Regency DVi34L Gas Inbuilt Fireplace
Air
Intake
Minimum 2.4 m Maximum 10.7 m
Exhaust
Flue
April 13/99
revised as per Joe G.
June 10/99 revised as per Jan. S.
Oct.22/99: removed "Canadian Installations from Ventng2.eps
Canadian Installations
Check local
codes whether
a continuous
length is
required or if
certified joiner
kits may
be used.
#948-640
Termination
Cap (46DVA-VCH)
Adaptor (46DVA-GK)
FLUEING
This appliance is designed to be attached to two
76 mm co-linear aluminium flex running the full
length of the chimney. The flue length must be
a minimum length of 2.44 m and a maximum of
10.7 m. See chart below for minimum distances
from roof. Periodically check that the vent is
unrestricted.
Masonry chimneys may take various contours
which the flexible liner will accommodate.
However,
keep the flexible liner as straight as
possible
, avoid unnecessary bending.
The Air Intake pipe must be attached to the inlet
air collar of the termination cap.
GAS CONNECTION
GAS CONNECTION WARNING:
Only persons licensed to work
with gas piping may make the
necessary gas connections
to this appliance.
1)
If the appliance is to be installed into an
existing chimney system, thoroughly clean
the masonry fireplace.
2)
The appliance is provided with an opening
on the right hand side of the control
compartment. The 9.5 mm flexible gas hose
provided needs to be brought in from behind
this opening. Ensure all gas connections
are tight.
3)
Locate the center point where the vent
will pass through the chimney above the
appliance. Move the appliance into the
exact location where it is to be installed.
Ensure that the Insert is level.
INSTALLATION
305 mm Mantel
89 mm
Mantel
535 mm
610 mm
to floor
Top
Faceplate
51
0
305
152 102
203
254
51
0
305
152
406
102
356
203
457
254
Side View
330 mm
508
559
Mantel Clearances
Note: A non-combustible mantel may be
installed at a lower height if the fram-
ing is made of metal studs covered
with a non-combustible board.
CLEARANCES TO
COMBUSTIBLES
Minimum Clearances to Combustibles
From Unit
Sides
A
255 mm
Ceiling
B
1205 mm
Mantel
C
330 mm
Max. Mantle Depth
E
305 mm
(see Dia. 2)
Min. Alcove Width
F
1220 mm
Max. Alcove Depth G
915 mm
*No hearth required.
CL
Gas
Inlet
WARNING
DO NOT USE AN UNLINED
MASONRY CHIMNEY AS THE
FLUE FOR THIS APPLIANCE.
THE APPLIANCE MUST NOT
CONNECT TO A CHIMNEY
FLUE SERVING A SEPARATE
SOLID FUEL BURNING APPLI-
ANCE AND MUST NOT BE
TERMINATED TO THE
OUTDOORS.
Note: When installing the flueing, identify
the flues. Mark one exhaust and one
intake as indicated on the top of the
unit.
Air
Intake
Minimum 2.4
m
Maximum 10.7
m
Exhaust
Flue
Flashing
April 13/99
revised as per Joe G.
June 10/99 revised as per Jan. S.
Oct.22/99: removed "Canadian Installations from Ventng2.eps
Canadian Installations
Co-linear DV
Vertical Termination
Cap #946-549
Check local
codes whether
a continuous
length is re-
quired or if
certified joiner
kits may
be used.
#948-640
Part #
Description
948-640
76 mm Flex - 12.2 m
946-549
Co-linear DV Vertical
Termination Cap
Alternate Termination Cap/Adaptor
Part #
Description
46DVA-GK Simpson Duravent Adaptor
46DVA-VCH Simpson Vertical High Wind
Cap