3
Manual C
ORRIGO
U-
SERIE
2002-09
Technical data
Supply voltage
24V AC +/- 15%
Power consumption
3VA
Ambient temperature
0...50 deg.C.
Storage temperature
-40...+50 deg.C.
Ambient humidity
Maximum 90% RH
Dimensions (w x h x d)
105 x 112 (incl.terminals) x 58 mm.
Protection class
IP20. Front mounting IP40
Mounting
On DIN-rail in a cabinet or standard housing.
On cabinet front using mounting kit FMC
Connections
Disconnectable terminal strips
Temp.sensor inputs
PT1000
Analogue inputs
0....10V DC
Digital inputs
Potential free closure.
Digital outputs
0.5 A, 24 V AC triac outputs
Analogue outputs
0...10 V DC, 5 mA. Short-circuit protected
Memory
Flash. All settings are stored in the event of power failure.
Real-time clock with 48 hour reserve running time.
Display
Background illumination. LCD, 2 rows of 16 characters
Running indication
7 in number steady shining yellow LEDs
Alarm indication
7 in number steady shining/flashing red LEDs
Alarms
Steady shining/flashing LED and relay output,
1A 24V DC/AC.
The alarm output can be blocked to prevent unprioritised
alarms activating the alarm relay during the night or during
holidays.
This product conforms with the requirements of
European EMC standards CENELEC EN50081-1 and
EN50082-1 and carries the CE mark.
Overview - models for heating control
C
ORRIGO
for heating control is available in two models which differ slightly in their
control function and in the number of inputs and outputs. Both models are available
without, U10 and U20 or with, U10-LON and U20-LON communication via LON
Works.
Control radiator group
Control tap hot-water
Control tap hot-water primary circuit
Temperature logging of min/max values
Analogue inputs (PT1000)
Digital inputs
Analogue outputs (0...10 V)
Digital outputs
Output indication with yellow LEDs
Alarm indication in script and red LEDs
Night set-back, two levels
Automatic pump stop with daily exercising
Flash memory (all settings are saved in the event of power failiure)
Realtime clock (48 hours running reserve)
Year base clock
Communicaton (Lon-versions)
Clock controlled outputs
1
2
1
1
1
1
•
•
6
8
4
5
3
6
4
7
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
0
2
U10 U20
Содержание Corrigo U10 Series
Страница 1: ...U10 20 User manual...
Страница 35: ...35 Manual CORRIGO U SERIE 2002 09...