Regency P33 Sunrise™ Gas Fireplace
29
INSTALLATION
GAS PIPE PRESSURE
TESTING
The appliance must be isolated from the gas
supply piping system by closing its individual
manual shut-off valve during any pressure
testing of the gas supply piping system at test
pressures equal to or less than 1/2 psig. (3.45
kPa). Disconnect piping from valve at pressures
over 1/2 psig.
The manifold pressure is controlled by a regulator
built into the gas control, and should be checked
at the pressure test point.
Note: To properly check gas pressure, both
inlet and manifold pressures should
be checked using the valve pressure
ports on the valve.
1)
Make sure the valve is in the "OFF" position.
2)
Loosen the "IN" and/or "OUT" pressure tap(s),
turning counterclockwise with a 1/8" wide
fl
at
screwdriver.
3)
Attach manometer to "IN" and/or "OUT"
pressure tap(s) using a 5/16" ID hose.
4)
Light the pilot and turn the valve to "ON"
position.
5)
The pressure check should be carried out
with the unit burning and the setting should
be within the limits speci
fi
ed on the safety
label.
6)
When
fi
nished reading manometer, turn
off the gas valve, disconnect the hose and
tighten the screw (clockwise) with a 1/8"
fl
at
screwdriver.
Note: Screw should be snug,
but do not over tighten.
Incorrect fl ame pattern will have small,
probably yellow fl ames, not coming into
proper contact with the rear burner or
thermopile or thermocouple.
HIGH ELEVATION
This unit is approved in Canada for altitude to
4500 ft. (CAN/CGA-2.17-M91). For Natural Gas
installations above 4500 ft. follow current CAN/
CGA-B149.1.
PILOT ADJUSTMENT
Periodically check the pilot fl ames. Correct
fl ame pattern has three strong blue fl ames:
1 fl owing around the thermopile, 1 around
the thermocouple and 1 fl owing across the
burner (it does not have to be touching the
burner).
Note: If
you have an incorrect fl ame
pattern, contact your FPI dealer for further
instructions.
P33S-NG4 System Data
Conversion Kit# 434-970 (NG to LP)
For 0 to 4500 feet altitude
Burner Inlet Orifi ce Sizes:
#47
Max. Input Rating
17,000 Btu/h
Min. Input Rating
12,000 Btu/h
Supply Pressure
min.5.0"
w.c.
Manifold Pressure
(High)
3.5"+/- 0.3" w.c.
P33S-LP4 System Data
For 0 to 4500 feet altitude
Burner Inlet Orifi ce Sizes:
#56
Max. Input Rating
15,500 Btu/h
Min. Input Rating
12,000 Btu/h
Supply Pressure
min.11.0"
w.c.
Manifold Pressure
(High)
10"+/-
0.4"w.c.
S.I.T. VALVE DESCRIPTION
1)
Gas on/off knob
2)
Manual high/low adjustment
3)
Pilot
Adjustment
4)
Thermocouple Connection -
option
5)
Outlet Pressure Tap
6)
Inlet Pressure Tap
7)
Pilot Outlet
8)
Main Gas Outlet
9)
Alternative TC Connection Point