temperatures)is below the reference
fl
ow temperature for 5 minutes continuously.
F 5.9 - Reference /
menu 5.9
= switch-off hysteresis
(only if sensor S4 is connected)
This settings determines the allowed overstepping of the heating circuit temperature to the calculated
reference
fl
ow temperature at sensor S4. If the temperature at S4 exceeds the reference
fl
ow temperature by
this value, the additional heating is switched off.
Setting range: 1
°C to 10
°C
Default: 2
°C
Caution