Installation 

 

 

 

Vacuum spray degassing — 28.08.2019 - Rev. B 

 

English — 15 

 

 

 

6.3.3

 

Degassing line to the system 

 

Installation detail of the "DC" degassing line 
Install the "DC" degassing lines as follows: 
• 

Prevent an overload of the "ST" dirt trap in the device 
caused by coarse dirt. 

• 

Install the gas-rich degassing pipe “DC” upstream of the 
gas-poor degassing pipe (when viewed in the system 
flow direction). 

• 

Preferably install on the return side of the facility 
system. 
– 

The water temperature must be in the range of 0 
°C – 70 °C to ensure sufficient degassing 
capacity. 

 

 
Device installation in a heating system – Pressure maintenance with bladder "MAG" expansion vessel 

 

 

 

Heating system 

 

Device 

Bladder expansion vessel 

 

"DC" degassing line (gas-rich water) 

For optional equipment and accessories, see 
chapter 4.5 "Optional equipment and accessories" 
on page 10  

 

"DC" degassing line (degassed water) 

 
Proceed as follows: 
• 

Connect the "DC" degassing lines in the "V" main volume flow of the facility system. 

• 

The device requires two "DC" degassing lines to the facility system. 
–  

One degassing line for the gas-rich water from the facility system 

–  

One degassing line for the degassed water back to the facility system. 

• 

Fit the degassing lines near the "EC" expansion line. 
–  

This ensures stable pressure conditions. 

• 

Install the device near the "MAG" expansion vessel. 
–  

This ensures pressure monitoring of the expansion vessel. 

–  

Set the "Magcontrol" operating mode at the device controller. 

 

 

Note! 
• 

Ensure the integration with the "V“ main flow volume. in particular in switching variants with hydraulic 
switching points and return admixtures. 
–  

For switching and make-up variants, see chapter 6.4 "Switching and make-up variants" on page 16 . 

 

 

 

Содержание Servitec S

Страница 1: ...Vacuum spray degassing 28 08 2019 Rev B Servitec S GB Operating manual Original operating manual...

Страница 2: ......

Страница 3: ...stem 15 6 4 Switching and make up variants 16 6 4 1 Pressure dependent Magcontrol make up mode 17 6 4 2 Level dependent Levelcontrol make up mode 17 6 5 Electrical connection 18 6 5 1 Terminal diagram...

Страница 4: ...e for access at any time 2 Liability and warranty The device has been built according to the state of the art and recognised safety rules Nevertheless its use can pose a risk to life and limb of perso...

Страница 5: ...nnel or specially trained personnel only The electric connections and the wiring of the device must be executed by a trained electrician in accordance with all applicable national and local regulation...

Страница 6: ...em or the circuitry 3 6 Residual risks The device has been manufactured using state of the art technology Despite this residual risks cannot be excluded WARNING Risk of fire due to open ignition sourc...

Страница 7: ...tems in which interruptions of operations due to dissolved or free gases The device provides the following safety features No direct intake of air thanks to a regulation of the pressure maintenance wi...

Страница 8: ...he spray pipe The DC feed during WC make up degassing to the vacuum spray tube VT is open Gas rich water is sprayed into the spray tube via a nozzle The system is set up so that the pump draws more wa...

Страница 9: ...ry make up request during continuous or interval degassing The make up volume is monitored via the make up time and the make up cycles Make up variants There are two make up variants for the device Th...

Страница 10: ...shipping document for the initial shipment and the content is shown on the packaging Immediately after receipt of the goods please check the shipment for completeness and damage Please notify us imme...

Страница 11: ...th the accessories and optional equipment 5 Technical data Note The following values apply for all systems Permissible operating temperature Permissible make up water operating temperature Permissible...

Страница 12: ...e work is not carried out correctly there is a risk of burns and other injuries at the connection points if pressurised hot water or hot steam suddenly escapes Ensure proper installation removal or ma...

Страница 13: ...n DN 15 according to DIN EN 1717 Electric connection 230 V 50 Hz 10 A with upstream RCD tripping current 0 03 A Note Shut off valves must be used at the connection point to the pipe network Note We re...

Страница 14: ...the facility system temperature The device is pre wired and must be adapted to match the local facility system conditions Proceed as follows 1 Complete the water side connections from the device to th...

Страница 15: ...ptional equipment and accessories see chapter 4 5 Optional equipment and accessories on page 10 6 DC degassing line degassed water Proceed as follows Connect the DC degassing lines in the V main volum...

Страница 16: ...WC make up line 3 Note Avoid a device fault Ensure that manual water make up to the facility system is possible Note Use a pressure reducer in the WC make up line if the idle pressure exceeds 6 bar 6...

Страница 17: ...egassing lines are connected close to the bladder expansion vessel This ensures that the pressure monitoring for water make up is provided 6 4 2 Level dependent Levelcontrol make up mode Operating mod...

Страница 18: ...ndard systems and are limited to the necessary user provided connections 1 Disconnect the system from the power source and secure it against unintentional reactivation 2 Remove the cover DANGER Risk o...

Страница 19: ...l via L N User optional 5 P4 3 6 WM1 Insufficient water external digital input User optional 7 WM2 4 8 K1 Contact water meter User optional 9 K2 5 10 24 V Conductivity analogue input 4 20 mA User opti...

Страница 20: ...n the operating manual The settings in the controller match the local conditions Note When any factory set values of the device are changed you must enter this information in the Maintenance certifica...

Страница 21: ...irectly entered together with the pressure dependent regulated make up at the Servitec device in systems with an expansion vessel via the Reflex Control Smart operating app The value is determined at...

Страница 22: ...ed During commissioning continuous degassing is automatically activated to remove any residual free or dissolved gases from the system The times for continuous and interval degassing can be set in the...

Страница 23: ...s completed interval degassing starts automatically Interval degassing This mode comprises repeating intervals There is an idling time between the intervals 8 1 2 Stop mode On the controller press Sto...

Страница 24: ...g operation Flashes during vacuum test 4 Stop button LED For stop mode Lights up yellow 5 Auto button LED For automatic mode Acknowledge error messages Lights up green 6 Error LED Lights up red if an...

Страница 25: ...ked 4 Check the system s pressure expansion vessel 06 100 Hz 02 1 Hz 03 1Hz 02 1 Insufficient water 1 Dirt trap clogged 2 Feed pipe blocked 1 Clean the dirt trap 2 Unblock the feed pipe check the make...

Страница 26: ...ontinuous stop 4 h 1 The system has been in stop mode for more than 4 hours Set the controller to automatic mode by pressing the Auto button on the system 06 100 Hz 04 Stop LED flashes 1 Hz 20 Make up...

Страница 27: ...due to pressurised liquid If installation removal or maintenance work is not carried out correctly there is a risk of burns and other injuries at the connection points if pressurised hot water or hot...

Страница 28: ...dirt trap in the degassing pipe must be cleaned no later than after the expiry of the continuous degassing time Check the dirt traps after every filling action or extended operation 1 Press Stop on t...

Страница 29: ...is secured and cannot be reactivated by other persons Ensure that installation work for the electric connection of the device is carried out by an electrician and in compliance with electrical engine...

Страница 30: ...the device Then disconnect the device from all electrical power sources Proceed as follows 1 Set the device controller to stop mode 2 Close the connections from the device for the degassing pipes 3 T...

Страница 31: ...llowing included materials are fully recyclable EPP housing ABS front cover of the controller PP back cover of the controller 13 Appendix 13 1 Reflex Customer Service Central customer service Switchbo...

Страница 32: ......

Страница 33: ......

Страница 34: ...SI1916enB 09 19 Reflex Winkelmann GmbH Gersteinstra e 19 59227 Ahlen Germany 49 0 2382 7069 0 49 0 2382 7069 9546 www reflex de...

Отзывы: