Regulus TRS 4 Скачать руководство пользователя страница 22

│ 

22

REGULUS - TRS 4 Controller - www.regulus.eu

Special functions 

menu 8

F 8 - Special functions

Menu 

„8. Special functions”

 is used to set basic 

items and expanded functions.

The settings in this menu should only be 

made by a specialist.

The menu is closed by pressing 

„esc”

 or selecting 

„Exit special functions”

.

F 8.1 - Sensor calibration   

 

menu 8.1 / 8.1.1 - 8.1.6

Deviations in the temperature values displayed, for example due to cables which are to long or sensors which 

are not positioned optimally, can be compensated for manually here. The settings can be made for each 

individual sensor in steps of 0.5 °C.

Offset S1...S6 per settings range : -10 °C...+10 °C

Default: 0 °C

Settings are only necessary in special cases at the time of initial commissioning by the specialist. 

Incorrect measurement values can lead to unpredictable errors.

F 8.2 - Commissioning 

 

 

menu 8.2

The commissioning help guides you through the necessary basic settings in the correct order, and provides 

brief descriptions of each parameter in the display.

Pressing the 

„esc”

 key takes you back to the previous value so you can look at the selected setting again 

or adjust it if desired. Pressing the 

„esc”

 more than once takes you back step by step to the selection mode, 

thus cancelling the commissioning help (see also E 3).

May only be started by a specialist during commissioning! Observe the explanations for the 

individual parameters in these instructions, and check whether further settings are necessary for 

your application.

F 8.3 - Factory settings 

 

 

menu 8.3

All of the settings that have been made can be reset, thus returning the controller to its delivery state.

The entire parametrization, statistics, etc. of the controller will be lost irrevocably. The controller 

must then be commissioned once again.

F 8.4 - Expansions   

 

 

menu 8.4

This menu can only be selected and used if additional options or expansion modules have been built into the 

controller. The associated supplementary installation, mounting and operation instructions are then included 

with the specific expansion.

F 8.5 - Mixer   

 

 

 

menu 8.5

Settings are only necessary at the time of initial commissioning by the specialist. Incorrect 

measurement values can lead to severe unpredictable errors.

F 8.5.1 - Turn time   

 

 

menu 8.5.1

The mixing valve is switched on i.e. is opening or closing for the time span set here, then the temperature is 

measured to control the flow temperature.

Settings range: 0.5 sec to 3 sec.

Default: 2 s

Danger

Caution

Caution

Caution

Caution

Содержание TRS 4

Страница 1: ...TRS 4 Controller EN v 1 0 Installation wiring and operating instructions...

Страница 2: ...y devices to be provided by the customer e g a safety valve air vent valve etc The installation shall be done by a quali ed specialist who is trained accordingly For the user Make sure that the specia...

Страница 3: ...ts E Controller Use E 1 Display and input 10 E 2 Menu sequence and menu structure 11 E 3 Commissioning help setup wizard 12 E 4 Free commissioning 12 F Menu Description F 1 Measurements 13 F 2 Statist...

Страница 4: ...ontroller operation max 85 rel humidity at 25 C for transport storage no moisture condensation permitted Other speci cations and dimensions Housing design 2 part ABS plastic Installation method wall i...

Страница 5: ...al graphics extensive menus with interactive explanations menu lock can be activated to prevent unintentional setting changes usual preset parameters in factory setting A 3 Scope of supply TRS4 heatin...

Страница 6: ...lation tank 6 Two heating circuits mixed and direct one with boiler and accumulation tank B HYDRAULIC VARIANTS The following illustrations should be viewed only as schematic diagrams showing the respe...

Страница 7: ...n doing so 4 Hold the lower part of the housing up to the selected position and mark the 3 mounting holes Make sure that the wall surface is as even as possible so that the housing does not become dis...

Страница 8: ...rminals e g with a screwdriver Fig C 2 1 and wire the cables following the diagrams in section D 5 Lock the housing lid onto the top margin of its bottom counterpart push the cables inside and close t...

Страница 9: ...r 3 heating circuit 2 S4 sensor 4 accumulation tank S5 sensor 5 indoor sensor S6 sensor 6 remote controller free Z1 Optional expansion Z2 Optional expansion Use terminal block S for connecting the sen...

Страница 10: ...used to cancel an entry or to exit a menu If applicable there will be a request for con rmation as to whether the changes which have been made should be saved The function of each of the other three...

Страница 11: ...of the system with operating hours etc 3 Operating times for heating circuit setting the clock 4 Operating times for heating circuit manual mode 5 Set parameters for the heating circuit 6 Set paramet...

Страница 12: ...Finally menu 4 3 under operating mode Manual should be used to test the switch outputs with the consumers connected and to check the sensor values for plausibility Then switch on automatic mode E 4 Fr...

Страница 13: ...Overview or esc exits the Info mode If Error appears on the display instead of the measurement value then there may be a defective temperature sensor or its wiring If the cables are too long or the se...

Страница 14: ...e and the two left buttons scroll through the diagram F 2 2 28 days Menu 2 2 ow temperature during the last 28 days In the graphical overview the characteristics of the outdoor and ow temperature duri...

Страница 15: ...circuit day menu 3 2 This menu is used to select the daytime mode times for the heating circuit three time periods can be speci ed for each weekday and copied over to the following days Setting range...

Страница 16: ...value 14 day reference Off Default Automatic F 4 2 Heating circ 2 menu 4 2 Auto Automatic Normal mode using the set times Continuous Day The set values for day mode are used Continuous Night The set...

Страница 17: ...own To start the program press restart Pressing restart again will reset the 14 day reference program and start it at day 1 F 4 6 Heating circuit 2 reference HC2 menu 4 6 If operating mode HC2 Referen...

Страница 18: ...a normal straight curve Setting simple or a split curve Setting split that is divided into 2 parts by a split point The straight curve can be set easily using one parameter The characteristic curve fo...

Страница 19: ...e comfort temperature boost is added to the set day correction In this manner it is possible to carry out quick heating and or a higher temperature in the living spaces at a certain time each day Sett...

Страница 20: ...C Angle differs depends on steepness and split point The following settings can be used for parallel shift of the curve for certain periods such as daytime and nighttime F 6 2 Day correction menu 6 2...

Страница 21: ...low can lead to severe damage of the system F 7 3 Min ow temperature menu 7 3 The minimum ow temperature is the lower limit for the characteristic curve slope and as a result also for the reference o...

Страница 22: ...ed Pressing the esc more than once takes you back step by step to the selection mode thus cancelling the commissioning help see also E 3 May only be started by a specialist during commissioning Observ...

Страница 23: ...uence in the room temperature has on the reference ow temperature For every degree of deviation of the room temperature from the reference room temperature the percentage of the calculated reference...

Страница 24: ...closed by pressing esc or selecting Exit menu lock The menus listed below remain completely accessible despite the menu lock being activated and can be used to make adjustments if necessary F 1 Measur...

Страница 25: ...61 10 2 10 32 10 62 10 3 10 33 10 63 10 4 10 34 10 64 10 5 10 35 10 65 10 6 10 36 10 66 10 7 10 37 10 67 10 8 10 38 10 68 10 9 10 39 10 69 10 10 10 40 10 70 10 11 10 41 10 71 10 12 10 42 10 72 10 13 1...

Страница 26: ...If the error is no longer present the warning symbol changes to an info symbol and the red light no longer ashes To obtain more detailed information on the error press the key under the warning or inf...

Страница 27: ...heck it Exchange the defective fuse for a new one locate the external source of the error e g pump and exchange it Then rst recommission the controller and check the function of the switch outputs in...

Страница 28: ...record any analyses and data that are particularly important to you at regular intervals see 7 G 5 Disposal IMPORTANT INFORMATION ON DISPOSAL IN COMPLIANCE WITH THE EUROPEAN DIRECTIVE 2002 96 EC Europ...

Отзывы: