Heater break alarm

Reset Action

: Programmable; automatic or latched

Standby Mode

: Programmable; enable or disable

Hysteresis

:

 

Programmable

Probe Break Action

: Upscale

Annunciator

: LED backlight for “A1”, “A2”

13. 

COOLING:

 Software selectable (overrides alarm 2)

Control

: PID or ON/OFF

Output

: Time Proportioning

Cycle time

: Programmable

Proportional Gain Adjust

: Programmable

Heat/Cool Deadband Overlap

: Programmable

14. 

MAIN AND SECOND LINEAR DC OUTPUT: 

(optional)

Self-powered (active)

Main

: Control or Re-transmission, programmable update rate from 0.1 sec to 

250 sec

Second

: Re-transmission only, fixed update rate of 0.1 sec

* Accuracies are expressed as 

±

 percentages after 20 minutes warm-up. Output 

accuracy is specified in two ways: Accuracy over an 18 to 28°C range at 10 

to 75% RH environment; and accuracy over a 0 to 50°C range at 0 to 85% 

RH (non-condensing) environment. Accuracy over the wide temperature 

range reflects the temperature coeffecient of the internal circuitry.

** Outputs are independently jumper selectable for either 10 V or 20 mA. The 

output range may be field calibrated to yield approximately 10% overrange 

and a small underrange (negative) signal.

15. 

REMOTE SETPOINT INPUT: 

(optional)

Input type

:

0/4 to 20 mA

Input Resistance

: 10 

Overrange

: -5% to 105%

Overload

: 100 mA (continuous)

Scale Range

: -999 to 9999 degrees or -99.9 to 999.9 degrees.

Resolution

: 1 part in 10,000.

Accuracy

:

At 25

°

 C

±

(0.1 % of full scale +

½

 LSD) 

Over 0 to 50

°

C range

±

(0.2% of full scale +

½

 LSD)

Reading Rate

: 10/sec.

Setpoint Filtering

: Programmable Digital

Setpoint Ramping

: Programmable, 0.1 to 999.9 degrees/minute.

16. 

HEATER CURRENT MONITOR INPUT: 

(optional)

Type

: Single phase, full wave monitoring of load currents controlled by main 

output (01).

Input

: 100 mA AC output from current transformer (RLC #CT004001) or 

any CT with 100 mA AC output.

Display Scale Range

:

 

1.0 to 999.9 Amps or 0.0 to 100.0%

Input Resistance

: 5 

Accuracy

At 25

°

 C

±

(0.5 % of full scale +

½

 LSD), (5 to 100% of Range)

Over 0 to 50

°

C range

±

(1.0% of full scale +

½

 LSD), (5 to 100% of Range)

Frequency

: 50 to 400 Hz.

Alarm Mode

: Dual acting; heater element fail detect and control device fail 

detect.

Overrange

: 105% Capacity

Overload

: 200 mA (continuous).

17. 

SERIAL COMMUNICATIONS: 

(optional)

Type

: RS485 multipoint, balanced interface

Baud Rate

: 300 to 9600

Data Format

: 7O1, 7E1, 7N2, 8N1

Node Address

: 0-99, max of 32 units per line

Transmit Delay

: 2-100 msec or 100-200 msec

Data Encoding

:

 

ASCII

Isolation w.r.t Main Input Common

: 500 Vrms for 1 min. (50 V working)

Not isolated w.r.t. Remote Setpoint or Heater Current inputs, or Analog 

Output common

Note:

 

RS485 and the Analog Output commons are not internally isolated 

within the controller. The terminating equipment of these outputs must not 

share the same common (ie. earth ground).

18. 

ENVIRONMENTAL CONDITIONS:

Operating Range

: 0 to 50°C

Storage Range

: -40 to 80°C

Span Drift 

(max.)

: 130 ppm/°C, main input

Zero Drift 

(max.)

: 1µV/°C, main input

Operating and Storage Humidity

:

85% max. relative humidity (non-condensing) from 0°C to 50°C.

Vibration to IEC 68-2-6

: Operational 5 to 150 Hz, 2 g.

Shock to IEC 68-2-27

: Operational 20 g (10 g relay).

Altitude

: Up to 2000 meters

19. 

ISOLATION BREAKDOWN RATINGS:

AC line with respect to all Inputs and outputs

: 250 V working (2300 V for 

1 minute).

Main input with respect to Analog Outputs, Remote Setpoint Input, 

Heater Current Input

: 50 V working (2300 V for 1 minute).

All other inputs and outputs with respect to relay contacts

: 2000 VAC

Not isolated between Analog Outputs, Remote Setpoint and Heater Current 

commons.

20. 

CERTIFICATIONS AND COMPLIANCES:

CE Approved

EN 61326-1 Immunity to Industrial Locations

Emission CISPR 11 Class A

IEC/EN 61010-1

RoHS Compliant

UL Recognized Component: File #E156876

Type 4X Enclosure rating (Face only)

IP65 Enclosure rating (Face only)

IP20 Enclosure rating (Rear of unit)

Refer to EMC Installation Guidelines section of the manual for additional 

information.

21. 

CONNECTION:

 Wire clamping screw terminals

22. 

CONSTRUCTION:

 Black plastic alloy case and collar style panel latch. Panel 

latch can be installed for vertical or horizontal instrument stacking. One piece 

tinted plastic bezel. Bezel assembly with circuit boards can be removed from the 

case to change the output board without removing the case from the panel or 

disconnecting wiring. Unit meets NEMA 4X/IP65 requirements for indoor use, 

when properly installed. Installation Category II, Pollution Degree 2.

23. 

WEIGHT:

 0.38 lbs (0.17 kgs)

3

OUTPUT ** 

RANGE

ACCURACY * 

(18 to 28°C)

ACCURACY * 

(0 to 50°C)

COMPLIANCE RESOLUTION

0 to 10 V

0.10% of FS 

+ 1/2 LSD

0.30% of FS 

+ 1/2 LSD

10k ohm min.

1/3500

0 to 20 mA

0.10% of FS 

+ 1/2 LSD

0.30% of FS 

+ 1/2 LSD

500 ohm max.

1/3500

4 to 20 mA

0.10% of FS 

+ 1/2 LSD

0.30% of FS 

+ 1/2 LSD

500 ohm max.

1/2800

Содержание T48

Страница 1: ...esponse without excessive overshoot The unit can be transferred to operate in the manual mode providing the operator with direct control of the output The controller may also be programmed to operate in the ON OFF control mode with adjustable hysteresis A second setpoint is available on select models to allow quick selection of a different setpoint setting Dual 4 digit displays allow viewing of th...

Страница 2: ...ROLS Four front panel push buttons for modification and setup of controller functions and one external input user for parameter lockout or other functions 4 MEMORY Nonvolatile E2 PROM retains all programmable parameters and values 5 MAIN SENSOR INPUT Sample Period 100 msec Response Time Less than 300 msec typ 400 msec max to within 99 of final value w step input typically response is limited to re...

Страница 3: ...e 300 to 9600 Data Format 7O1 7E1 7N2 8N1 Node Address 0 99 max of 32 units per line Transmit Delay 2 100 msec or 100 200 msec Data Encoding ASCII Isolation w r t Main Input Common 500 Vrms for 1 min 50 V working Not isolated w r t Remote Setpoint or Heater Current inputs or Analog Output common Note RS485 and the Analog Output commons are not internally isolated within the controller The terminat...

Страница 4: ...on The output can be set for 0 to 10 V 0 to 20 mA or 4 to 20 mA ranges and can be configured for control or for transmission of temperature or setpoint values A Second Linear DC output is dedicated for retransmission of input temperature The output can be scaled and converted independent of the input and Main Linear DC output This output is isolated from the input SETPOINT FEATURES The controller ...

Страница 5: ...t higher limit SPrP Enter setpoint ramp rate InPt Select user input function Configuration 2 Outputs 2 OP CYCt Enter time proportioning cycle time OPAC Select output control action OPLO Enter output power low limit OPHI Enter output power high limit OPFL Enter probe fail power preset OPdP Enter output control dampening CHYS Enter ON OFF control hysteresis tcOd Select auto tuning dampening ANtP Mai...

Страница 6: ... the Heater Current Monitor Part Number CT005001 Current Ratio 50 0 1 Amperes Operation Frequency 50 to 400 Hz Insulation Class 0 6 KV BIL 10 KV full wave Terminals Brass studs No 8 32 UNC with flat washer and hex nuts Window Diameter 1 13 28 7 mm Weight 8 oz 226 0 g 1 2 3 4 5 6 7 8 9 10 13 14 12 11 2 39 60 7 MAX 1 96 49 8 MAX PANEL LATCH INSTALLED FOR VERTICAL UNIT STACKING HORIZONTAL UNIT STACKI...

Страница 7: ... than 12 outside the manufacturer s specifications of 140 to 150 F 11 12 14 13 10 9 8 7 6 5 4 3 2 1 USER INPUT COMM TC RTD AL2 O2 COMM AL1 O1 N O COMM AC POWER 85 250 VAC AC POWER POWER AC NO GO GO 13 14 12 11 10 9 8 7 6 5 4 3 2 1 OUT OUT 02 A2 COMM 01 A1 USER INPUT COMM TC RTD IN IN SLAVE CONTROLLER 1 TC COMM 4 9 01 A1 5 MASTER CONTROLLER 11 12 10 RTD IN 02 A2 OUT OUT 3 2 1 USER INPUT 13 14 IN 8 ...

Страница 8: ...OG OUTPUT HEATER CURRENT INPUT DEDICATED MAIN CONTROL O1 OUTPUT DEDICATED ALARM 1 A1 OUTPUT RS485 This output is programmable as either Control PID or as an Alarm This output is jumper and program selectable for either a current or voltage Linear DC output These part numbers are equipped with a second setpoint 1 Replacement Output Board RBD48100 may be used 2 Replacement Output Board RBD48111 may ...