Safety
Reflex ex separator — 21.11.2016
English — 5
1.3
Notes to personnel
Note!
Every person installing this equipment or performing any other work at the equipment is required to carefully read this
manual prior to commencing work and to comply with its instructions. The manual is to be provided to the device
operator and must be stored near the device for access at any time.
•
Modifications of the equipment are not permitted.
•
For example, welding at other points than the connection piece (in equipment with welded connection)
•
For example, mechanical deformations
•
Use only original parts provided by the manufacturer when replacing parts.
•
All required inspections must be ordered by the operator pursuant to the provisions of the applicable industrial safety regulations.
Required inspections and tests are:
•
Inspections and tests prior to commissioning
•
Inspections and tests after significant modifications of the installation
•
Recurring inspections
•
The devices to be installed and operated must not exhibit any visible exterior damage at the pressure component.
•
Ignoring this manual and the safety information in particular, may cause the destruction and defects of the equipment, endanger
persons and adversely affect the functioning. Any contravention voids the guarantee and liability.
1.4
Intended use
The device is a pressure maintaining station for heating and cooling water systems. It is intended for maintaining the water pressure,
water make-up and degassing of water in a system. The devices may be used only in systems that are sealed against corrosion and with
the following water types:
•
Non-corrosive
•
Chemically non-aggressive
•
Non-toxic
The ingress of atmospheric oxygen into the entire heating and cooling water system, make-up water, etc. must be reliably minimized
during operation.
Note!
•
To ensure fault-free operation of the system for the long-term, glycols whose inhibitors prevent corrosion
phenomena must always be used for systems operating with water/glycol mixtures.
•
The specifications of the respective manufacturer are always decisive for the specific properties and mixing ratio of
the water/glycol mixtures.
•
Types of glycol must not be mixed and the concentration is generally to be checked every year (see manufacturer
information).
Cooke Industries - Phone: +64 9 579 2185 Email: [email protected] Web: www.cookeindustries.co.nz
Содержание Exdirt
Страница 2: ...Cooke Industries Phone 64 9 579 2185 Email sales cookeindustries co nz Web www cookeindustries co nz...
Страница 14: ...Cooke Industries Phone 64 9 579 2185 Email sales cookeindustries co nz Web www cookeindustries co nz...
Страница 21: ...Cooke Industries Phone 64 9 579 2185 Email sales cookeindustries co nz Web www cookeindustries co nz...