Regency CS1200 Freestanding Wood Stove
13
INSTALLATION
MOBILE HOME INSTALLATION
WARNING:
Minimum height requirements
must be met. Safe removal of
the chimney system must be
adhered to when transporting the
mobile home.
WARNING: Operate only with door fully
closed - open feed door to feed fi re only.
Once you have properly marked the position of your unit and the fl oor protec-
tion as outlined in the Residential Installation items #1 through #8, a supply of
fresh air has to be supplied to your unit. Cut a minimum 4 inch diameter hole
through your outside wall. Use 4" duct pipe with a mesh grill to pipe fresh air
into the back shield area. Place your unit in position and secure it to the fl oor
using two lag bolts 3/8" x 3-1/2" through the two holes inside the pedestal
base. It is important to maintain the structural integrity of the Mobile Home
fl oor, walls and roof when installing your unit.
For Mobile Home units installed in the U.S; the unit must be grounded using
a #8 ground wire with approved termination and star washer.
Secured to fl oor with 2 lag bolts.
4" outside air kit
Содержание Alterra CS1200
Страница 28: ...28 Regency CS1200 Freestanding Wood Stove NOTES ...
Страница 29: ...Regency CS1200 Freestanding Wood Stove 29 NOTES ...
Страница 30: ...30 Regency CS1200 Freestanding Wood Stove NOTES ...