Secure the support structure either by screwing it into
the roof, or applying a burden.
In no event the permissible roof load shall be
exceeded. Consulting a statics expert in advan-
ce is necessary. A damaged roof must be re-
insulated by a specialist.
Fix the collectors to the rails in the same man-
ner as if installing on an inclined roof (see point
2.4).
Minimum distance between collector arrays see Fig. 22.
Flat roof mount
up to 8m high
roof
1 collector
290 kg
2 collectors
580 kg
3 collectors
870 kg
4 collectors
1160 kg
5 collectors
1450 kg
Fig. 21: Static safety (burden)
twice the height
winter
sun
solar
collector
heigh
t
25°
solar
collector
Fig. 22: Minimum distance between collector arrays