12
Regency DVi34L Gas Inbuilt Fireplace
AERATION SETTINGS
The burner aeration is factory set but may need adjusting due to either the local gas supply, air supply or altitude. This adjustment is performed by
the installer. (Close the aeration for a more yellow flame, or open it to make the flame bluer).
NG:
13mm open
Propane:
13mm open
ULPG:
13mm open
Note: Any damage due to carboning resulting from improperly setting the aeration and restrictor setting controls is NOT covered
under warranty.
INSTALLATION
DVi34LNG: For 0 to 610 meters altitude
DVi34LLPG: For 0 to 610 meters altitude
DVi34LULPG: For 0 to 610 meters altitude
Burner Inlet Orifice Sizes:
NG
Propane ULPG
Burner #37
#52 #53
Max. Input
NG
31.7 MJ/h
Propane
30.6 MJ/h
ULPG
26.4 MJ/h
Min. Input
NG
21.1 MJ/h
Propane
25.1 MJ/h
ULPG
20.9 MJ/h
Supply Pressure
NG
1.13 kPa
Propane
2.75 kPa
ULPG
2.75 kPa
Manifold Pressure HIGH LOW
NG
0.87 kPa 0.4 kPa
Propane
2.51 kPa 1.6 kPa
ULPG
2.51 kPa 1.6 kPa
Electrical: 240 V. 50Hz.
Circulation: High/Off/LO speed fan,
150/89 CFM.
Log Set: Ceramic fiber, 7 per set.
Aeration Setting
NG
13 mm open
Propane 13 mm open
ULPG
13 mm open
System Data
DVi34L