background image

1

D

P

A2

A1

O1

MN

DV

%P

13

14

12

11

10

9

8

7

6

5

4

3

2

1

(49.5)

(49.5)

1.95

1.95

4.17 (105.9)

0.37

(9.4)

(44.7)

1.76

1.76 (44.7)

1.772

(45        )

1.772

(45        )

+0.024

-0.000

+0.6

-0.0

+0.024

-0.000

+0.6

-0.0

  

PID CONTROL WITH REDUCED OVERSHOOT

  

ON DEMAND AUTO-TUNING OF PID CONTROL SETTINGS

  

NEMA 4X/IP65 BEZEL 

  

DUAL LED DISPLAYS FOR SIMULTANEOUS INDICATION OF 

TEMPERATURE AND SETPOINT

  

STATUS INDICATORS FOR OUTPUTS AND CONTROL MODES

  

ACCEPTS 10 TYPES OF SENSOR INPUTS (Thermocouple or RTD)

  

OPTIONAL HEATER CURRENT MONITOR AND HEATER BREAK 

ALARM

  

OPTIONAL DUAL ALARM OUTPUTS

  

OPTIONAL TWO LINEAR DC OUTPUTS (0 to 10 V, 0/4 to 20 mA)

  

MANUAL/AUTOMATIC CONTROL MODES

  

SETPOINT RAMPING FOR PROCESS STARTUP

  

PROGRAMMABLE USER INPUT (Digital) FOR ADDED FLEXIBILITY

  

SENSOR ERROR COMPENSATION (Offset) AND BREAK 

DETECTION

  

HEATING AND OPTIONAL COOLING OUTPUTS

  

PARAMETER SECURITY VIA PROGRAMMABLE LOCKOUTS

  

FIELD REPLACEABLE OUTPUT BOARD 

(Relay or Logic/SSR Drive)

  

OPTIONAL TRIAC OUTPUT

  

SECOND SETPOINT SETTING  

  

OPTIONAL REMOTE SETPOINT INPUT (0/4 to 20 mA)

  

OPTIONAL RS485 SERIAL COMMUNICATIONS

  

PC SOFTWARE AVAILABLE FOR CONTROLLER CONFIGURATION

DESCRIPTION

The T48 Controller accepts signals from a variety of temperature sensors 

(thermocouple or RTD elements), precisely displays the process temperature, 

and provides an accurate output control signal (time proportional or linear DC) 

to maintain the process at the desired temperature. The controller’s 

comprehensive yet simple programming allows it to meet a wide variety of 

application requirements.

The controller operates in the PID control mode for both heating and cooling, 

with on-demand auto-tune, which will establish the tuning constants. The PID 

tuning constants may be fine-tuned by the operator at any time and then locked 

out from further modification. The controller employs a unique overshoot 

suppression feature, which allows the quickest response without excessive 

overshoot. The unit can be transferred to operate in the manual mode, providing 

the operator with direct control of the output. The controller may also be 

programmed to operate in the ON/OFF control mode with adjustable hysteresis. 

A second setpoint is available on select models to allow quick selection of a 

different setpoint setting.

Dual 4-digit displays allow viewing of the process temperature and setpoint 

simultaneously. Front panel indicators inform the operator of the controller and 

output status. On many models the main control output and the alarm outputs 

are field replaceable.

Optional alarm(s) can be configured to activate according to a variety of actions 

(Absolute HI or LO, Deviation HI or LO, Band IN or OUT, and Heater Current 

Break) with adjustable hysteresis. A standby feature suppresses the alarm during 

power-up until the temperature stabilizes outside the alarm region. The second 

alarm can be configured as a secondary PID output (heat/cool applications).

Optional Main Linear DC output (10 V or 20 mA) can be used for control or 

temperature re-transmission purposes. Programmable output update time 

reduces valve or actuator activity. The output range can be scaled independent 

of the input range.

Optional Second Linear DC output (10 V or 20 mA) provides an independent 

temperature re-transmission, while the main Linear DC output is being used for 

control. The output range can be scaled independent of the input range.

Optional Heater Current Monitor provides a direct readout of process heater 

current. An alarm can be programmed to signal when the heater has failed. This 

provides early warning of system failure before product quality is affected.

MODEL T48 - 1/16 DIN TEMPERATURE CONTROLLER

DIMENSIONS  In inches (mm)

PANEL CUT-OUT

CAUTION: Risk of Danger.

Read complete instructions prior to 

installation and operation of the unit.

CAUTION: 

Risk of electric shock.

Bulletin No.  T48-H
Drawing No.  LP0332
Released  08/13

Tel +1 (717) 767-6511
Fax +1 (717) 764-0839
www.redlion.net

UL Recognized Component, 

File # E156876 

Содержание T48

Страница 1: ...esponse without excessive overshoot The unit can be transferred to operate in the manual mode providing the operator with direct control of the output The controller may also be programmed to operate in the ON OFF control mode with adjustable hysteresis A second setpoint is available on select models to allow quick selection of a different setpoint setting Dual 4 digit displays allow viewing of th...

Страница 2: ...ROLS Four front panel push buttons for modification and setup of controller functions and one external input user for parameter lockout or other functions 4 MEMORY Nonvolatile E2 PROM retains all programmable parameters and values 5 MAIN SENSOR INPUT Sample Period 100 msec Response Time Less than 300 msec typ 400 msec max to within 99 of final value w step input typically response is limited to re...

Страница 3: ...e 300 to 9600 Data Format 7O1 7E1 7N2 8N1 Node Address 0 99 max of 32 units per line Transmit Delay 2 100 msec or 100 200 msec Data Encoding ASCII Isolation w r t Main Input Common 500 Vrms for 1 min 50 V working Not isolated w r t Remote Setpoint or Heater Current inputs or Analog Output common Note RS485 and the Analog Output commons are not internally isolated within the controller The terminat...

Страница 4: ...on The output can be set for 0 to 10 V 0 to 20 mA or 4 to 20 mA ranges and can be configured for control or for transmission of temperature or setpoint values A Second Linear DC output is dedicated for retransmission of input temperature The output can be scaled and converted independent of the input and Main Linear DC output This output is isolated from the input SETPOINT FEATURES The controller ...

Страница 5: ...t higher limit SPrP Enter setpoint ramp rate InPt Select user input function Configuration 2 Outputs 2 OP CYCt Enter time proportioning cycle time OPAC Select output control action OPLO Enter output power low limit OPHI Enter output power high limit OPFL Enter probe fail power preset OPdP Enter output control dampening CHYS Enter ON OFF control hysteresis tcOd Select auto tuning dampening ANtP Mai...

Страница 6: ... the Heater Current Monitor Part Number CT005001 Current Ratio 50 0 1 Amperes Operation Frequency 50 to 400 Hz Insulation Class 0 6 KV BIL 10 KV full wave Terminals Brass studs No 8 32 UNC with flat washer and hex nuts Window Diameter 1 13 28 7 mm Weight 8 oz 226 0 g 1 2 3 4 5 6 7 8 9 10 13 14 12 11 2 39 60 7 MAX 1 96 49 8 MAX PANEL LATCH INSTALLED FOR VERTICAL UNIT STACKING HORIZONTAL UNIT STACKI...

Страница 7: ... than 12 outside the manufacturer s specifications of 140 to 150 F 11 12 14 13 10 9 8 7 6 5 4 3 2 1 USER INPUT COMM TC RTD AL2 O2 COMM AL1 O1 N O COMM AC POWER 85 250 VAC AC POWER POWER AC NO GO GO 13 14 12 11 10 9 8 7 6 5 4 3 2 1 OUT OUT 02 A2 COMM 01 A1 USER INPUT COMM TC RTD IN IN SLAVE CONTROLLER 1 TC COMM 4 9 01 A1 5 MASTER CONTROLLER 11 12 10 RTD IN 02 A2 OUT OUT 3 2 1 USER INPUT 13 14 IN 8 ...

Страница 8: ...OG OUTPUT HEATER CURRENT INPUT DEDICATED MAIN CONTROL O1 OUTPUT DEDICATED ALARM 1 A1 OUTPUT RS485 This output is programmable as either Control PID or as an Alarm This output is jumper and program selectable for either a current or voltage Linear DC output These part numbers are equipped with a second setpoint 1 Replacement Output Board RBD48100 may be used 2 Replacement Output Board RBD48111 may ...

Отзывы: