Regency PG33NG4-R Gas Inbuilt
installation
• Flue must be supported at offsets.
• Firestops are required at each floor level and whenever passing through a wall.
• Maintain clearances to combustibles.
Note: Must use optional flue adapter when using Simpson Dura-Vent pipe (Part # 510-994).
FLUEING ARRANGEMENTS - VERTICAL TERMINATIONS
SIMPSON DURA-FLUE DIRECT FLUE GS SYSTEM
(NG, LPG & ULPG)
The shaded area in the diagram shows all allowable combinations of straight vertical and offset to vertical terminations , using one 90
o
elbow, with
Simpson Dura-Flue Direct Flue GS
flue systems for NG, LPG and ULPG.
Minimum
8'6
(2.6m)
Maximum 40
(12.2m)
40
8
10
12
14
16
18
20
22
24
26
28
30
6
0
2
4
2
0
6
4
Vertical Height (ft/m)
Horizontal (ft/m)
(5.5m)
(1.8m)
(3.7m)
(7.3m)
(9.1m)
(0.6m)
(1.2m)
(1.8m)
(10.9m)
(10.4m)
(9.8m)
(8.5m)
(7.9m)
(6.7m)
(6.1m)
(4.9m)
(4.3m)
(3.0m)
(2.4m)
(0.6m)
(1.2m)
(12.2m)
3
3.6
Vertical Height (M)
Minimum
8'6
(2.6m)
Maximum 27
(8.2m)
Horizontal (M)
Min. 12 (305mm)
3
3.6
4.2
4.8
5.4
6
6.6
7.2
8
8.6
9.2
9.8
10.4
11
11.6
Max. 10 (3m)
(centerline to centerline)
0
0.6
1.2
1.8
2.4
0.6
0
1.8
1.2
2.4