Manual
– TopCon TC.LAE
Installation and commissioning
30 / 56
2016-06-08
6.2.3.
Liquid cooling
– device connection
5
7
3 4
1
2
6
Fig. 17
Connection of a coolant hose to the coolant standard interface
of the device.
Preparation:
Open-end wrench: 24 mm
Coolant hose:
inside Ø:
13 mm
outside Ø:
16 mm
Procedure:
Remove the sealed rubber stopper
-1-
from the connection fitting
and keep it for a future use.
Loosen the union nut
-2-
from the connection fitting, by turning to
the left via open-end wrench.
The union nut
-3-
pull over the coolant hose
-4-
.
Push
-5-
the coolant hose with the nut over the nipple
-6-
of the
coolant interface. Try to push the hose to the nipple base.
Tighten strongly
-7-
the nut by turning to the right.
Repeat the procedure for the other coolant interface.
Fill-up the coolant in the device.
For further information about the fill-up procedure,
refer to chapter 6.2.6, page 33.
Check the connection for leaks at 1,5 bars for 10 min, as per the
standard EN50178.