10
Mansfield L850B ST Woodfire
installation
COMBUSTIBLES
Combustible Enclosure of
Chimney when passing
through 2nd Floor
Combustible Ceiling
2nd Floor
Combustible Ceiling
Minimum
50mm
clearance to
combustibles
as it passes
through floors,
living space
and ceilings.
Minimum
50mm
clearance to
combustibles
as it passes
through floors,
living space
and ceilings.
1. Ventilation grills = 2 grills, 1 below & 1 above fuel loading doors. One grill each side or opposite sides. Only two grills required.
Require minimum 8000mm
2
of open area for each grill.
2. Require unit to be raised minimum of 300mm from finished floor.
3. Non-combustible board and steel framing is required for the entire enclosure however the ceiling may be of combustible material -
see page 9 for minimum ceiling height.
4. Clearances to combustibles for triple skin flue as it passes through ceiling, living spaces = 50mm.
5. Non-combustible with walls of enclosure to be 9mm thick minimum.