56
REFUsol 48K-UL
REFU Elektronik GmbH
Error
Code
Text
Description
Action
A011F Parameter error
LT 5
Faulty reading or writing process in
power section memory
1.) Switch off device with DC
disconnector.
2.) Wait until the display has turned
off completely.
3.) Switch on device with DC
disconnector.
If this does not rectify the error,
contact Service.
A0172
P24V LT aux.
supply
P24V supply voltage at the power
stack is too low.
Please contact Service
A0173
P5V LT aux.
supply
P5V supply voltage at the power
stack is too low.
A0174
P15V LT aux.
supply
P15V supply voltage at the power
stack is too low.
A0178
Temp. Sensor
KR LT
checking open loop or short loop for
temperature sensor cooler right
A0179
Temp. Sensor IL
LT
checking open loop or short loop for
temperature sensor cooling interior
left
A017A Temp. Sensor IR
LT
checking open loop or short loop for
temperature sensor cooling interior
right
A017B Temp. Sensor
KL LT
checking open loop or short loop for
temperature sensor cooler left
A017C N15V LT aux.
Supply
N15V supply voltage at the power
stack is too low.
A017D Phase defect
an error has been detected in the
power modules