Regency P33 Sunrise™ Gas Fireplace
INSTALLATION
Caution Requirements
The top, back and sides of the
fi
replace are de
fi
ned by
standoffs. The metal ends of the standoff may
NOT
be
recessed into combustible construction.
WARNING
Fire hazard is an extreme risk
if these clearances (air space) to combustible materials are not
adhered to. It is of greatest importance that this fi replace and vent
system be installed only in accordance with these instructions.
CLEARANCES
The clearances listed below are Minimum distances unless otherwise stated:
A major cause of chimney related fi res is failure to maintain required clearances (air space) to combustible materials. It is of the greatest importance
that this fi replace and vent system be installed only in accordance with these instructions.
C
F
Clearance:
Dimension
Measured From:
A: *Front Floor Clearance (min.)
1" (25mm)
Underside of Unit
B: *Sidewall (on one side)
7-1/2" (241mm)
Side of Unit
C: *Ceiling
(room and/or alcove)
30" (889mm)
Top of Unit
D: Alcove Width
48" (1219mm)
Sidewall to Sidewall (Minimum)
E: Alcove Depth
36" (914mm)
Front to Back Wall (Maximum)
F: Max. mantel depth
12" (305mm)
B
C
Close to Ceiling
Flue Clearances
Horizontal - Top
2-1/2"
Horiztonal - Side
1-1/2"
Horiztonal - Bottom
1-1/2"
Vertical (Flex Vent)
1-1/2"
Vertical (Rigid)
1-1/4"
*Note: All measurements are from the top/side of the unit, not optional front.