Greenfire® GF1500L-2 Gas Fireplace
| 35
installation
Direct Flue Zero Clearance Top Exit Vertical Flue Kit Installation Instructions
This flue kit has been manufactured for use with GF1500L and to be installed in accordance
with AS/NZS 5601. To ensure safety and correct unit operation this flue kit must be installed
as outlined in these instructions. Heater and flue clearances from combustible materials must
be in accordance with these instructions and AS/NZS 5601.
1. Locate the heater in its proposed position and mark the point for penetration directly above
the centre of the heater flue outlet. Check the heater location allows the outer flue to clear
all structural timber and combustible surfaces by 40mm minimum.
2. If the enclosure consists of a ceiling – cut a 303mm square hole (minimum) for the flue to
penetrate, cut hole through roofing material and prepare flashing for termination.
3. Starting at the heater, install first length of inner pipe, using Mill-Pac sealant and self-tapping
screws (or rivets). Note – first length of inner pipe has a Swage only.
4. Continue assembling flue pipes inner and outer, ensuring each inner join is sealed using
Mill-Pac sealant and self-tapping screws (or rivets). Outer flue pipe installs crimped end up
and must be sealed and fixed together also.
5. If required, fix outer flue in the ceiling space using non-combustible bracing to stop move-
ment. On penetration of roof, fit an appropriate flashing or weather seal to suit the roofing
material, ensure all joints outside are sealed with appropriate sealer.
6. Fit approved gas cowl ensuring inner and outer flue pipes are sealed.
7. Start heater and run for at least 15 minutes to check flue seal. If operational issues are noted,
check flue again to ensure proper seal of inner pipe.
SUPPLIED
Mill-Pac SEALANT MUST BE USED OR WARRANTY WILL BE VOID
– IF RE-
QUIRED, MORE SEALANT CAN BE PURCHASED USING PART NUMBER 948-128
45º bends (if required) part number 946-688 – Note, if bends are used at the start of flue run,
a deeper crimp may be required at the unit for inner pipe fitment. Can be crimped on site and
sealed with Mill-Pac sealant and self- tapping screws (or rivets).
Gas Cowl
58DVA-VCH
Outer Flue
203mm dia x 900mm x 4
Inner flue
127mm dia x 900mm x 4
Outer Flue
203mm dia x 900mm x 4
Inner flue
127mm dia x 900mm x 4
Flomet Cap
If required 45° Inner Flue &
Outer Flue may be installed.
Install with pop rivets or self
tapping screws and seal with
Milpac
If required 45° Inner Flue &
Outer Flue may be installed.
Install with pop rivets or self
tapping screws and seal with
Milpac
1st Length Inner Flue
has Swage Only
1st Length Inner Flue
has Swage Only
Last Length of Outer
Flue has deep crimp
and is marked
Last Length of Outer
Flue has deep crimp
and is marked
Mil-Pac SEALANT
INNER FLUE
NO
TES
• Use a minimum of 3 screws equidistant to
secure every inner flue pipe joint as well as
Mil-Pac sealant.
• It is the installers responsibility to ensure the
installation complies with AS/NZS 5601 and
all local and building codes.