G. Function sensor AI7 (C

ORRIGO

 U20 only)

0.

---     Input not active

1.

HS2 Supply.
Must be configured as HS2 Supply if the sequence HS2is to be used for
heating control.
Function as for AI2, see point B.

H. Function sensor AI8 (C

ORRIGO

 U20 only)

0.

---     Input not active

1.

HS2 Room sensor.
AI8 must be configured as room sensor if HS2 is to have room compensation.
Function as for AI3, see point C.

2.

HS2 Return
The sensor reading is not used in any control-function but only for data
acquisition.

I. Night set-back HS1
0.

No

1.

Yes
C

ORRIGO

 has the possibility of sheduler controlled room temperature set-back

to two different levels, night set-back and stand-by set-back, the latter
normally used for shutting the system down for longer periods. A larger
temperature lowering is normally programmed.
The size of the set-back is set in the menu ”Control HS1”.
Setting of time and date is in the menu ”Scheduler”.
If no room sensor is configured the controller will calculate the lowering of the
water temperature using the current outdoor temperature and the set K-factor
for the room.

J. Room compensation HS1
0.

No

1.

Yes
Is only shown if AI3 has been configured as room sensor. Any room tempera-
ture deviation will displace the setpoint for the watertemperature so that the
deviation is eliminated.

K. HS1-CV1 type
0.

0...10V DC
Controls the actuator using an analogue 0...10 V DC signal on output AO1.
Control parameters are set in the menu ”Control HS1”.

1.

3-point
Controls the actuator using increase/decrease signals on the outputs DO2 and
DO3. Control parameters are set in the menu ”Control HS1”.

L. HS1-CV2 (C

ORRIGO

 U20 only)

0.

No

1.

Yes
Determins whether HS1 should have one or two sequences. Is automatically
set to No if CV1 has been set to 3-point since C

ORRIGO

 U only can sequence

0...10V outputs.

M. Night set-back HS2 (C

ORRIGO

 U20 only)

See corresponding function for HS1 under point I.

0.

No

1.

Yes

N. Room compensation HS2 (C

ORRIGO

 U20 only)

See corresponding function for HS1 under point J.

0.

No

1.

Yes
Is only shown if AI8 is configured as room sensor.

Содержание Corrigo U10 Series

Страница 1: ...U10 20 User manual...

Страница 2: ...nt of a cabinet The required functions are selected with the help of questions in normal script or by means of a code under the configuration menu depending on the type of application CORRIGO U series...

Страница 3: ...lashing LED and relay output 1A 24V DC AC The alarm output can be blocked to prevent unprioritised alarms activating the alarm relay during the night or during holidays This product conforms with the...

Страница 4: ...g control of one radiator system HS1 using one control valve HS1 CV1 Also control of tap hot water using either one or two separate control circuts HW and THW or a single control circuit with two sequ...

Страница 5: ...valve THW CV1 AO3 Control valve THW CV1 or Control valve THW CV2 AO4 Control valve HS2 CV1 AO5 Control valve HS1 CV2 AO6 Control valve HS2 CV2 Digital outputs DO1 Control output pump HS1 DO2 Three po...

Страница 6: ...ts The controller has common poles for signal neutral to transmitters AI 1 8 and a common pole for digital input signals Terminal 22 common for digital input signals is not the same as signal neutral...

Страница 7: ...S1 P DI8 Not connected DI7 Not connected DI6 Not connected DI5 Not connected DI4 External alarm DI3 Alarm expansion vessel DI2 Monitor pump HWC P DI1 Monitor pump HS1 P Common DI1 DI8 AI1 Temperature...

Страница 8: ...I7 Not connected DI6 Monitor pump HS2 P DI5 Not connected DI4 External alarm DI3 Alarm expansion vessel DI2 Monitor pump HWC P DI1 Monitor pump HS1 P Common DI1 DI8 AI1 Temperature outdoor Signal neut...

Страница 9: ...ny control function but only for data acquisition AI4 HS1 return temperature or HP1 Heating primary The sensor reading is not used in any control function but only for data acquisition AI5 HW Outgoing...

Страница 10: ...tuator See under Configuration AO5 Control valve HS1 CV2 C20 only AO5 is only active if HS1 has been configured for two actuators in sequence See Configuration AO6 Control valve HS2 CV2 C20 only AO5 i...

Страница 11: ...r 24 V AC See figure in the margin DO1 Control of circulation pump HS1 DO2 3 point output HS1 CV1 increase DO3 3 point output HS1 CV1 decrease DO2 and DO3 are only active if HS1 CV1 has been configure...

Страница 12: ...d active and non acknowledged alarms will be displayed in the menu window The LED for alarms placed above the alarm button is lit when there are alarms in the queue If there are multiple alarms use an...

Страница 13: ...isplays shown above will alternate at three second intervals Main menu Press the OK button The information menu will stop and the main menu will open immediately The main menu consists of a number of...

Страница 14: ...ed by a steady AL and a steady red light on the alarm signals Arrows on the right hand side show when there are more alarms in the queue Login CORRIGO has four different login levels to prevent the us...

Страница 15: ...er level 2 2222 User level 3 3333 Changing codes The codes for the three user levels can easily be changed in user level 3 Enter the login menu The arrow means that there are menus below press the arr...

Страница 16: ...s are to be configured in the same way The first thing to be shown when the configuration menu is opened is the setting of the control function Using the arrow up button the two configuration codes wi...

Страница 17: ...curve to compensate the supply water temperature for any offset in room temperature the K factor determining the room temperature influence on the setpoint must be set in the menu Settings 2 HWC Retur...

Страница 18: ...om sensor is configured the controller will calculate the lowering of the water temperature using the current outdoor temperature and the set K factor for the room J Room compensation HS1 0 No 1 Yes I...

Страница 19: ...he pump control are set in the menu Settings Stopped pump is exercised daily T Pump control HS2 CORRIGO U20 only 0 No 1 Yes U Pump indication HWC 0 No 1 Yes Absence of signal from HWC P on DI2 will tr...

Страница 20: ...put Only shown if HS1 is configured with 2 sequences 3 Manual offset Actual setpoint The control curve can be offset 30K Setpoint including offset 4 Setpoint Room Actual Room Room compensation Display...

Страница 21: ...e the applicable sensor input press Adjust the display value using or When completed confirm using OK Bear in mind that CORRIGO is always supplied with factory calibrated inputs This applies also to s...

Страница 22: ...is configured as 3 point See Configuration point K DO3 3 point output HS1 decrease Only shown if HS1 CV1 type is configured as 3 point See Configuration point K DO4 Control pump HS2 CORRIGO U20 only...

Страница 23: ...U20 each have 1 period for standby Standby lowering of the room temperature is utilised at longer periods of vacancy St lls in p motsvarande s tt som f r natts nkningsperiod 1och 2 ovan Vid verlappand...

Страница 24: ...THW Should the actual temperature differ from the setpoint by more than the set value an alarm will be activated after a set time Only active if THW has been configured 5 Alarm HWC P 0 No 1 Yes 6 Ala...

Страница 25: ...t values encountered since the last activation of the function are stored and will be displayed for each input under the menu Analogue in LEDs The LEDs are connected to the functions of certain in and...

Страница 26: ...control HS1 active T Pump control HS2 active U Pump monitor HWC P active V Daylight saving time active Factory settings U10 Configuration Factory setting Config code 1 1100 1100 0000 Config code 2 000...

Страница 27: ...for U10 0 Code must be 0 Q Control THW 0 1 sequence _______________ R Control HW 1 Yes _______________ S Control HS1 P 1 Yes _______________ T Not available for U10 0 Code must be 0 U Indication HWC...

Страница 28: ...settings 1 Control alarm HS1 5K 5 min ______ _______ 2 Control alarm HW 5K 5 min ______ _______ 3 Control alarm THW 5K 5 min _______________ 4 Sum alarm output active Mo Su 00 00 24 00 _______________...

Страница 29: ...____________ O HS2 CV1 Type 0 0 10 V DC _______________ P VS2 SV2 0 Nej _______________ Q Control THW 0 1 sequence _______________ R Control HW 1 Yes _______________ S Control HS1 P 1 Yes ____________...

Страница 30: ...0 00 00 _______________ Standby HS1 00 00 00 00 _______________ NRed 1 HS2 00 00 00 00 _______________ NRed 2 HS2 00 00 00 00 _______________ Standby HS2 00 00 00 00 _______________ TO1 Per 1 00 00 00...

Страница 31: ...D Function sensor AI4 0 Input not active 0 1 HS1 Return 1 2 HP Outgoing 2 E Function sensor AI5 0 Input not active 0 1 HW Outgoing 1 2 HP Return 2 F Function sensor AI6 0 Input not active 0 1 THW Out...

Страница 32: ...U10 0 Not active Do not change 0 O Not available to Corrigo U10 0 Not active Do not change 0 P Not available to Corrigo U10 0 Not active Do not change 0 Q Control THW 0 1 sequence 0 1 2 sequences 1 R...

Страница 33: ...turn 2 D Function sensor AI4 0 Input not active 0 1 HS1 Return 1 2 HP Outgoing 2 E Function sensor AI5 0 Input not active 0 1 HW Outgoing 1 2 HP Return 2 F Function sensor AI6 0 Input not active 0 1 T...

Страница 34: ...Yes 1 N Room compensation HS2 0 No 0 1 Yes 1 O HS2 CV1 type 0 0 10 V DC 0 1 3 point 1 P HS2 CV2 0 No 0 1 Yes 1 Q Control THW 0 1 sequence 0 1 2 sequences 1 R Control HW 0 No 0 1 Yes 1 S Pump control...

Страница 35: ...35 Manual CORRIGO U SERIE 2002 09...

Страница 36: ...ate while at the same time utilizing energy in the most cost effective way possible The product range consists of Regin s own products as well as products from leading manufacturers V r aff rsid r att...

Отзывы: