Start by setting the current hour (in this case: 18) with the
arrow buttons and confirm with “ok”. Continue with the minutes
(in this case: 46) and the seconds (in this case: 29).
Start by setting the current day (in this case: 29) with the arrow
buttons and confirm with “ok”. Continue with the month (in this
case: 11) and the year (in this case: 01).
A check is performed as to whether the signal issued by
the level gauge (oil cell) at the foot of the VG basic vessel
corresponds to the factory-set vessel in the controller.
Proper assembly of the ’variomat’ system according to these
instructions is absolutely necessary for correct balancing
(
→
see also p. 9).
The vessel type can be balanced here (see name plate on
the VG basic vessel).
If auto-zeroing has been successfully performed, this
is indicated as scrolling text. The message
“Auto-zero
successfully executed!”
is displayed. In this case, the
following 2 paragraphs are skipped.
If the controller detects a value that is not plausible, the
message
“Empty con repeat balancing!”
is
displayed.
If auto-zeroing cannot be performed despite verification of
the above points, it can be cancelled. To do so, confirm the
message “Empty con repeat balancing!” using “ok”.
The question
“Abort auto-zero? Yes/No”
is displayed. Select
your answer using the arrow keys. If you choose
“Yes”
, the
correct vessel must be selected in the service menu after the
start routine is completed (please notify Reflex Service).
At the end of the start routine you will be asked whether you
wish to exit the start routine. If you choose
“Yes”
and confirm
with “ok”, the system automatically switches to stop mode. It
should be left in stop mode in order to undertake additional
start-up measures.
If you choose
“No”
, the start routine is repeated.
You are now in stop mode.
Important: Do not switch to
automatic mode yet.
Time:
18:46:29
Date:
29.11.01
2% 2.1
bar
Auto-zero
0% 2.1
bar
Auto-zero successfully
0% 2.1
bar
Empty
Abort
auto-zero? No
Exit
routine? Yes
0% 2.1
bar
Stop
ok
ok
ok
ok
ok
ok
ok
Important: The VG
basic vessel must be
empty.
reflex ’variomat’
Initial start-up
17
00800 l 740 mm
Weight = 0149 kg