9
│
REGULUS - TRS 4 Controller - www.regulus.eu
D - ELECTRIC WIRING
Sensor side - max 12V
Mains side - 230V 50Hz
Note: If the RC21 remote controller or another room thermostat is connected, the bridge at S6 has to be
removed.
Note: If the hydraulic variant 4, 5 or 6 (page 5) is used, then the sensor of heating circuit 2 shall be connected
to terminal S3.
If an accumulation tank is used, the sensor can be connected to terminal S4 (see menu 7.4).
- Temperature sensors S1 – S6
(polarity freely selectable)
- Optional additional functions Z1/Z2
Terminal:
connection for:
-
Jumper terminal block S-
S1
sensor 1 outdoor sensor
S2
sensor 2 heating circuit
S3
sensor 3 heating circuit 2
S4
sensor 4 accumulation tank
S5
sensor 5 indoor sensor
S6
sensor 6 remote controller*
+
free
Z1
Optional / expansion
Z2
Optional / expansion
Use terminal block S- for connecting the
sensor earths of S1-S6.
The polarity is freely selectable.
The sensors S3-S6 are optional, depending
on the hydraulic variant chosen.
- Protective conductor PE, metal terminal block
- Neutral conductor terminal block N
- Mains phase conductor L
- Switch output R1-R4
- Floating contact at R5/R5I
Caution: Only suitable for 230V!
Terminal:
connection for:
N
Jumper terminal block N
L
Mains phase conductor L
R1
Heating circuit pump
R2
Mixing valve opens
R3
Mixing valve closes
R4
HC2 pump
R5
add. heating
R5I
add. heating
PE
The PE protective conductor
must be connected to the PE
metal terminal block!
jumper terminal block S
jumper terminal block N