ER Code
Alarm
Floating contact
Cause
Remedy
Alarm reset
06
Makeup time
-
•
Set value exceeded.
•
Water loss in the system
•
Makeup line not connected.
•
Makeup rate insufficient.
•
Makeup hysteresis too low.
•
Check set value in the
Customer or Service
menu.
•
Check water level.
•
Connect "WC"
makeup line.
Quit
07
Makeup cycles
-
Set value exceeded.
•
Check set value in the
Customer or Service
menu.
•
Seal the leak in the
system.
Quit
08
Pressure
measurement
-
For "Magcontrol" setting only.
•
Controller receives incorrect
signal.
•
Connect the plug.
•
Check the cable for
damage.
•
Check the pressure
sensor.
Quit
10
Maximum pressure
-
For "Magcontrol" setting only.
•
Set value exceeded.
•
Check set value in the
Customer or Service
menu.
•
Set the tripping
pressure of the safety
valve.
-
11
Back-up volume
-
"With water meter" must be
activated in the Customer menu.
•
Set value exceeded.
•
Severe water loss in the
system.
•
Check set value in the
Customer or Service
menu.
•
Check the water loss
and correct, if
necessary.
Quit
14
Discharge period
-
•
Set value exceeded.
•
"DC" degassing line closed.
•
Dirt trap clogged.
•
Check set value in the
Customer or Service
menu.
•
Open the "DC"
degassing line.
•
Clean the dirt trap.
Quit
15
Makeup valve
-
Contact water meter measures
without makeup request.
Check the "CD" 3-ways ball
valve for leaks.
Quit
16
Power failure
-
No power.
Connect to power supply.
-