4.5 Connecting a Cooling System
4.5.1 Introduction
In order to dissipate the generated heat, the TC.ACS is equipped with an internal heat-exchanger. This heat
exchanger necessarily needs to be connected to an external cooling system.
4.5.2 Requirements to a Cooling System
The requirements to a cooling system are given by the following:
• Specifications of the internal Heat Exchangerer (
)
• Requirements to the Cooling Liquid (
)
• Pressure Differences and Flow Rates (
4.5.2.1 Specifications of the internal Heat Exchanger
er
Option: Liquid to Air Heat Exchanger TC.LAE
is designed to be used as an external cooling
system with the TC.ACS.
Any other external cooling system has to to meet specific requirements (see
).
CAUTION
Possible damage to the device!
Due to condensation inside the device or on the supply tube.
Avoidance:
Keep the inlet temperature of the cooling liquid at a temperature level above the dew point.
For the relevant dew point refer to a dew point table.
Damage to the device due to condensed water is excluded from the warranty.
General specifications
Connections
G1/2” (see
)
Heat sink material
EN AW-5083
Thermal rating
5 kW
Approx. thermal resistance
< 0.01 K/W
Performance data with a cooling liquid with a specific heat capacity of 4.19 kJ/kgK
Recommended flow rate
5 l/min
Min. flow rate
2.5 l/min
Max. inlet temperature
25 °C @ 2.5 l/min, 50 °C @ 8 l/min