Description of the device
Vacuum spray degassing — 28.08.2019 - Rev. B
English — 7
CAUTION
Risk of injury due to heavy device weight
The device weight may cause physical injury or accidents.
•
If necessary, work with a second person during assembly or disassembly.
ATTENTION
Device damage during transport
If the device is not transported correctly, it may be damaged.
•
Use suitable covers to protect the connections against damage.
4
Description of the device
The device is a degassing and make-up station. Its main areas of application are heating and cooling circuits and systems in which
interruptions of operations due to dissolved or free gases. The device provides the following safety features:
•
No direct intake of air thanks to a regulation of the pressure maintenance with automatic make-up.
•
No circulation issues caused by free bubbles in the circuit water.
•
Reduced corrosion damage due to oxygen removal from fill and make-up water.
4.1
Overview
1
Connection, WC make-up line
9
Motorized ball valve system-side
2
Controller
10
Pump
3
Gas-rich water inlet / System side DC
11
Spray tube
4
air vent
12
Pressure sensor
5
Check valve at the air vent
13
Motorized ball valve make-up side
6
Nameplate
WC
Make-up connection
7
Dirt trap
DC
Degassing connection
•
Degassed water outlet
•
Gas-rich water inlet
8
Degassed water outlet / System side DC
Содержание Servitec S
Страница 1: ...Vacuum spray degassing 28 08 2019 Rev B Servitec S GB Operating manual Original operating manual...
Страница 2: ......
Страница 32: ......
Страница 33: ......