Disassembly
52 — English
Vacuum spray degassing — 06.07.2016 - Rev. B
Prior to the disassembly, lock out the "DC" degassing lines and the "WC" makeup line from the system and de-pressurise the device. Then
disconnect the device from all electrical power sources.
1. Disconnect the system from the power supply and secure it against unintended reactivation.
2. Lock out the "DC" degassing lines and the "WC" makeup line.
3. Set the device controller to manual mode, see chapter 8.1.2 "Manual mode" on page 35 .
4. Open the "CD" 3-ways motor ball valve until you have attained equal pressure with the ambient atmosphere.
5. Disconnect the power cable of the device from the power supply.
6. Disconnect all cables from the terminals of the device controller.
DANGER – Risk of serious injury or death due to electric shock. Some parts of the device's circuit board may still carry 230 V
voltage even with the device physically isolated from the power supply. Before you remove the covers, completely isolate the device
controller from the power supply. Verify that the main circuit board is voltage-free.
7. If necessary, remove the device from the system area.