Commissioning protocol U20
Configuration
Factory setting Commissioning setting
Config. code 1
1100.1110.0000
____._____._____
Config. code 2
0000.0111.11
____._____.___
A. AI1
1 Outdoor temp
_______________
B. AI2
1 HS1 Supply
_______________
C. AI3
0 --------
_______________
D. AI4
0 --------
_______________
E. AI5
1 HW Supply
_______________
F. AI6
1 THW Supply
_______________
G. AI7
1 HS2 Supply
_______________
H. AI8
0 ----
_______________
I. HS1 Night setback
0 No
_______________
J. HS1 Room compensation
0 No
_______________
K. HS1-CV1 Type
0 0...10 V DC
_______________
L. HS1-CV2
0 No
_______________
M. HS2 Night setback
0 No
_______________
N. HS2 Room compensation
0 No
_______________
O. HS2-CV1 Type
0 0...10 V DC
_______________
P. VS2-SV2
0 Nej
_______________
Q. Control THW
0 1 sequence
_______________
R. Control HW
1 Yes
_______________
S. Control HS1-P
1 Yes
_______________
T. Control HS2-P
1 Yes
_______________
U. Indication HWC
1 Yes
________________
V. Daylight saving
1 Yes
________________
Control HS1
Man. offset
0
_______________
Setpoint room
20.0°C
_______________
Nightreduction / Standby
-1.0 / -2.0
_______ / ______
Outdoor plot 1
-20.0°C / 65.0°C
_______ / ______
Outdoor plot 2
-10.0°C / 55.0°C
_______ / ______
Outdoor plot 3
-5.0°C / 50.0°C
_______ / ______
Outdoor plot 4
±0.0°C / 43.0°C
_______ / ______
Outdoor plot 5
+5.0°C / 35.0°C
_______ / ______
Outdoor plot 6
+10.0°C / 30.0°C
_______ / ______
Outdoor plot 7
+20.0°C / 20.0°C
_______ / ______
PBand / I-time
60K / 120 s
_____/_____/____
Runtime HS1-CV1
180 s
________________
Installation
System
Commiss.date
Commiss. by
Page 1