22
REGULUS - TRS 4 Controller - www.regulus.eu
Special functions
menu 8
F 8 - Special functions
Menu
„8. Special functions”
is used to set basic
items and expanded functions.
The settings in this menu should only be
made by a specialist.
The menu is closed by pressing
„esc”
or selecting
„Exit special functions”
.
F 8.1 - Sensor calibration
menu 8.1 / 8.1.1 - 8.1.6
Deviations in the temperature values displayed, for example due to cables which are to long or sensors which
are not positioned optimally, can be compensated for manually here. The settings can be made for each
individual sensor in steps of 0.5 °C.
Offset S1...S6 per settings range : -10 °C...+10 °C
Default: 0 °C
Settings are only necessary in special cases at the time of initial commissioning by the specialist.
Incorrect measurement values can lead to unpredictable errors.
F 8.2 - Commissioning
menu 8.2
The commissioning help guides you through the necessary basic settings in the correct order, and provides
brief descriptions of each parameter in the display.
Pressing the
„esc”
key takes you back to the previous value so you can look at the selected setting again
or adjust it if desired. Pressing the
„esc”
more than once takes you back step by step to the selection mode,
thus cancelling the commissioning help (see also E 3).
May only be started by a specialist during commissioning! Observe the explanations for the
individual parameters in these instructions, and check whether further settings are necessary for
your application.
F 8.3 - Factory settings
menu 8.3
All of the settings that have been made can be reset, thus returning the controller to its delivery state.
The entire parametrization, statistics, etc. of the controller will be lost irrevocably. The controller
must then be commissioned once again.
F 8.4 - Expansions
menu 8.4
This menu can only be selected and used if additional options or expansion modules have been built into the
controller. The associated supplementary installation, mounting and operation instructions are then included
with the specific expansion.
F 8.5 - Mixer
menu 8.5
Settings are only necessary at the time of initial commissioning by the specialist. Incorrect
measurement values can lead to severe unpredictable errors.
F 8.5.1 - Turn time
menu 8.5.1
The mixing valve is switched on i.e. is opening or closing for the time span set here, then the temperature is
measured to control the flow temperature.
Settings range: 0.5 sec to 3 sec.
Default: 2 s
Danger
Caution
Caution
Caution
Caution