SO 2-Ex
25
Controller setting procedure:
The
initialization routine
starts at the switched-on controller, zero system deviation and short pressing of the
SW1
button for ca 2 sec (i.e. until the diode
D3
got on). Loosing the button some of the default menus starts
(usually control signal) what is shown with 1 blink on the
D3
diode as well as one of the default parameters
(usually control signal of 4-20mA) what is shown with 1 blink on the
D4
diode. Then the required parameters of
the controller can be changed according to Table 2:
press shortly the
SW1
button to list the menu shown with the blinking number on the
D3
diode.
press shortly the
SW2
button to set parameters shown with the blinking number on the
D4
diode.
After changing of the parameters according to user's wishes, put the controller to
autocalibration
with
pressing the
SW1
button for ca 2 sec (i.e. until the diode D3 got on). During this process the controller performs
the feedback transmitter and turning sense checking, sets actuator to the positions "open" and "closed",
measures inertia mass in the directions "opening" and "closing", and loads the adjusted parameters into the
EEPROM memory. In case that during the initialization process an error occurs (e.g. in connection or
adjustment) the initialization process will be interrupted and the controller with the
D4
diode reports about the
type of the error. Else after finishing the initialization process the controller is put into the
regulation mode
.
Error messages of the controller with D4 diode at initialization
4 blinks..........improper connection of the torque switches
5 blinks..........improper connection of the feedback transmitter
8 blinks..........bad sense of actuator's turning direction or adverse connection of the feedback
transmitter
4.6.2 Watching operation and error states
Watching operation and error states is possible with the EA open.
a) Operation status with the D3 LED diode signalling:
it is continuously lighting - the controller regulates
it is continuously not lighting - system deviation in the insensitiveness range - the EA has stopped
b) Error state with the D4 and D3 LED diodes signalling - D4 continuously lighting,
1 blink
(repeated):
indication of the "TEST" mode - the EA is put to the position
according to the signal in the "TEST" menu (at connecting the
66 and 86/87 terminals)
2 blinks
(repeating after short pause)
missing of control signal - the EA is put to the position according
to the signal in the "TEST" menu
4 blinks
(repeating after short pause)
torque switches activity indication (the EA switched-off with the
torque switches in a mid-position)
5 blinks
(repeating after short pause)
failure of the feedback transmitter - the EA is put to the position
according to the signal in the "TEST" menu
7 blinks
(repeating after short pause)
control signal (current at range 4-20mA less than 4mA (3.5mA).
Содержание SO 2-Ex
Страница 31: ...SO 2 Ex 29 7 Enclosures 7 1 Wiring diagrams SO 2 Ex...
Страница 32: ...30 SO 2 Ex 7 2 Wiring diagrams SO 2 Ex with controller...
Страница 33: ...SO 2 Ex 31...
Страница 35: ...SO 2 Ex 33 7 3 Dimensional drawings...
Страница 36: ...34 SO 2 Ex...
Страница 37: ...SO 2 Ex 35...
Страница 38: ...36 SO 2 Ex...
Страница 39: ...SO 2 Ex 37...
Страница 40: ...38 SO 2 Ex...
Страница 41: ...SO 2 Ex 39...